4
Configuration
4.1
Signal output delay
Figure 4-1: Delay Timers for Signal Output Change
3
A
B
6
10
20
30
60
0
1
2
3
6
10
20
0
A. Delay timer in seconds - for the switchover from a covered-to-uncovered
paddle state. Factory default is 3 seconds.
B. Delay timer in seconds - for the switchover from an uncovered-to-covered
paddle state. Factory default is 1 second.
4.2
Jumper Settings for Fail Safe High or Low
Use the FSH setting when the level switch is to be applied as a full-silo
detector. A power failure or line break is regarded as a full-silo signal (as
protection against overfilling).
Use the FSL setting when the level switch is to be applied as an empty-silo
detector. A power failure or line break is regarded as empty-silo signal (as
protection against running dry).
Figure 4-2: Jumper Settings for FSH or FSL
B
A
C
A. Jumper setting for enabling FSL (factory default)
B. Jumper setting for enabling FSH