Ensure the screwed cable gland safely seals the cable and is tight enough to
prevent water ingress. Unused conduit or cable entries must be sealed with a
stopping (blanking) plug.
A strain relief must be provided for the field wiring cables when the device is
installed with the factory-provided cable glands.
3.2.8
Conduit system
When a threaded conduit system is used instead of a cable gland, the
regulations of the country must be observed. The conduit must have a
½
-in.
NPT tapered thread to match a NPT threaded conduit entry of the level
switch and comply with ANSI B 1.20.1. Unused conduit entries must be
closed tightly with a metal stopping (blanking) plug.
3.2.9
Micro-switch protection
Provide protection for micro-switch contacts to protect the device against
inductive load surges.
3.2.10 Static charging
The Rosemount 2501 must be grounded to avoid a static electrical build-up.
This is particularly important for applications with pneumatic conveying and
non-metallic containers.
3.2.11 Commissioning
Commissioning must be performed with closed lid.
3.3
Wiring the level switch
Wiring connections are done directly on the PCB.
Figure 3-1: PCB Connections
7 6 5
1 2
A
A
B
C
A. Connection terminals for power supply and signal outputs
B. The motor is internally connected to the housing (grounded)
C. Protective Earth (PE) terminal