Accuracy over measuring range
The measuring range is limited at the very top of the tank according to
.
Figure A-1: Accuracy Over Measuring Range
±0.08 in.
(±2 mm)
±0.4 in.
(±10 mm)
0.8 in. (20 mm)
5.9 in. (150 mm)
A
B
A. Accuracy
B. Distance
A.1.3
Environment
Vibration resistance
•
2 g at 10-1000 Hz according to IEC 61298-3, level “field with general application”
Electromagnetic compatibility (EMC)
•
EMC Directive (2014/30/EU): EN 61326-1
•
NAMUR recommendations NE21 (only 4-20 mA output)
Pressure Equipment Directive (PED)
Complies with 2014/68/EU article 4.3
Radio approvals
•
Radio Equipment Directive (2014/53/EU): ETSI EN 302 372 (TLPR) and EN 62479
•
Part 15 of the FCC Rules
•
Industry Canada RSS 211
Specifications and reference data