7.3.7
Lagging of measured level
Symptom
Measured level lags during rapid level changes.
Figure 7-7: Symptom
A
B
C
D
A. Level
B. Time
C. Actual level
D. Reported level
Possible cause
Damping value is set too high.
Recommended actions
•
If there is a problem with lag during rapid level changes, consider decreasing the
Damping value.
Related information
Service and troubleshooting
Reference Manual
September 2020
00809-0100-4480
58
Rosemount 1408H Level Transmitter