Reference Manual
00809-0100-4631, Rev BA
April 2007
5-7
Rosemount 1154 Series H
TROUBLESHOOTING
Table 5-3. Troubleshooting.
Symptom
Potential Source
Corrective Action
High Output
Primary Element
Check for restrictions at primary element, improper installation or poor condition. Note any changes
in process fluid properties.
Impulse Piping
Check for leaks or blockage.
Ensure that blocking valves are fully open.
Check for entrapped gas in liquid lines and for liquid in dry lines.
Ensure that density of fluid in impulse lines is unchanged.
Check for sediment in the transmitter process flanges.
Transmitter Electronics
Make sure that post connectors and the sensor connections are clean.
If the electronics are still suspect, substitute new electronics.
Transmitter Electronics
Failure
Determine faulty circuit board by trying spare boards. Replace faulty circuit board.
Sensing Module
See sensing module checkout section. The sensing module is not field repairable and must be
replaced if found to be defective. See “Disassembly Procedure” for instructions on disassembly. Check
for obvious defects, such as punctured isolating diaphragm or fill fluid loss, and contact Rosemount
Nuclear Instruments, Inc. at 952-949-5210.
Power Supply
Check the power supply output voltage at the transmitter.
Low Output or
No Output
Primary Element
Check for restrictions at primary element, improper installation or poor condition. Note any changes
in process fluid properties.
Loop Wiring
Check for adequate voltage to the transmitter.
Check the milliamp rating of the power supply against the total current being drawn for all transmitters
being powered.
Check for shorts and multiple grounds.
Check for proper polarity at the signal terminal.
Check loop impedance.
Check wire insulation to detect possible shorts to ground.
Impulse Piping
Ensure that the pressure connection is correct.
Check for leaks or blockage.
Check for entrapped gas in liquid lines.
Check for sediment in the transmitter process flange.
Ensure that blocking valves are fully open and that bypass valves are tightly closed.
Ensure that density of the fluid or other fluid properties in the impulse piping are unchanged.
Transmitter Electronics
Connections
Ensure that calibration adjustments are in allowable range.
Check for shorts in sensor leads.
Make sure post connectors are clean, and check the sensor connections.
If the electronics are still suspect, substitute new electronics.
Test Diode Failure
Replace electronics housing.
Transmitter Electronics
Failure
Determine faulty circuit board by trying spare boards. Replace faulty circuit board.
Sensing Module
See sensing module checkout section. The sensing module is not field repairable and must be
replaced if found to be defective. See “Disassembly procedure” for instructions on disassembly. Check
for obvious defects, such as punctured isolating diaphragm or fill fluid loss, and contact Rosemount
Nuclear Instruments, Inc. at 952-949-5210.
Power Supply
Check the power supply output voltage at transmitter.
Continued On Next Page
Do not use over 100 volts to check the loop, or damage to the transmitter electronics
may result.
Содержание Rosemount 1154DH
Страница 6: ...Reference Manual 00809 0100 4631 Rev BA April 2007 Rosemount 1154 Series H 1 2 ...
Страница 10: ...Reference Manual 00809 0100 4631 Rev BA April 2007 Rosemount 1154 Series H TOC 4 ...
Страница 12: ...Reference Manual 00809 0100 4631 Rev BA April 2007 Rosemount 1154 Series H 1 2 ...
Страница 52: ...Reference Manual 00809 0100 4631 Rev BA April 2007 Rosemount 1154 Series H 6 10 ...
Страница 55: ......