Reference Manual
00809-0100-4302, Rev BA
January 2008
2-3
Rosemount 1153 Series B
The Swagelok tube fittings are shipped completely assembled for immediate
use.
Do not disassemble them before use
; doing so may contaminate the
fittings and result in leaks. Insert the tubing into the Swagelok tube fitting,
making sure that the tubing rests firmly on the shoulder of the fitting and that
the nut is finger tight. Tighten the nut one-and-one-quarter turns past finger
tight to prepare the transmitter for use.
Do not overtighten
.
The connections can be loosened and re-tightened 20-30 times without
compromising the leak proof seal. To reconnect, insert the tubing with
pre-swaged ferrules into the fitting until the front ferrule sits in the fitting.
Tighten the nut by hand, then rotate one-quarter turn more or to the original
one-and-one-quarter tight position. Then snug the nut slightly with a wrench.
For more information regarding the use of Swagelok tube fittings, refer to:
Fittings Catalog MS-01-140
“Gaugable Tube Fitting and Adapter Fittings”
www.swagelok.com
If the drain/vent valves must be opened to bleed process lines, torque them to
7.5 ft-lb (10 N-m) when closing.
Proper location of the transmitter with respect to the process tubing depends
on various process parameters. When determining the best location, consider
the following:
•
Keep hot or corrosive fluids from contacting the transmitter.
•
Prevent sediment from depositing in the impulse tubing.
•
Ambient temperature gradients and fluctuations can result in erroneous
transmitter readings.
•
Keep impulse tubing as short as possible.
•
For differential transmitters, balance the liquid head on both legs of the
impulse tubing.
•
For liquid flow or pressure measurements, make taps on the side of the
line to avoid sediment deposits, and mount the transmitter beside or
below the taps so gases vent into the process line (see Figure 2-6 on
page 2-11).
•
For gas flow or pressure measurements, make taps on the top or side
of the line and mount the transmitter beside or above the taps so liquid
drains into the process line (see Figure 2-6 on page 2-11).
•
For steam flow or pressure measurements, make taps on the side of
the line, and mount the transmitter below the taps so the impulse tubing
stays filled with condensate (See Figure 2-6 on page 2-11).
•
For steam service, fill the lines with water to prevent steam from
contacting the transmitter. Condensate chambers are not necessary
since the volumetric displacement of the transmitter
is negligible.
Содержание Rosemount 1153 Series B
Страница 6: ...Reference Manual 00809 0100 4302 Rev BA January 2008 Rosemount 1153 Series B iv ...
Страница 9: ...Reference Manual 00809 0100 4302 Rev BA January 2008 TOC 3 Rosemount 1153 Series B ...
Страница 10: ...Reference Manual 00809 0100 4302 Rev BA January 2008 Rosemount 1153 Series B TOC 4 ...
Страница 12: ...Reference Manual 00809 0100 4302 Rev BA January 2008 Rosemount 1153 Series B 1 2 ...
Страница 50: ...Reference Manual 00809 0100 4302 Rev BA January 2008 Rosemount 1153 Series B 5 12 ...
Страница 62: ...Reference Manual 00809 0100 4302 Rev BA January 2008 Rosemount 1153 Series B Index 2 ...
Страница 63: ......