PACSystems™ RSTi
-EP EPSCPE100 Standalone CPU Quick Start Guide
GFK-3012E
Programming the CPE100
To configure the CPE100, connect the computer running the PME programming
software to an Ethernet port of LAN1 using the default IP address 192.168.0.100. PME
9.5 SIM 1 or later is required.
Configuration will either start out using the RSTi-EP CPE100 template when creating
a new project or will convert an existing project to the CPE100 using the
Family
Conversion
feature in PME.
Backwards Compatibility
To convert an existing project which uses any other PLC, use the Family Conversion
feature in PME. Be aware of the constraints involved, as will be notified in PME. For
instance, the first PROFINET Controller in an RX3i CPU320 application will be assigned
to the embedded PROFINET Controller feature of the CPE100.
PROFINET Controller Configuration
An Embedded PROFINET Controller may be configured on LAN2. To enable the
PROFINET Controller in a CPE100 project, select the CPE100 target in the PME
Navigator (Figure 11) and open the Hardware Configuration.
On the Settings tab, change the LAN2 Mode of the selected port to PROFINET. The
PROFINET Controller node description then displays that a PROFINET node exists on
the selected LAN (under the CPE100). For further details, refer to the PACSystems
RX3i & RSTi-EP PROFINET IO-Controller User Manual, GFK-2571.