NetSure
™
-48V DC Power System
Quick Start Guide, QS582127000 (Issue AC, December 10, 2013)
Spec. No: 582127000
Code: QS582127000
Model No: 721
NPBB
Issue AC, December 10, 2013
[58]
Figure 47.
List BF: Battery Disconnect Distribution Panel,
(2) TPH Fuse Battery Disconnect Positions (with Shunts) (without Return Busbar)
Figure 48.
List BG: Battery Disconnect Distribution Panel,
(4) TPH Fuse Battery Disconnect Positions (without Shunts) (without Return Busbar)
-48VDC Battery
Connections
BATTERY CONNECTIONS
3/8-16 Captive Nuts on 1” Centers
Maximum Lug Width: 1.88 inches.
(Customer must supply
or order additional
hardware)
Observe proper polarity
when making battery
connections.
WARNING!
For an 800A fuse,
load must not exceed 600A.
-48VDC Battery
Connections
BATTERY CONNECTIONS
3/8-16 Captive Nuts on 1” Centers
(Customer must supply
or order additional
hardware)
Observe proper polarity
when making battery
connections.
WARNING!
Maximum Lug Width: 1.75 inches.
Maximum fuse size is 400A.