![background image](http://html.mh-extra.com/html/emerson/netsur-721npbb/netsur-721npbb_quick-start-manual_104048065.webp)
NetSure
™
-48V DC Power System
Quick Start Guide, QS582127000 (Issue AC, December 10, 2013)
Spec. No: 582127000
Code: QS582127000
Model No: 721
NPBB
Issue AC, December 10, 2013
[57]
Figure 45.
List BC: Battery Disconnect Distribution Panel (with Return Busbar) and
List BD: Battery Disconnect Distribution Panel (without Return Busbar),
(4) GJ/218 Circuit Breaker Battery Disconnect Positions
Figure 46.
List BE: Battery Disconnect Distribution Panel,
(2) TPH Fuse Battery Disconnect Position (without Shunts) (without Return Busbar)
-48VDC Battery
Connections
Battery Return
Connections
BATTERY AND BATTERY RETURN CONNECTIONS
3/8-16 Captive Nuts on 1” Centers
(Customer must supply
or order additional
hardware)
Maximum Lug Width:
1.375 inches.
Return Busbar
(not included
with List BD)
Observe proper polarity
when making battery
connections.
WARNING!
For an 800A circuit breaker,
load must not exceed 600A.
-48VDC Battery
Connections
BATTERY CONNECTIONS
3/8-16 Captive Nuts on 1” Centers
Maximum Lug Width: 1.88 inches.
(Customer must supply
or order additional
hardware)
Observe proper polarity
when making battery
connections.
WARNING!
For an 800A fuse,
load must not exceed 600A.