8
Functional Safety Manual
M310/FSM, Rev BA
Designing a Safety Function Using the Level Switch
April 2017
Designing a Safety Function Using the Level Switch
Each subsystem must be checked to assure compliance with minimum Hardware Fault Tolerance
(HFT) requirements. When using the level switch in a redundant configuration, a common cause
factor of at least 5% should be included in the safety integrity calculations.
The failure rate data listed in the FMEDA report is only valid for the useful lifetime of the level switch.
Failure rates increase after this useful lifetime period has expired. Reliability calculations based on
the data listed in the FMEDA report for mission times beyond the lifetime may yield results that are
too optimistic, i.e. the calculated SIL will not be achieved.
3.5
SIL capability
3.5.1
Systematic integrity
The Mobrey level switch has met manufacturer design process requirements of Safety Integrity
Level 2 (SIL 2). These are intended to achieve sufficient integrity against systematic errors of design
by the manufacturer.
A Safety Instrumented Function (SIF) designed with the Mobrey level switch must not be used at a
SIL higher than the statement without “prior use” justification by the end-user, or verification of
diverse technology in the design.
3.5.2
Random integrity
The Mobrey level switch is a type A device according to Table 2 of the standard IEC 61508-2.
Using Route 2H assessment criteria, the device Random Capability has been determined as SIL 2.
3.5.3
Safety parameters
The failure rates given here are valid for the useful lifetime of the product, as described in the section
.
Note
The FMEDA report is available from the Mobrey Magnetic Horizontal Float Switches web site page at
. In the Documents section, there are SIL documents including the FMEDA
report and this safety manual.
Table 3-1. Failure Rates for Level Switch, 4-contact Versions – Types D and P
Failure category
Failure rate (FIT)
(1)
1.
FIT is the abbreviation for Failure In Time. One FIT is 1x10
-9
failure per hour.
Maximum detection
Minimum detection
Fail Safe Detected
0
0
Fail Safe Undetected
88
117
Fail Dangerous Detected
0
0
Fail Dangerous Undetected
243
214
No Effect
34
34
Содержание Mobrey Series
Страница 2: ......
Страница 8: ...4 Functional Safety Manual M310 FSM Rev BA Introduction April 2017 Introduction ...
Страница 18: ...14 Functional Safety Manual M310 FSM Rev BA Operation and Maintenance April 2017 Operation and Maintenance ...
Страница 20: ...Proposed Proof test Procedure April 2017 Functional Safety Manual M310 Rev BA Proposed Proof test Procedure 16 ...
Страница 25: ......