37
Reference Manual
24625020, Rev AA
Installing the Electronics Control Unit
March 2017
Installing the Electronics Control Unit
Figure 3-15. Power Supply Connections
A. Connector on printed circuit board (PCB): PL101 (Channel 1) and PL301 (Channel 2).
B. Power connector.
C. Shroud half-shell.
D. Cable clamp.
3.5.5
Connecting the prepared cables to the front panel
The following procedure assumes that:
Front panel PCB ‘jumpers’ have been set for all required options,
as guided in
“Setting the printed circuit board (PCB) jumpers” on page 23
Cables have been suitably prepared, as guided in previous pages.
Connecting the cables procedure
1.
Take the front panel and plug the cables for Hydratect channels 1 and 2 into the
relevant connectors on the PCB, referring to
.
2.
Connect the ground (earth) bonding lead from the case to the grounding
(earthing) point on the front panel.
3.
Fit the front panel of the Control Unit into the case, ensuring that no cable
conductors are trapped between panel and case.
4.
Secure the front panel with the four screws and four washers.
Ensure that the four washers make complete contact with the metalwork of the front panel.
The label (art work) on the front panel must not be trapped under these washers.
The Hydratect 2462 system is ready for testing, as described in
.
A
D
C
B
230 Vac
L
Not connected
N
L
N
Not connected
115 Vac
20 to 60 Vdc
+ve
Not connected
-ve
1
2
3
Содержание Mobrey Hydratect 2462
Страница 1: ...Reference Manual 24625020 Rev AA March 2017 Mobrey Hydratect 2462 Steam Water Detection System ...
Страница 2: ......
Страница 16: ...10 Reference Manual 24625020 Rev AA Introduction March 2017 Introduction ...
Страница 26: ...20 Reference Manual 24625020 Rev AA Installing the electrodes March 2017 Installing the electrodes ...
Страница 52: ...46 Reference Manual 24625020 Rev AA System Testing March 2017 System Testing ...
Страница 62: ...56 Reference Manual 24625020 Rev AA Electronics Servicing March 2017 Electronics Servicing ...
Страница 65: ......