Installing the Electronics Control Unit
March 2017
Installing the Electronics Control Unit
If the installation is adversely affected by the operation of nearby equipment, then
re-routing the cables to these instructions should improve performance:
Avoid bundling the cables together.
Ensure that cables run against earthed (grounded) metalwork, where possible.
Use shielded (screened) cables for all connections, making sure a good annular
(ring shaped) contact is made with a good quality RF cable gland.
Do not run cables over the PCB, where possible.
Figure 3-16. Connector Locations on Front Panel PCB
A. Connector for plugging in fault and status outputs, and status reset input cable.
B. Connector for plugging in power supply connection cable.
C. Grounding (earthing) point.
D. Connector for plugging in electrode cable.
Hydratect Channel 2
Hydratect Channel 1
PL404
PL204
PL101
PL201
PL406
PL206
PL403
PL203
PL405
PL205
A
D
B
C