Restriction
This feature is available only with a HART 7 host.
Procedure
1. Enable event notification.
2. Select all desired alerts.
If one or more of the selected alerts occurs, each active burst message will broadcast HART Command
119 until the alert is acknowledged by a HART master.
3. Set
Trigger Interval
as desired.
Trigger Interval
controls the delay before HART Command 119 is broadcast.
•
Default: 0 seconds
•
Range: 0.5 to 3600 seconds
Trigger Interval
begins when the transmitter detects the alert condition. When
Trigger Interval
expires:
•
If the alert is still active, HART Command 119 is broadcast.
•
If the alert is not active, no message is broadcast.
Tip
If you set
Trigger Interval
to 0, HART Command 119 is broadcast as soon as the alert is detected.
4. Set
Retry Rate
as desired.
Retry Rate
controls the rate at which HART Command 119 is broadcast when event notification is
active.
•
Default: 0.5 seconds
5. Set
Maximum Update Time
as desired.
Maximum Update Time
controls the rate at which HART Command 119 is broadcast when event
notification is not active.
•
Default: 60 seconds
10.6 Configure Modbus communications
ProLink III
Device Tools
→
Configuration
→
Communications
→
Communications (Modbus)
Field communicator
Not available
Modbus communications parameters control Modbus communications with the transmitter.
Modbus support is implemented on the RS-485 physical layer via the RS-485 terminals.
Important
Your device automatically accepts all connection requests within the following ranges:
•
Protocol: Modbus RTU (8-bit) or Modbus ASCII (7-bit) unless
Modbus ASCII Support
is disabled
Integrate the meter with the control system
Configuration and Use Manual
March 2021
MMI-20020954
100