Procedure
1. Select the event that you want to configure.
2. Assign a process variable to the event.
3. Specify
Event Type
.
Option
Description
HI
x
> A
The event occurs when the value of the assigned process variable (
x
) is greater
than the setpoint (
Setpoint A
), endpoint not included.
LO
x
< A
The event occurs when the value of the assigned process variable (
x
) is less than
the setpoint (
Setpoint A
), endpoint not included.
IN
A ≤
x
≤ B
The event occurs when the value of the assigned process variable (
x
) is
in range,
that is, between
Setpoint A
and
Setpoint B
, endpoints included.
OUT
x
≤ A or
x
≥ B
The event occurs when the value of the assigned process variable (
x
) is
out of
range,
that is, less than
Setpoint A
or greater than
Setpoint B
, endpoints
included.
4. Set values for the required setpoints.
•
For HI and LO events, set
Setpoint A
.
•
For IN and OUT events, set
Setpoint A
and
Setpoint B
.
5. Optional: Configure a Discrete Output to switch states in response to the event status.
6. Optional: Specify the action or actions that the transmitter will perform when the event occurs.
•
Using the display: Choose
Menu
>
Configuration
>
Alert Setup
>
Enhanced Events
, select any
enhanced event, and choose
Assign Actions
. Then assign the desired action to the desired
enhanced event.
•
Using ProLink III: Choose
Device Tools
>
Configuration
>
I/O
>
Inputs
>
Action Assignment
. Then
assign the desired action to the desired enhanced event.
•
Using the Field Communicator: Choose
Configure
>
Alert Setup
>
Enhanced Events
. Then assign
the desired action to the desired enhanced event.
Options for Enhanced Event Action
Action
Label
Display
ProLink III
Field Communicator
Standard
Start sensor zero
Start Zero Calibration
Start Sensor Zero
Start Sensor Zero
Configure advanced options for process measurement
Configuration and Use Manual
April 2019
MMI-20048166
72
Micro Motion 4200 Transmitters
Содержание Micro Motion 4200
Страница 144: ...Measurement support Configuration and Use Manual April 2019 MMI 20048166 144 Micro Motion 4200 Transmitters ...
Страница 210: ...Using the transmitter display Configuration and Use Manual April 2019 MMI 20048166 210 Micro Motion 4200 Transmitters ...
Страница 218: ...Channel combinations Configuration and Use Manual April 2019 MMI 20048166 218 Micro Motion 4200 Transmitters ...