For some faults only: If
Fault Timeout
is set to a non-zero value, the transmitter will not implement the
fault action until the timeout has elapsed.
CAUTION
Do not use
Discrete Output Source
as a fault indicator. If you do, you may not be able to distinguish a fault
condition from a normal operating condition. If you want to use the Discrete Output as a fault indicator,
see
Fault indication with a Discrete Output
.
Procedure
Set
Discrete Output Fault Action
as desired.
Default: None
Options for Discrete Output Fault Action
Label
Discrete Output behavior
Polarity=Active High
Polarity=Active Low
Upscale
•
Fault: Discrete Output is ON (24 VDC or
site-specific voltage)
•
No fault: Discrete Output is controlled
by its assignment
•
Fault: Discrete Output is OFF (0 V
•
No fault: Discrete Output is controlled
by its assignment
Downscale
•
Fault: Discrete Output is OFF (0 V
•
No fault: Discrete Output is controlled
by its assignment
•
Fault: Discrete Output is ON (24 VDC or
site-specific voltage)
•
No fault: Discrete Output is controlled
by its assignment
None (default)
Discrete Output is controlled by its assignment
Fault indication with a Discrete Output
To indicate faults via a Discrete Output, set
Discrete Output Source
to Fault. Then, if a fault occurs, the
Discrete Output is always ON and the setting of
Discrete Output Fault Action
is ignored.
Integrate the meter with the control system
Configuration and Use Manual
April 2019
MMI-20048166
108
Micro Motion 4200 Transmitters