August 2020 

 

Reference Manual 

L231040 Rev AD

 

 

22 

 

Section 8: LTM-350 in a SIS 

 

8.0 General Safety Guidelines 

 

The  LTM-350  transmitters  are  designed  to  output  a 
4/20mA 

output 

signal 

under 

normal 

operation 

representing liquid level in a vessel. The 4/20mA output is 
considered the safety function of the transmitters.  
 
The  LTM-350  transmitters  are  design  to  operate  without 
the  need  for  periodic  maintenance  or  inspection.  If  the 
LTM-350  transmitters  are  being  used  as  part  of  a  Safety 
Implemented  System  (SIS)  then  periodic  proof  testing  will 
be  required  for  the  transmitter  to  detect  any  potential 
failure  which  is  defined  as  Dangerous  Undetectable  in  the 
transmitters' normal operation. 
 
Proof  Testing  must  be  performed  at  regular  interval  of  1 
year. The result of this testing must be documented.  If the 
transmitter  exhibits  a  failure  mode  output  during  normal 
operation then it will be necessary to perform proof testing 
regardless of scheduled intervals. 
 
 

8.1 LTM-350 Safety Ratings 

 

1.

 

The Safe Failure Fraction: 92.46% 

2.

 

The  average  Probability  of  Failure  on  demand  is: 
1.19 x 10¯³ 

3.

 

Executes  diagnostics  at  a  maximum  interval  of  1 
sec. 

4.

 

Provides a diagnostic/ failure update in less than 2 
seconds of the occurrence. 

5.

 

The transmitter may only be used in an SIS when: 

 

Software Revision is 1.01.16 or greater 

 

Hardware Revision is 1.00.02 or greater 

6.

 

It is classified as Type B equipment. 

7.

 

The  transmitters  must  be  used  within  the  limit 
defined in this manual. 

8.

 

The  maintenance,  troubleshooting  and  safety 
inspection should be done by qualified personnel.  
The  qualifications  include  but  are  not  limited  to 
knowledge  of  the  products  operating  principles, 
application  in  which  the  transmitter  is  being 
utilized,  the  information  in  this  instruction  manual 
and  a  general  knowledge/experience  as  an 
Instrumentation or Electronic Technician. 

 
 

 
 
 

8.2 LTM-350 Proof Test 

 

1.

 

To avoid any false alarms take appropriate steps to 
notify  control  room  that  the  instrument  is  being 
tested. 

2.

 

Utilize  the  pushbuttons  and  scroll  through  the 
main menus until "TestLoop" is shown.1 

3.

 

Enter  into  this  menu  and  modulate  the  current 
output  from  3.5  to  20.8  mA  while  verifying  the 
current  output  with  a  multimeter  or  the  control 
room.  If  this  function  does  not  work  then 
instrument is in Failure Mode. Use troubleshooting 
tips to figure out why instrument is in failure mode 
and do not try to recalibrate. 

4.

 

Exit "TestLoop" function by pressing enter. 
 
Notes: 
The  "TestLoop"  function  helps  test  for  power 
supply  problems  such  as  not  enough  voltage  or 
possible quiescent current related failures. 

 
 

8.3 Safety Inspection 

 

The  LTM-350  transmitters  have  3  major  components  the 
magnetic  float,  the  electronics  (analog  output)  and  the 
sensor  probe.    The  LTM-350  detects  the  magnetic  float 
position  from  inside  the  MLI  (MLI  -  mounted)  or  along  its 
sensor  (Direct  Insertion).    To  work  properly  the  float  must 
move  freely  either  inside  the  MLI    or  along  the  sensor.    If 
the  float  is  damaged  or  gets  stuck  in  the  vessel  or  along 
the  probe  the  transmitter  will  continue  to  report  the 
level/position  of  the  float.  This  qualifies  as  a  Dangerous 
undetected  failure.  To  avert  this  failure  the  float  will  need 
to be inspected for integrity and movement. Depending on 
the  application  some  MLI’s  can  have  two  floats  inside  the 
chamber and some transmitters can have two floats on the 
sensor.    In  both  cases  the  following  inspection  should  be 
done for both floats. 
For MLI - mounted transmitters: 
1.      Remove  the  float  from  the  level  gage  chamber  and 
visually inspect for damage such as dents or visible holes. 
2.   The float can be checked for leaks by submerging it in 
water and observing for air bubbles. 
3.   Install the float inside the chamber (note orientation of 
float) and move the float from bottom process connection 
(0%)  to  the  top  process  connection  (100%)  length  of  the 
chamber  using  process  fluid  or  other  media.    The  float 
should move freely from 0 to100%. 
 

Содержание Magtech LTM-350 Series

Страница 1: ...August 2020 Reference Manual L231040 Rev AD 1 Magtech LTM 350 Series Magnetostrictive Level Transmitter for Liquid Level Measurement Instruction and Operations Manual ...

Страница 2: ...do so may impair the protection provided by the equipment Do not perform any services other than those contained in this manual unless you are qualified Explosions could result in death or serious injury Verify the operating environment of the Magtech LTM 350 series transmitter is consistent with the appropriate hazardous locations certifications Do not remove the gauge cover in explosive atmosphe...

Страница 3: ... Mount Transmitter Installation 7 3 1 Direct Insertion Transmitter Installation 8 3 2 General Installation Guidelines 8 3 3 Recommended Wiring 9 Section 4 Specifications Page 4 0 Transmitter Electrical Specifications 10 4 1 Transmitter Sensor Tube 11 Section 5 Menu Structure and Features Page 5 0 Pushbutton Operation 10 5 1 Menu Structure 11 5 2 Features Description 13 5 3 Advance Menus 13 Section...

Страница 4: ...rmation 19 7 1 Hart Protocol Menus and Flowchart 20 Section 8 LTM 350 in a SIS Page 8 0 General Safety Guidelines 22 8 1 LTM 350 Safety Ratings 22 8 2 LTM 350 Proof Test 22 8 3 Safety Inspection 22 8 4 Identification 23 Section 9 Warranty Page 9 0 Warranty 23 Section 10 China RoHS Page 10 0 LTM 350 Model Disclosure 24 ...

Страница 5: ... configuration a single purpose float rides up and down the sensor tube totally surrounding it A multi purpose float may also be used to activate the sensor such a float being placed inside a liquid isolation pipe i e MLI and strategically located within a certain longitudinal distance from the sensor tube In either case the float has a somewhat lighter specific gravity than the liquid whose level is to...

Страница 6: ...plied properly has potentially very high measurement resolution typically better than 0 001 inch In the machine tool industry such a high resolution is desirable In the liquid level measurement application however a resolution of 0 03 inch is more than adequate In a brief description the magnetostrictive principle consists of a wire extruded and heat treated under carefully chosen conditions to re...

Страница 7: ...and the second output will be calibrated automatically The second time interval is timed in the same manner as the first one to derive the position of the heavier float The two floats require a separation of approximately three inches The float size geometry and magnetic strength all play a factor in how close the two floats can be without interfering with each other Only via HART Protocol 3 Prima...

Страница 8: ...tube with the change in fluid level If build up of process or contaminates should restrict the movement of the float the transmitter sensor tube will have to be cleaned or the float may have to be replaced with one that has a wider inside diameter The floats are designed to match the pressure and specific gravity for the process being measured and come in various materials ranging from stainless steel ...

Страница 9: ...ed around and will not grip the sensor probe C Is incorrect because the clamp has been tightened too much and the probe may be damaged distorted 4 Remote Mount Electronics Option Due to process temperature vibration or accessibility the housing electronics of the LTM transmitter can be remote mounted as far as 25 ft The housing electronics are supplied with a pipe mount bracket that can be mounted...

Страница 10: ...TM 351 only Hazardous Location Approvals FM Exp Cl I Div I Grp BCD Cl II Grp EFG Cl III CSA Exp Cl I Div I Grp BCD Cl II Grp EFG Cl III IECEx Exp Ex d IIC T5 Humidity Limits SAMA PMC 31 1 5 2 Vibration Limits SAMA PMC 31 1 5 3 RFI Limits SAMA PMC 31 1 20 to 1000 MHz up to 30V m 4 1 Transmitter Sensor Tube Material 316ss standard optional Hastelloy Monel Kynar coated Operating Temperature 50 to 302...

Страница 11: ... Temp mA Out Range SelLngt h 30 00in Lvl Unit in ft mm cm m Temp Unit C F R K Sel PV Level Interface Sel Alrm FailHigh FailLow HoldOut ChgRnge Sel LRV Sel URV Yes No yes 0 00in 24 00in SelDam p 1 sec ROC Fltr 10 0in s TrmSnsr TrimZero TrimZero TrimSpan TrimSpan Span Yes No yes Busy 24 00in Busy Error if incorrect Offset 0 00in TrimDAC Trim 4mA Trim 20mA Yes No yes 120 3860 TstLoop LoopTest Yes No ...

Страница 12: ...ll shift 3 00 inches higher than the Sel LRV 0 00 in original point It is recommended to leave this at 0 00 most of the time unless a special circumstance arises Press enter to go the next screen Select Upper Range Value URV This is the 20 00mA 100 00 point on the sensor This value should only be decremented Changing this parameter will change the measuring range or span of the transmitter Sel URV...

Страница 13: ...ace or Temp or mA Out or Range Rate of Change RoC Filter The RoC filter is a continuous monitor of how fast the rate the level is rising and falling It is also an excellent tool to help eliminate any temporary spontaneous noise that may be present in field For example if the level in a tank cannot rise or fall faster than 12 0 in s then the setting for the RoC filter should be set to 12 0 in s or ...

Страница 14: ...ettings or load settings saved in slots labeled Sensor 1 Sensor 2 or Sensor 3 if utilized by end user If desired one electronics module can save settings for 3 other sensor probes by calibrating the electronics module to a particular sensor probe then saving those settings into slots labeled sensor 1 2 or 3 Change the menu screen from load to save Then the user can save current setting into slots ...

Страница 15: ...nt level menu Enter the known current level in the vessel tank in engineering units and press enter The calibration should take place and the transmitter should be operational If the next menu appears then the operation was successful If the menu reverts back to the beginning of the 1pt Cal menu then the operation was unsuccessful Further troubleshooting may be necessary if the operation is unsucc...

Страница 16: ...al menu in the special features menu is ChngSgnl or change signal option The feature allows the adjustment of the signal being sent down the sensor probe It can be utilized when one electronics module is being utilized to save settings for various different length sensor probes This menu has 3 parameters that can be adjusted The first is Energy it is increased for a longer sensor probe and decreas...

Страница 17: ...and has been approved by the end user at some point during the ordering purchasing process Each transmitter has been factory calibrated to meet end user requirements so there is no need to recalibrate these transmitters unless the requirements have changed from the time of purchase delivery to installation If the need arises to calibrate these units to a new range please carefully read and follow ...

Страница 18: ...s are not reversed Electronics not making proper connection to power connector Make sure the electronics module is seated properly Open the front cover where the LCD is and firmly push on the Magtech text A good way to tell if the electronics are not seated properly is by making sure the protection screws are not physically higher than the outside of the housing Sometimes pulling the electronics m...

Страница 19: ...gy is sent down for Symptom Transmitter is erratic i e output going from correct reading to failure mode Possible Resolution Increase Energy Settings 1 Unlock the pushbuttons by moving the blue jumper to the left Hold the UP button for 1sec 2 While holding the UP button also hold ENTER button together for 3 secs 3 The menu should change to ComPort release the buttons 4 Bypass this menu by pressing...

Страница 20: ... Status Operation Status Calibration Status Level Alarm Status Calibration D A trim Full Level trim Full Temp trim 3 Calibration Review Level Gain Lvl UTP Value Live Measurements Level Pulse Sensor UTP Value Interface Pulse 4 Lvl LTP Value Tic Limit Sensor LTP Value Temperature Gain 3 Temperature Offset 3 RTD UTP Value 3 A D UTP Value 3 RTD LTP Value 3 A D LTP Value 3 DAC Zero DAC Full Basic Setup...

Страница 21: ...ode Ao Alrm typ D A trim Loop Test HART Output Poll addr Num req preams HART Information Manufacturer Model Unique ID serial Number Date Sales Order Purchase Order Tag Long Tag Message Descriptor Revision Universal rev Fld dev rev Final asmbly num Software rev Hardware rev 1 When Interf is PV Interf is displayed 2 Only Applies when interface float is included 3 Only Applies when temperature sensor...

Страница 22: ...350 Proof Test 1 To avoid any false alarms take appropriate steps to notify control room that the instrument is being tested 2 Utilize the pushbuttons and scroll through the main menus until TestLoop is shown 1 3 Enter into this menu and modulate the current output from 3 5 to 20 8 mA while verifying the current output with a multimeter or the control room If this function does not work then instr...

Страница 23: ...ified by persons that are not authorized by Magtech 2 Products subjected to misuse negligence or accidents 3 Products that are connected installed or otherwise used in such a way not in strict accordance with manufacturer s instructions This warranty is in lieu of any other warranty expressed or implied by any party other than Magtech Repairs and or replacements shall be at the sole discretion of M...

Страница 24: ...ybrominated diphenyl ethers PBDE 电子组件 Electronics Assembly X O O O O O 本表格系依据SJ T11364的规定而制作 This table is proposed in accordance with the provision of SJ T11364 O 意为该部件的所有均质材料中该有害物质的含量均低于GB T 26572所规定的限量要求 O Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB T 26572 X 意为在该部件所使用的所有均质材料里 至少有一类均质材料中该有害物质的含量高于GB T 26572所规定的限量要...

Отзывы: