Operation

17

Inverter Asynchronous

This alarm is triggered by an inverter software routine when the inverter and bypass waveforms 

are misaligned by more than 6 degrees in phase. This alarm resets automatically once the 

condition is no longer true.

1. First check if the alarm “Bypass unable to trace” or “Bypass abnormal” occurs. If so, solve it 

first.

2. Verify the waveform of the bypass voltage. If it is too distorted, ask the customer to verify and 

seek any possible measurements.

Inverter Fault

Inverter output voltage beyond limits. Load transfers to bypass.

Inverter Overtemp.

The temperature of the inverter heat sink is too high to keep inverter running.

This alarm is triggered by the signal from a temperature monitoring thermostat on the inverter 

bridge heat sink.

The UPS will recover automatically after a 5 minute delay from the disappearance of the 

overtemperature signal.

If the overtemperature condition is true, then check for and verify:

1. high ambient air temperature.

2. blocked cooling airway.

3. any fan failure.

4. prolonged inverter overload

Fan Fault

At least one of the cooling fans has failed

Inverter STS Fail

At least one of the static switches of inverter side is open or short circuit. This fault is locked until 

power off.

Bypass STS Fail

At least one of the static switches of bypass side is open or short circuit. This fault is locked until 

power off

Operation Invalid

This record is registered following an incorrect operation:

Output Fuse Fail

At least one of the inverter output fuses is blown. Inverter shuts down. Load transfers to bypass.

Control Power 2 Fail

UPS operates but Redundant Control Power is not available.

Unit Over load

The UPS is confirmed to be overload when the load arises above 105% nominal rating.

The alarm automatically resets once the overload condition is removed.

1. Confirm that the alarm is true by checking the load percent indicated on the LCD panel to 

determine which phase is being overloaded.

2. If the alarm is true, measure the actual output current to verify that the indications are valid.

Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing 

error can also leads to the alarm.

System Over load

The UPS parallel system is confirmed to overload when the total load arises above 105% 

nominal rating for the set basic number of UPSs. The alarm automatically resets once the 

overload condition is removed.

1. Confirm that the alarm is true by checking the system load percent indicated on the LCD 

panel to determine which phase is being overloaded.

2. If the alarm is true, measure the actual output current to verify that the indications are valid.

Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing 

error can also leads to the alarm.

Unit Over load Timeout

The UPS is confirmed to overload and the overload times out.

Note 1: the highest loaded phase will indicate overload timing-out first.

Note 2: When the timer is active then alarm “unit overload” should also be active as the load is 

above nominal.

Note 3: When the timer has expired, the inverter Static Switch is opened and the load 

transferred to bypass. The inverter shutdown and will restart after 10 seconds.

Note 4: If the load decreases lower than 95% after 5 minutes, the system will transfer back to 

inverter mode.

Confirm that the alarm is genuine by checking the load percent indicated on the LCD. If an 

overload is indicated then check the load, and investigate any additional load connected prior to 

the alarm (if applicable).

Byp. Abnormal Shutdown

Both bypass and inverter voltages unavailable. Load interruption

Inverter Over Current

Inverter Pulse Width Modulation module overloaded.

Table 13

RMP messages (continued)

Message

Description / Suggested Action (if any)

Содержание Liebert NX Remote Monitoring Panel

Страница 1: ... F3 F2 F1 EMERSON Network Power Liebert Press any key back to main menu Liebert NX 081 kVA 3x3 12 16 2009 Single 12 22 14 Normal STATUS EMERSON Network Power SILENCE ON OFF Remote Monitor Panel Lie be rt N X Liebert Remote Monitoring Panel User Manual ...

Страница 2: ......

Страница 3: ...the RMP on Drywall 5 2 6 Electrical connections 6 3 0 OPERATION 8 3 1 Startup and Reset 8 3 2 LED Mimic Power Flow 11 3 3 Audible Alarms Buzzer 11 3 4 Direct Access Push Buttons Keys 12 3 5 LCD Monitor and Menu Keys 12 3 6 Detailed Description of Menu Items 14 3 7 Status and Event Messages 16 3 8 Prompt Popup Windows 20 3 9 Dynamic Energy Flow Chart and UPS Help Screen 20 3 10 Default screen saver...

Страница 4: ...een 21 Figure 17 Default screen 21 TABLES Table 1 RMP component location in Figure 1 3 Table 2 Communication cable specifications 4 Table 3 Rectifier indicator 11 Table 4 Battery indicator 11 Table 5 Bypass indicator 11 Table 6 Inverter indicator 11 Table 7 Load indicator 11 Table 8 Status Alarm indicator 11 Table 9 Audible alarm key 11 Table 10 Menu key Icons and their meaning 12 Table 11 UPS sys...

Страница 5: ... Class A compliant EN IEC AS 62040 3 Performance requirements and test methods This equipment complies with UL 60950 1 2003 First Edition CSA C22 2 No 60950 1 03 1st Ed April 1 2003 For details see 4 0 Technical Specifications Continued compliance requires installation in accordance with these instructions and the use of man ufacturer approved accessories only General The unit must be grounded in ...

Страница 6: ...ty and maintenance staff This type location enhances the unit s capacity to provide notice if a status change or alarm requires an electrician or a UPS technician s intervention The RMP can monitor only one Liebert NX UPS If there are multiple Liebert NX UPSs an RMP will need to be installed for each unit For parallel systems the system load information may be viewed via the system screen from any...

Страница 7: ... update 6 Audible Alarm Buzzer 15 RS 232 Reserved not used 7 UPS Status and Alarm indicator 16 AC power input cable entry 8 F1 Function Key 17 RS 485 communication cable entry 9 F2 Function Key UPS Room Liebert NX Communication Cable Maxi mum Length 100m 328ft field supplied Maintenance or Control Room HELP F4 F3 F2 F1 EMERSON Network Power Liebert Press any key back to main menu Liebert NX 081 kV...

Страница 8: ...ntilation to keep the temperature within the specified operating range see Table 17 If the RMP is to be installed on a wall or other vertical surface ensure that the surface can bear the weight see Table 16 and there is no water leakage 2 3 Power Supply The RMP requires a 120V 230V AC input for detailed electrical specifications see Table 18 Figure 3 RMP electrical input plug 2 4 Cable Specificati...

Страница 9: ...hor and tighten firmly 4 Remove the four hooks from the RMP reverse them then reattach them to the RMP 5 Hang the RMP on the wall by slipping the hooks over the heads of the screws and lowering the RMP slowly until the screws are seated in the slotted portion of the hooks Figure 5 Mounting hole dimensions UPS_U2_J24 Up to 328ft 100m RMP_X1_J1 Shield Shield 485 485 485 485 1 2 3 4 1 2 3 4 STATUS Re...

Страница 10: ...Figure 6 Figure 6 Power and communication cable routing Extract four screws to remove the cable access cover Attach AC Input cable to labeled connector Attach communi cation cable to labeled RS 485 connector Reinstall cable access cover inserting AC Input and communication cables into respective labeled slots ...

Страница 11: ...bert NX as shown in Figure 7 Figure 7 RS 485 cable connection to Liebert NX Connect the other end of the RS 485 signal cable to the X4 slot on the monitor board The monitor board is inside the UPS front door Communication connections on Remote Monitoring Panel board ...

Страница 12: ... Figure 9 will be displayed while the data is loading The loading time is about 30 seconds Figure 9 Data loading progress screen If the firmware in the UPS and the RMP are compatible the RMP will display the screen shown in Figure 10 The NX screen will display the same screen F2 F4 F5 F1 F3 Liebert NX 2006 01 22 12 30 36 30kVA 3X3 Unit 1 Normal Bypass Main Vphase V Iphase A Freq Hz Vline V P F A A...

Страница 13: ...tor 50 50 50 1 4 1 4 1 4 F2 F4 HELP F1 F3 Input breaker closed 01 12 12 28 16 Manual turn on 01 12 12 30 06 UPS in normal mode 01 22 12 30 16 Liebert NX 2006 01 22 12 30 36 30kVA 3X3 Unit 1 Normal Bypass Main Vphase V Iphase A Freq Hz Vline V P F A AB 120 20 5 50 1 208 0 99 B BC 120 20 5 50 1 208 0 99 C CA 120 20 5 50 1 208 0 99 Output Remote Monitor Panel silence F2 F4 HELP F1 F3 Input breaker cl...

Страница 14: ...t NX 2006 01 22 12 30 36 30kVA 3X3 Unit 1 Normal Bypass Main Vphase V Iphase A Freq Hz Vline V P F A AB 120 20 5 50 1 208 0 99 B BC 120 20 5 50 1 208 0 99 C CA 120 20 5 50 1 208 0 99 Output Communication with UPS Failed CommErrID 0x01 F2 F4 HELP F1 F3 Input breaker closed 01 12 12 28 16 Manual turn on 01 12 12 30 06 UPS in normal mode 01 22 12 30 16 Liebert NX 2006 01 22 12 30 36 30kVA 3X3 Unit 1 ...

Страница 15: ...rmal Failed overcurrent overtemperature Off Battery and Converter Normal Battery charging Table 5 Bypass indicator Green Load on Bypass power Red Bypass not available out of normal range or Static bypass switch fault Off Bypass Normal load not on bypass Table 6 Inverter indicator Green Inverter Normal and powering the load Flashing Green Inverter ON starting up synchronizing or standing by ECO mod...

Страница 16: ...avigate within the graphic LCD monitor windows Figure 14 Graphic LCD monitor windows and keypad The function of keys F1 to F4 is shown by a self explanatory icon as appropriate for the particular window As shown in Figure 14 above pressing F1 moves the cursor resting in OUTPUT from the UPS Menu Window 2 to current record window 4 where it would first rest in Input breaker closed In a similar manne...

Страница 17: ... No 1 Phone No 2 Phone No 3 Command password System Sout kVA Pout kW Qout kVAR Single unit no parallel data Records history log Language Choices for display Mains input L N voltage V L N current A Frequency Hz L L voltage V Power factor Load Sout kVA Pout kW Qout kVAR Loadlevel Crest factor Bypass L N voltage V Frequency Hz L L voltage V Output L N voltage V L N current A Frequency Hz L L voltage ...

Страница 18: ...Warning or Fault Normal UPS operating Normal Warning System attention required e g AC Input Failure Fault UPS Fuse or Hardware Failure Table 12 Descriptions of RMP menus and data window items Menu Type Item Type Explanation Mains input L N voltage V Phase voltage L N current A Phase current Frequency Hz Input frequency L L voltage v Line line voltage Power factor Power factor TX Input L N voltage ...

Страница 19: ...on Phone No 1 When IntelliSlot 1 Communication mode is Modem this is the first phone number to be dialed to send an alarm notification Phone No 2 When IntelliSlot 1 Communication mode is Modem this is the second phone number to be dialed to send an alarm notification Phone No 3 When IntelliSlot 1 Communication mode is Modem this is the third phone number to be dialed to send an alarm notification ...

Страница 20: ...ecover automatically Check the environment and ventilation Batt Contactor Fail Battery contactor or circuit breaker not responding to control signals Batt Charger Fault The voltage of the battery charger is too high Control Power 1 Fail UPS operates but Redundant Control Power is not available Mains Phase Reversed AC Input phase sequence is reversed Rectifier Overcurrent Rectifier is overloaded So...

Страница 21: ...ce the overload condition is removed 1 Confirm that the alarm is true by checking the load percent indicated on the LCD panel to determine which phase is being overloaded 2 If the alarm is true measure the actual output current to verify that the indications are valid Disconnect unnecessary load and ensure the safety In a parallel system a severe load sharing error can also leads to the alarm Syst...

Страница 22: ... above 135 rating The UPS just alarms and does nothing LBS Active Load Bus Synchronization is active The UPS is acting as an LBS master or slave in a dual bus configuration Setting Save Error History records not saved Reserved Mains Neutral Lost AC Input mains reference neutral not detected Protocol version clash Firmware incompatibility between Monitor Board and Digital Signal Processor Board Bat...

Страница 23: ... Input Isolation Transformer Over Temperature Ext Output TX Overtemp External Output Isolation Transformer Over Temperature Battery Room Alarm Environment in Battery Room Needs Attention Rotary Sw Test Pos Rotary switch is in test position Rotary Sw Normal Pos Rotary switch is in normal position Rotary Sw Bypass Pos Rotary switch is in bypass position Rotary Sw Maint Pos Rotary switch is in mainte...

Страница 24: ...peration leads to inverter overload confirm or cancel The turn off this inverter will lead to the overload of remaining inverter s in a parallel system Turn on more UPS to carry current load The number of paralleled inverters already turned on is insufficient to carry the existing load Battery will be depleted confirm Battery Capacity test discharges the battery 100 System self test finished every...

Страница 25: ...2 minutes of inactivity the backlight turns off Press any key F1 F4 or Help to reactivate the screen Figure 17 Default screen F2 F4 HELP F1 F3 Help information Select the previous menu item Select the current record window Q3 Q2 Q1 Q5 Press help key back to main menu F2 F3 F4 HELP F1 Liebert NX 2005 05 22 12 30 36 20 kVA 3x3 UNIT 1 NORMAL Press any key back to main menu ...

Страница 26: ...40 Relative humidity 90 or less at 20 C Acoustical noise dBA 32 Altitude of operation m 2000 Storage transport temperature C 25 70 Table 18 Electrical specifications Electrical Characteristics Units Value Rated input voltage VAC 100 120 220 230 240 Input voltage range VAC 90 254 Input Frequency Hz 50 60 Input frequency tolerance Hz 47 67 Input Current A 0 7A Max Table 19 Cable specifications Item ...

Страница 27: ...ted RFI CISPR 22 A Radiated RFI CISPR 22 A Table 21 Electromagnetic susceptibility EMS immunity levels Standard IEC EN AS Requirement Level Criterion Electrostatic Discharge 61000 4 2 6 kV contact 8 kV air 3 B Radiated Electric Fields 61000 4 3 10 V m 3 A Fast Electrical Transients 61000 4 4 2 kV 5 kHz Power and Signal ports 3 B Surges 61000 4 5 Power port 2kV common mode 1kV differential mode Sig...

Страница 28: ...oration All names referred to are trademarks or registered trademarks of their respective owners Technical Support Service Web Site www liebert com Monitoring 800 222 5877 Liebert monitoring emerson com Outside the US 614 841 6755 Single Phase UPS 800 222 5877 upstech emersonnetworkpower com Outside the US 614 841 6755 Three Phase UPS 800 543 2378 powertech emersonnetworkpower com Environmental Sy...

Отзывы: