Technical Specifications
23
4.1
Agency and Certifications
Safety Standard
: IEC/EN/AS 62040-1-1 incorporating applicable portions of IEC/EN/UL/AS 60950-1
Certification
: CE and UL 60950-1:2003, First Edition CSA C22.2 No. 60950-1-03 1st Ed.
Electromagnetic Compatibility Standard
: IEC/EN/AS 62040-2 incorporating applicable portions
of emission and immunity standards as detailed in
Tables 20
and
21
below.
Table 20
Electromagnetic interference (EMI)—emission limits
Standard
IEC/EN/AS
Class
Harmonic Current
61000-3-2
-
Voltage Fluctuations & Flicker
61000-3-3
-
Conducted RFI
CISPR 22
A
Radiated RFI
CISPR 22
A
Table 21
Electromagnetic susceptibility (EMS)—immunity levels
Standard
IEC/EN/AS
Requirement
Level
Criterion
Electrostatic Discharge
61000-4-2
6 kV contact, 8 kV air
3
B
Radiated Electric Fields
61000-4-3
10 V/m
3
A
Fast Electrical Transients
61000-4-4
2 kV / 5 kHz (Power and Signal ports)
3
B
Surges
61000-4-5
Power port
2kV (common mode)
1kV (differential mode)
Signal port
1kV
3
B
Continuous Conducted Interfer.
61000-4-6
10V 3
A
Magnetic Field at Power Freq
61000-4-8
30A/m
-
B
Voltage Dips and Short
Interruptions
61000-4-11
70%Ut:
1ms, 3ms, 10ms
—
A
30ms, 100ms, 300ms, 1000ms
—
B
40%Ut:
1ms, 3ms
—
A
10ms, 30ms, 100ms, 300ms, 1000ms
—
B
0%Ut
1ms
A
3ms, 10ms, 30ms, 100ms, 300ms, 1000ms
—
B
Low Frequency Signals
61000-2-2
10V 140Hz-250Hz-360Hz
—
A