62 Chapter 8 Options
Liebert
®
ITA 16kVA And 20kVA UPS User Manual
The standard battery cabinets are listed in Table 8-11.
Table 8-11 Standard battery cabinet list
Battery cabinet type
UPS power
Configuration
Corresponding
battery (CSB)
Dimension/Weight
PM32-75C4-2-50-A
≤
90kVA
Four layers, can load 32-cell
batteries; configure 250A ABB
three-pole air breaker and
50mm
2
cables
12V 100Ah
800mm × 1100mm × 2000mm
227kg
PM32-38C4-50-A
≤
90kVA
Four layers, can load 32-cell
batteries; configure 250A ABB
three-pole air breaker and
50mm
2
cables
12V 26Ah
12V 40Ah
12V 52Ah
12V 75Ah
600mm × 1100mm × 2000mm
203kg
Note
1. The connection cables between the battery cabinets are not configured. Please contact the local dealer if you need.
2. The parallel bus bar (3 pcs) of the battery cabinet is a copper bar used to connect battery cabinets in parallel. Sets = battery
cabinet number - 1.
8.8 Communication Options And Monitoring Options
The communication options and the monitoring options are listed in Table 8-12.
Table 8-12 Communication options and the monitoring optios
Name Type
Description
Appearance
SIC card
UF-SNMP810
Remote monitor UPS through TCP/IP protocol and
Internet;
Support remote safe shutdown;
Provide an extended net port, cascade-connect up to
eight temperature humidity sensors
RS485 card
UF-RS485
Be used to connect UPS to RDU-A monitoring unit, or
connect to the cascade-communication in parallel
system
MODBUS card
UF-MODBUS410
Select it when the UPS is connected to the monitoring
system of building
Dry contact card
UF-DRY410
Offer four routes relay signal outputs and three routes
digital signal inputs
Extended dry
contact card
UF-DRY420
Offer four routes relay signal outputs, three routes
digital signal inputs, RS232 and RS485
communication function and four routes analog signal
acquisition function
SiteMonitor PC license monitoring software (Monitors at the site server; a VCD is
delivered with the UPS, and the Network Shutdown program is provided in it)
SiteMonitor network license monitoring software (Number of user
≤
5)
SiteMonitor network license monitoring software (Number of user
≤
20)
Remote
monitoring
software
SiteMonitor
SiteMonitor network license monitoring software (limitless)
Temperature
sensor
RDU-A-S01T
With LCD screen, the SIC card is needed to be
connected
Temperature
humidity sensor
RDU-A-S02TH
With LCD screen, the SIC card is needed to be
connected