Connect to the Card - Terminal Emulation, Telnet or Web Interface
A2
A.2 C
ONNECT
TO
THE
C
ARD
- T
ERMINAL
E
MULATION
, T
ELNET
OR
W
EB
I
NTERFACE
Upgrading the firmware requires connecting to the card with one of these interfaces.
A.2.1
Open the Terminal Emulation Interface - Serial Connection
To connect to the card using terminal emulation software with a
serial connection to the Web card:
1. Open a terminal emulation application, such as
HyperTerminal.
To do this:
• Click the
Start
button, then
Programs
,
Accessories
,
Communications
and finally
HyperTerminal
.
2. In the Connection Description window, enter a name for the
connection—for example,
GXT2U
—then click
OK
.
3. In the Connect To window:
• Choose
COM3
from the Connect Using drop-down list.
• Click
OK
.
4. In the COM3 Properties window, enter the communication
settings shown in
Table A3
.
5. When the message at right appears in the HyperTerminal
window, press the Enter key.
A.2.2
Open the Terminal Emulation Interface - TCP/IP Connection
To connect to the card using terminal emulation software with
an Ethernet connection to the Web card:
1. Open a terminal emulation application, such as
HyperTerminal.
To do this:
• Click the
Start
button, then
Programs
,
Accessories
,
Communications
and finally
HyperTerminal
.
2. In the Connection Description window, enter a name for the
connection—for example,
GXT2U
—then click
OK
.
3. In the Connect To window:
• Choose
TCP/IP (Winsock)
from the Connect Using
drop-down list.
• Enter the IP address of the Web card—for example,
192.168.0.125
—in the Host Address box, then click
OK
.
4. When the message at right appears in the HyperTerminal window,
press the Enter key.
5. Enter the Administrator username and password (both are case-
sensitive):
a.
Login
(username—default is
Liebert
)
b.
Password
(default is
Liebert
)
Name
COM3
Connection
settings
Table A3
Communication settings
Baud Rate:
9600
Data Bits:
8
Parity:
None
Stop Bits:
1
Flow Control:
None
Name
TCP/IP
(Winsock)
RTCS v2.96.00 Telnet server
Service Port Manager Active
<Esc> Ends Session
Login: Liebert
Password: ********