Messaging
31
Terminal Emulation (Serial or TCP/IP Connection) / Telnet
To activate and set up SMS messages:
1. Choose
Messaging
from the Main Menu, then
SMS
.
2. To enable the SMS feature, enter
y
(yes) at the prompt.
3. Choose
SMS Configuration
from the Messaging Menu, then select an option and use the
following guide to make changes.
Web Interface
To access SMS Configuration through the Web interface:
• Click on the
Configure
tab, then
SMS
in the left panel and finally
Edit
in the right panel. After
making changes, click
Save
.
Enable SMS [y/n] ?>
Table 20
SMS configuration guide
Parameter
Description
Maximum
SMS From
The e-mail address of the sender—for example,
—
typically, the address where replies should be sent.
64
characters
SMS Message
Recipients
The message will be sent to this list of addresses. The SMS/Text Message
address is usually a 10-digit phone number followed by @____.com (where ____
might be a company name). To add an SMS address, use the format
. Multiple addresses must be added individually.
Changes may be made by entering
d
to delete an entry or
e
to edit an entry.
NOTE:
To specify multiple recipients of the SMS message in the Web interface,
use a semicolon (;) to separate addresses in the SMS To box.
64
characters
SMS Subject
The subject line of the message. By default, this is the event description—e.g.,
AlarmOnBypass
—but it may be customized.
120
characters
SMS Customize
Message
The text of the message sent to e-mail recipients. Choose from a list of items to
include in the message. For details, see
6.3 - Customize Messages
.
—
SMTP Server
The IP address or domain name of the SMTP e-mail server that sends messages.
32
characters
Port
SMTP server port—typically the default port, 25.
—
Test SMS
After saving changes to SMS parameters, send a test SMS message to verify the
settings are correct. The message status will be displayed.
—
View Test
SMS Log File
Choose this option to display a log showing the results of test messages.
—
SMS