Electrical Connections—UPS
37
Liebert
®
APM
™
Figure 22 Single UPS Remote Emergency Power Off
Table 8
EPO input contact relays
Position
Name
Description
J6.1
EPO_NC
EPO Activated when opened to J6.2
J6.2
+12V
EPO Activated when opened to J6.1
J6.3
+12V
EPO Activated when shorted to J6.4
J6.4
EPO_NO
EPO Activated when shorted to J6.3
NOTE
The Emergency Stop action within the UPS shuts down the rectifier, inverter and static
bypass. It does not internally disconnect the input power supply. To disconnect ALL power to
the UPS, open the upstream feeder breaker(s) when the remote EPO is activated.
NOTE
Normally Closed EPO – J6: 1, 2, these terminals are supplied factory-linked on the Bypass
Module on the UPS and must remain installed if using NO contacts.
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
for maximum runs between 80 and 200 feet (25-60m), respectively.
UAM04031-00
Rev. 1