![background image](http://html.mh-extra.com/html/emerson/gie-4820-3a-3-45kw/gie-4820-3a-3-45kw_user-manual_103999022.webp)
16
Chapter 1 System Outline
GIE 4820/3A/3.45KW Power Supply System User Manual
1.6 System Specifications
AC Input
Single phase, three wires
Rated input voltage: 220V
AC
(
90V
AC
~
290V
AC
)
(Note: between 90V
AC
~
170V
AC
, system linearity derating current-limiting
output, refer to Fig. 1-9)
Maximum input current: 20A
Frequency: 50Hz (45
~
65Hz)
Battery Input
Two groups of batteries are parallel with DC output of rectifier module
(keep the same polarity) via 63A circuit breaker, and work in FC (floating
charge) or EC (equalized charge) mode. The rated input voltage of the
battery is 48V with a rated volume of 50~500Ah.
Note:
1, By default, the battery group capacity is set to 100AH. If the actual
battery capacity is different, the setting should be changed accordingly
through the background lest the battery management should go wrong.
2These two groups of batteries actually conduct battery management
through a common power off contactor and a shunt. The battery current
tested by the monitoring module is actually the total current of two groups
of batteries. So the battery group number should be set as one group, and
the battery capacity should be set as the sum of two groups of batteries
the during the monitoring module background setting.
Rated voltage
-48V
DC
Voltage adjustable
range
-43.2V
DC
~
-57.6V
DC
(adjustable inner)
DC output branch
Load 1 10A (MCB)
Load 2 20A (MCB)
Load 3 20A (MCB)
Load 4 50A (MCB)
Battery 63A (MCB)
DC Output
Total DC output
current
Fig.1-9 Relation between Output Current and Input
Voltage of Power System