Chapter 1 System Outline
11
GIE 4820/3A/3.45KW Power Supply System User Manual
Recommended Sensors
Signal
Port
Silk-sc
reen
Pin Functions
Factory
Model
Functions
Smoking
sensor port
SMOKE Pin 2 is +24V power, and
pin 1 is signal cable.
Shenzhen
Fanhai
Sanjiang
Electron Co.,
Ltd
JTY-LZ98
3K(HW)
Working in the detecting
workroom. When the fog grain
enters into the workroom, it will
output alarm current signal.
Once the sensor sends alarm,
its alarm state keeps all the
while. The current should be
cut off for recovering.
Gate
magnetic
sensor port
JTM1
Pin 2 is +24V power, and
pin 1 is signal cable. In the
default condition, the
shorting of pin 1 and pin 2
represents gate magnetic
normal, and the
disconnection represents
alarm. If the system do not
connect gate magnetic
sensor, the alarm can be
shielded by shorting pin 1
and pin 2 of the socket.
ALEPH
PS-1523
It can feel the open and close
of the door and send alarm. Its
technical specifications can
refer to the product manual.
Alarm dry
contact port
JK1,
JK2
The maximum voltage endurable is 60V
DC
, the maximum load current is 500mA. When
there is a general alarm, Jk2 dry contact is shorting. When there is serious alarm, Jk1
dry contact is shorting. The level of the serious alarm and general alarm can be set
through the background software by users.
Opto-coupler
output port
JAC1,
JAC2
Pin 1 and pin 2 connects with C pole and E pole of opto-coupler separately, and the
parameters of the opto-coupler are Vcemax=40Vdc, Icmax=80mA. Pay attention to the
derating application.
Standby
digital value
input port
JTD1~J
TD7
Pin 1 o24V power, pin 2 o12V power, pin 3 is signal input, and pin 4
connects with grounding.
Users can connect correspond signal according to self-demanding, and can bring it into
the monitoring range after the simple configuration of the monitoring module.
The monitoring module of the system adopts hot-swappable design, and can be
replaced when the system is operating.
The address of the monitoring module can be set through the toggle switch on the
monitoring main board (eight digits, and four low bits are effective) to achieve the
centralized management of multi-power systems.
Содержание GIE 4820/3A/3.45KW