Instruction Manual
D103272X012
LCP100 Local Control Panel
August 2017
22
Figure 19. Ex ia IIB or Ex tb IIIC Wiring Diagram 3
LCP100
Protection Method
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
Ex ia IIB
Ex tb IIIC
LOOP
LCP100 then DVC6200 SIS
Point-to-Point
NOTES:
1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE 8 mA. THE LCP100
WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
2 REFER TO THE DVC6200 SERIES QUICK START GUIDE (
D103556X012
)
FOR SCHEMATICS AND ENTITY PARAMETERS.
INTRINSICALLY
SAFE
BARRIER
LOOP
TERMINALS:
Ui = 30 VDC
Ii
= 226 mA
Pi = 1.4 W
Ci = 0.22
m
F
Li = 16.0
m
H
AUX
TERMINALS:
Ui = 30 VDC
Ii
= 452 mA
Pi = 1.4 W
Ci = 0
m
F
Li = 0 mH
(USER SUPPLIED)
LOGIC SOLVER
OUTPUT
8 - 20 mA
GE26881-Sheet 17
2
1