Instruction Manual
D103272X012
LCP100 Local Control Panel
August 2017
17
Figure 14. Ex ic IIC or Ex tb IIIC Wiring Diagram 4
LCP100
Protection Method
LCP100
Power Source
Wiring Order from
Logic Solver
DVC6200 SIS Mode
(Current or Voltage)
Ex ic IIC
Ex tb IIIC
LOOP
LCP100 then DVC6200 SIS
Multi-Drop
INTRINSICALLY
SAFE
BARRIER
NOTES:
1 THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
2 REFER TO THE DVC6200 SERIES QUICK START GUIDE (
D103556X012
) FOR
SCHEMATICS AND ENTITY PARAMETERS.
LOOP
TERMINALS:
Ui = 27 VDC
Ii
= N/A
Pi = N/A
Ci = 1.1 nF
Li = 0 mH
LOGIC SOLVER
OUTPUT
24 VDC
(USER SUPPLIED)
LC340 LINE
CONDITIONER
FLD
SYS
GE26881-Sheet 12
2
1