easy-Drive User Interface
The easy-Drive configurator is available on the Emerson
.
Figure 4. Fisher easy-Drive Configuration Software
Loss Detect
The loss detect is a user defined time the RPU-100 will wait to verify loss of power before performing a backup
operation. This time is configurable between 0.05 and 3.00 seconds. The default is 0.250 seconds.
Status Output
The status output is a discrete output that indicates the overall status of the RPU-100. If the output is on, (connection
made) this indicates the RPU-100 is operational. If the output is off, additional information can be found in the Modbus
diagnostic fault flags register.
See the Mounting section of this manual for wiring details.