Instruction Manual
D104551X012
easy-Drive RPU-100
May 2021
15
Replacement
WARNING
D
Refer to the WARNINGS at the beginning of the Installation section in this instruction manual.
D
To avoid exposure hazard or release of toxic gases, do not disassemble, subject to heat above 100
5
C (212
5
F), or
incinerate the RPU-100.
Note
Proper disposal of used reserve power unit, which contains acetonitrile, is required. Disposal should be done in accordance with
applicable federal, state, and local rules and regulations.
Removal
Refer to figures 5 through 10.
1. Remove the easy-Drive actuator upper enclosure per the applicable actuator instruction manual.
2. Disable RPU-100 by moving switch on reserve power unit to 'disable' position.
3. Disconnect power from the RPU-100.
4. Disconnect wiring harness from the RPU-100.
5. Remove the two mounting screws securing the RPU-100 to the actuator
.
6. Slide RPU-100 to remove from mounting bracket.
Installation
Refer to Mounting section, steps 5 through 9, for installation of new RPU-100 reserve power unit. The existing wiring
harness can be used to connect to the new RPU-100.
Parts Ordering
for assistance or when ordering replacement parts.
WARNING
Use only genuine Fisher replacement parts. Components that are not supplied by Emerson should not, under any
circumstances, be used in any Fisher actuator, because they may void your warranty, might adversely affect the
performance of the actuator, and could cause personal injury and property damage.
Содержание Fisher easy-Drive RPU-100
Страница 20: ...Instruction Manual D104551X012 easy Drive RPU 100 May 2021 20 Appendix B Certificate of Conformance continued ...
Страница 21: ...Instruction Manual D104551X012 easy Drive RPU 100 May 2021 21 Appendix B Certificate of Conformance cont ...
Страница 22: ...Instruction Manual D104551X012 easy Drive RPU 100 May 2021 22 ...
Страница 23: ...Instruction Manual D104551X012 easy Drive RPU 100 May 2021 23 ...