Figure 4. Cage Head Mounting Positions
RIGHT‐HAND MOUNTING
LEFT‐HAND MOUNTING
1 67CFR FILTER/REGULATOR.
AH9150-A
A2613-2
Mounting Caged Sensor
Note
Install the cage so that it is plumb; the displacer must not touch the cage wall. If the displacer touches the cage wall, the unit will
transmit an erroneous output signal.
Note
If the controller/transmitter is not mounted on the sensor, refer to the Installing Controller/Transmitter on Sensor procedures in
the Maintenance section. This section also provides instructions for adding a heat insulator to a unit.
Cage connections normally are either NPS 1‐1/2 or 2, screwed or flanged. Figure 5 shows the combinations. With
flanged connections, use standard gaskets or other flat‐sheet gaskets compatible with the process fluid. Spiral‐wound
gaskets without compression‐controlling centering rings cannot be used for flange connections.