Chapter 3 Installation and Wiring 19
EV2000 Series Universal Variable Speed Drive User Manual
2. Wire Connections of Drive for Basic Operation
Models: EV2000-4T0055G/0075P. EV2000-4T0075G/0110P
DCL DC reactor
(connect optional parts
externally)
Braking resistor
Bi-direction open
collector output
PB
(+)
(-)
R
S
T
R
S
T
3-phase
380V
50/60Hz
M
U
V
W
PE
Aux.
Power
supply
Breaker
P1
PG
P24
COM
X8
X7
PE
EV2000
DC current
meter
0/4-20mA current
signal
AO1
AO2
Frequency meter
Output 0-24V pulse
signal
DO
COM
GND
TB
TC
TA
Programmable
relay output
485-
485+
RS485
communication port
X1
X2
X3
X4
X5
X6
X7
X8
Multi-function input 1
FWD
REV
Forward/stop
Reverse/stop
PLC
COM
Speed command
0~10V
VCI
GND
VRF
PE
~
~
0 10V/0 20mA
Y1
Y2
CME
Output 1
Output 2
Common terminal
CCI
P24
COM
I
V
CN10
~
0 10V
.
.
.
CN16
~
0/4 20mA
RS232
RS485
CN14
TXD
RXD
GND
RS232
communication
port
Multi-function input 3
Multi-function input 7
CN17
~
0 10V
~
0/4 20mA
.
.
.
.
.
.
.
.
.
(connect optional parts
externally)
Multi-function input 2
Multi-function input 4
Multi-function input 5
Multi-function input 6
Multi-function input 8
P24
Fig. 3-9 Basic wiring 1
Notes:
1. Terminal CCI can be input voltage or current signal by switching the jumper CN10 on control board;
2. The auxiliary power supply comes from the bus (+) and bus (-);
3. Built-in braking kit is installed and a braking resistor is required to be connected between (+) and PB;
4. In the above figure, “O” is the terminal in main circuit, and “
⊙
” is the control terminal;
5. Refer to section 3.3.2 for the using of control terminals.