background image

 

1592009730 XW30-35VS GB r1.2 31.07.2015 

                            XW30VS  - XW35VS 

3/4 

OTHER 
Adr   RS485 serial address 

(1÷247)

Identifies the instrument address when connected to a ModBUS 

compatible monitoring system. 

PbC  Type of probe:

 it allows to set the kind of probe used by the instrument: 

PbC

 = PBC probe, 

ntC = 

NTC probe. 

rEL   Release software:

 (read only) Software version of the microprocessor. 

Ptb   Parameter table:

 (read only) it shows the original code of the Dixell parameter map. 

Prd   Probes display: 

(read only) display the temperature. 

Pr2   Access to the protected parameter list 

(read only). 

 

6.

 

DIGITAL INPUT 

The controllers have 1  free contact digital input. It is programmable in seven different configurations by 
the “

I2F

” parameter. 

6.1

 

DOOR SWITCH INPUT  (I2F = dor) 

It signals the door status and the corresponding relay output status through the “

odc

” parameter: 

no

 = normal (any change); 

Fan

 = Fan OFF; 

CPr

 = Compressor OFF; 

F_C

 = Compressor and fan OFF. 

Since  the  door  is  opened,  after  the  delay  time  set  through  parameter  “

dOA

”,  the  alarm  output  is 

enabled and the display shows the message “

dA

”. The alarm stops as soon as the external digital input 

is disabled again. During this time and then for the delay “

dot

” after closing the door, the high and low 

temperature alarms are disabled. 

6.2

 

GENERIC ALARM (I2F = EAL) 

As soon as the digital input is activated the unit will wait for “

did

” time delay before signalling the “

EAL

” 

alarm  message.  The  outputs  status  don’t  change.  The  alarm  stops  just  after  the  digital  input  is  de-
activated. 

6.3

 

SERIOUS ALARM MODE (I2F = BAL) 

When the digital input is activated, the unit will wait for “

did

” delay before signalling the “

BAL

” alarm 

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated. 

6.4

 

PRESSURE SWITCH (I2F = PAL) 

If  during  the  interval  time  set  by  “

did

”  parameter,  the  pressure  switch  has  reached  the  number  of 

activation  of    the  “

nPS

”  parameter,  the  “

PAL

”  pressure  alarm  message  will  be  displayed.  The 

compressor  and  the  regulation  are  stopped.  When  the  digital  input  is  ON  the  compressor  is  always 
OFF. 

If  the  nPS  activation  in  the  did  time  is  reached,  switch  off  and  on  the  instrument  to  restart 

normal regulation. 

6.5

 

START DEFROST (I2F = DFR) 

It executes a defrost if there are the right conditions. After the defrost is finished, the normal regulation 
will restart only if the digital input is disabled otherwise the instrument will wait until the “Mdf” safety time 
is expired. 

6.6

 

ENERGY SAVING (I2F =  ES) 

The  Energy  Saving  function  allows  to  change  the  set  point  value  as  the  result  of  the  SET+  HES 
(parmeter) sum. This function is enabled until the digital input is activated. 

6.7

 

REMOTE ON/OFF (I2F =  ONF) 

This function allows to switch ON and OFF the instrument. 

6.8

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “

I2P

” parameters. 

 

CL

 : the digital input is activated by closing the contact.

 

 

OP

 : the digital input is activated by opening the contact 

 

7.

 

INSTALLATION AND MOUNTING 

Instruments  shall  be  mounted on vertical panel, in a 72x56 mm hole,  and fixed using screws 

 3 x 

2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RGW-V).  
The  temperature  range  allowed  for  correct  operation  is  0  -  60  °C.  Avoid  places  subject  to  strong 
vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. 
Let the air circulate by the cooling holes. 

 

7.1

 

CUT OUT  

 

56

72

40

83

,5

 

 
 
 
 

8.

 

ELECTRICAL CONNECTIONS 

Relays, power supply, digital and analogue inputs have a Faston connection (6,3mm). Heat-resistant 
cables  have  to  be  used.  Before  connecting  cables  make  sure  the  power  supply  complies  with  the 
instrument’s requirements. Separate the probe cables from the power supply cables, from the outputs 
and  the  power  connections.  Do  not  exceed  the  maximum  current  allowed  on  each  relay,  in  case  of 
heavier loads use a suitable external relay. 

N.B.

 Maximum current allowed for all the loads is 20A. 

8.1

 

PROBE CONNECTIONS 

The probe shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. 
It  is  recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly  measure  the 
average room temperature.  

 

9.

 

USE OF THE PROGRAMMING “HOT KEY “ 

The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to the 

“Hot Key” 

and vice-versa. 

 

9.1

 

DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT) 

1.

 

Turn OFF the instrument by means of the ON/OFF key, remove the TTL serial cable if present, 
insert the 

“Hot Key” 

and then turn the Wing ON. 

2.

 

Automatically  the  parameter  list  of  the 

“Hot  Key”

  is  downloaded  into  the  Wing  memory,  the 

DoL

”  message  is  blinking.  After  10  seconds  the  instrument  will  restart  working  with  the  new 

parameters. 

3.

 

Turn OFF the instrument remove the 

“Hot Key”, 

plug in  the TTL serial cable, then turn it ON 

again. 

At the end of the data transfer phase the instrument displays the following messages: 

end

 “ for right programming. The instrument starts regularly with the new programming. 

err

”  for  failed  programming.  In  this  case  turn  the  unit  off  and  then  on  if  you  want  to  restart  the 

download again or remove the “

Hot key

” to abort the operation. 

 

 

9.2

 

UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”) 

1.

 

Turn  OFF  the  instrument  by  means  of  the  ON/OFF  key  and  remove  the  TTL  serial  cable  if 
present; then turn it ON again. 

2.

 

When  the  Wing  unit    is  ON,  insert  the  “

Hot  key

”  and  push 

o

 

key;  the   

"uPL" 

message 

appears. 

3.

 

Push “

SET”

 key to start the UPLOAD; the “

uPL

” message is blinking. 

4.

 

Turn OFF the instrument remove the 

“Hot Key”, 

plug in  the TTL serial cable, then turn it ON 

again. 

At the end of the data transfer phase the instrument displays the following messages: 

end

 “ for right programming. 

err

” for failed programming. In this case push “SET” key if you want to restart the programming again 

or remove the not programmed “

Hot key

”. 

10.

 

ALARM SIGNALS 

Message  Cause 

Outputs 

“P1” 

Thermostat probe failure 

Alarm output ON; Compressor output according to 
parameters “COn” and “COF” 

“P3” 

Display probe failure 

Alarm output ON; Other outputs unchanged 

“HA” 

Maximum temperature alarm 

Alarm output ON; Other outputs unchanged 

“LA” 

Minimum temperature alarm 

Alarm output ON; Other outputs unchanged 

“EE”   Data or memory failure 

Alarm output ON; Other outputs unchanged 

“dA” 

Door switch alarm 

Alarm output ON; Other outputs unchanged 

“EAL”  External alarm 

Alarm output ON; Other outputs unchanged 

“bAL”  Serious external alarm 

Alarm output ON; Other outputs OFF 

“PAL”  Pressure switch alarm 

Alarm output ON; Other outputs OFF

 

 
The alarm message is displayed until the alarm condition is recovery. 
All the alarm messages are showed alternating with the room temperature except for the “P1” which is 
flashing. To reset the “EE” alarm and restart the normal functioning press any key, the “

rSt

” message is 

displayed for about 3s. 

10.1

 

SILENCING BUZZER 

Once the alarm signal is detected the buzzer can be silenced by pressing any key.  

10.2

 

 “EE” ALARM 

The  Dixell  instruments  are  provided  with  an  internal  check  for  the  data  integrity.  Alarm  “EE”  flashes 
when a failure in the memory data occurs. In such cases the alarm output is enabled. 

10.3

 

ALARM RECOVERY 

Probe  alarms

  :  “

P1

”  (probe1  faulty)  and 

“P3”

;  they  automatically  stop  10s  after  the  probe  restarts 

normal operation. Check connections before replacing the probe. 

Temperature alarms

 “

HA

” and “

LA

” automatically stop as soon as the thermostat temperature returns 

to normal values or when the defrost starts. 

Door switch alarm

 “

dA

”  stop as soon as the door is closed. 

External alarms

 “

EAL

”, “

BAL

”  stop as soon as the external digital input is disabled  

Pressure switch alarm 

PAL” alarm is recovered by switching OFF the instrument

 
 
 
 
 
 
 
 
 
 
 

Содержание dixell XW30VS

Страница 1: ...mpressor operates in continuous mode for the time set through the CCt parameter The cycle can be terminated before the end of the set time using the same activation key o for about 3 seconds 3 3 DEFROST The defrost interval is control by means of parameter EdF EdF in the defrost is made every IdF time EdF Sd the interval IdF is calculate through Smart Defrost algorithm only when the compressor is ...

Страница 2: ...d rES Resolution for C in 1 C de 0 1 C allows decimal point display dE 0 1 C in 1 C Lod Local display select which probe is displayed by the instrument P1 Thermostat probe P3 Display probe P2 not set it 1r2 not set it DEFROST EdF Defrost mode in interval mode The defrost starts when the time Idf is expired Sd Smartfrost mode The time IdF interval between defrosts is increased only when the compres...

Страница 3: ...m the outputs and the power connections Do not exceed the maximum current allowed on each relay in case of heavier loads use a suitable external relay N B Maximum current allowed for all the loads is 20A 8 1 PROBE CONNECTIONS The probe shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration It is recommended to place the thermostat probe away from air streams to...

Страница 4: ...robe 0 255 min 15 Pr2 COF Compressor OFF time with faulty probe 0 255 min 30 Pr2 CH Type of regulation CL Ht CL Pr2 DISPLAY CF Temperature measurement unit C F C F Pr2 rES Resolution integer decimal point in de dE Pr1 Lod Local display P1 1r2 P1 Pr2 DEFROST EdF Defrost mode In Sd in Pr2 IdF Interval between defrost cycles 1 120h 8 Pr1 MdF Maximum length for 1 defrost 0 255 min 20 Pr1 dFd Displayin...

Отзывы: