                            XW30VS  - XW35VS 

2/4 

4.5

 

HOW TO SEE AND MODIFY THE SET POINT 

 

 

1.  Push and immediately release the 

SET 

key: the display will show the Set point value; 

2.  The SET LED start blinking; 
3.  To change the Set value push the 

or 

n

 arrows within 10s. 

4.  To memorise the new set point value push the 

SET

 key again or wait 10s. 

4.6

 

TO START A MANUAL DEFROST  

 

 
1.  Push the 

DEF 

key for more than 2 seconds and a manual defrost will start. 

4.7

 

TO ENTER IN PARAMETERS LIST “PR1”  

To enter the parameter list “Pr1” (user accessible parameters) operate as follows: 
 

 

 
1.  Enter the Programming mode by pressing the Set and DOWN key for few 

seconds (

 and 

 start blinking). 

 
2.  The instrument will show the first parameter present in “Pr1” 

 
 
 
 

4.8

 

TO ENTER IN PARAMETERS LIST “PR2” 

To access parameters in “

Pr2

”: 

1.

 

Enter the “Pr1” level. 

2.

 

Select “Pr2” parameter and press the “

SET

” key.  

3.

 

The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero. 

4.

 

Use 

o

 or 

n

 to input the security code in the flashing digit; confirm the figure by pressing “

SET

”. 

The security code is “321“. 

5.

 

If the security code is correct the access to “Pr2” is enabled by pressing “

SET

” on the last digit. 

 
Another possibility is the following: after switching ON the instrument the user can push Set and DOWN 
keys within 30 seconds. 
 

NOTE

: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing 

“SET”

 + 

n

When a parameter is present in “Pr1” LED 

 is on. 

 

4.9

 

HOW TO CHANGE THE PARAMETER VALUE 

1.

 

Enter the Programming mode. 

2.

 

Select the required parameter with 

o

 or 

n

3.

 

Press the “

SET

” key to display its value (

 and 

 LED starts blinking). 

4.

 

Use 

o

 or 

n

 to change its value. 

5.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + UP 

or wait 15s without pressing a key. 

NOTE

: the new programming is stored even when the procedure is exited by waiting the time-out. 

4.10

 

HOW TO LOCK THE KEYBOARD 

 

 

1.  

Keep the 

o

 and 

n

 keys pressed together for more than 3 s the 

o

 and 

n

 keys. 

2.  

The “POF” message will be displayed and the keyboard is locked. At this point it is 
only possible the viewing of the set point or the MAX o Min temperature stored and 
to switch ON and OFF the light, the auxiliary output and the instrument. 

 

TO UNLOCK THE KEYBOARD 

Keep the 

o

 and 

n

 keys pressed together for more than 3s. 

 

4.11

 

ON/OFF FUNCTION 

 

 

By  pushing the 

ON/OFF

 key, the instrument  shows “OFF” for 5 sec. and the ON/OFF 

LED is switched ON. 
During the OFF status, all the relays are switched OFF and the regulations are stopped;  

N.B. During the OFF status the Light button is active. 

 

 

4.12

 

TO SEE THE PROBE VALUES 

1. 

Enter in “

Pr2

” level. 

2. 

Select “

Prd

” parameter with 

o

 or 

n

3. 

Press the “

SET

” key to display “

Pb1” 

label alternate with Pb1 value. 

4. 

Use 

and 

n

 keys to display the other probe values.  

5. 

Press “

SET

” to move to the following parameter. 

 

5.

 

PARAMETER LIST 

REGULATION 
Hy  Differential: 

(0,1÷25,5°C;  1÷45°F):  Intervention  differential  for  set  point,  always  positive. 

Compressor  Cut  IN  is  Set  Point  Plus  Differential  (Hy).  Compressor  Cut  OUT  is  when  the 
temperature reaches the set point. 

LS  Minimum  set  point  limit: 

(-50,0°C

SET;  -58°F÷SET)  Sets  the  minimum  acceptable  value  for 

the set point. 

US  Maximum set point limit: 

(SET

110°C; SET÷230°F) Set the maximum acceptable value for set 

point. 

OdS Outputs activation delay at start up:

 (0÷255 min) This function is enabled at the initial start up 

of  the  instrument  and  inhibits  any  output  activation for the period of  time set in the parameter. 
(Light can work) 

AC  Anti-short  cycle  delay: 

(0÷30  min)  interval  between  the  compressor  stop  and  the  following 

restart. 

CCt  Thermostat override:

 (0min ÷23h 50min) allows to set the length of the continuous cycle. Can 

be used, for instance, when the room is filled with new products.

 

Con Compressor ON time with faulty probe: 

(0÷255 min) time during which the compressor is active 

in case of faulty thermostat probe. With COn=0 compressor is always OFF. 

COF Compressor OFF time with faulty probe: 

(0÷255 min) time during which the compressor is off 

in case of faulty thermostat probe. With COF=0 compressor is always active. 

CH  Type of action: 

CL = cooling; Ht = heating.

 

 
DISPLAY 
CF  Temperature measurement unit:

 °C = Celsius; °F = Fahrenheit. When the measurement unit is 

changed the SET point and the values  of some parameters have to be modified. 

rES  Resolution (for °C)

: (in = 1°C; de = 0,1°C) allows decimal point display. 

dE

 = 0,1°C; 

in

 = 1 °C  

Lod  Local display : 

select which probe is displayed by the instrument:

  

P1

 = Thermostat probe; 

P3

 = Display probe; 

P2: not set it, 1r2: not set it

 

DEFROST 
EdF  Defrost mode:

   

in

 = 

interval mode

. The defrost starts when the time “

Idf

” is expired. 

Sd

  = 

Smartfrost  mode

.  The  time  IdF  (interval  between  defrosts)  is  increased  only  when  the 

compressor  is  running  (even  non  consecutively)  and  only  if  the  evaporator  temperature  is  less 
than the value in "

SdF

” (set point for SMARTFROST).  

IdF  Interval between defrosts: 

(1÷120h) Determines the time interval between the beginning of two 

defrost cycles. 

MdF  (Maximum) duration of defrost: 

(0÷255 min) When 

P2P = n

, no evaporator probe, it sets the 

defrost duration, when 

P2P = y

, defrost end based on temperature, it sets the maximum length for 

defrost. 

dFd  Display during defrost:  
 

rt

 = real temperature; 

it

 = temperature reading at the defrost start; 

Set

 = set point; 

dEF

 = “dEF” label; 

 

dEG

 = “dEG” label;

 

dAd  Defrost display time out:

 (0

255 min) Sets the maximum time between the end of defrost and 

the restarting of the real room temperature display. 

dPO First defrost after start-up:   
 

= Immediately; 

n

 = after the IdF time 

dAF  Defrost delay after fast freezing: 

(0min÷23h 50min)  after a Fast Freezing cycle, the first defrost 

will be delayed for this time. 

FANS – Only for XR35VS 
FnC  Fan operating mode: 

C-n

 = running with the compressor, OFF during the defrost;  

C-y

 = running with the compressor, ON during the defrost; 

O-n

 = continuous mode, OFF during the defrost; 

O-y

 = continuous mode, ON during the defrost; 

Fnd  Fan delay after defrost:

 (0÷255 min)

 

The time interval between the defrost end and evaporator 

fans start.

 

ALARMS 
ALC Temperature alarm configuration 

rE

 = High and Low alarms related to Set Point  

Ab

 = High and low alarms related to the absolute temperature. 

ALU High temperature alarm setting:

  

 

ALC= rE, 0 

 

50°C or 90°F 

 

ALC= Ab, ALL 

 110°C or 230°F 

 

when this temperature is reached and after the ALd delay time the HA alarm is enabled. 

 

ALL  Low temperature alarm setting:

 

 

ALC = rE , 0 

 50 °C or 90°F 

 

ALC = Ab , - 50°C or -58°F 

 ALU 

 

when this temperature is reached and after the ALd delay time, the LA alarm is enabled,. 

AFH Temperature alarm differential: 

(0,1÷25,5°C; 1÷45°F) Intervention differential for temperature 

alarm set point, always positive.

 

ALd  Temperature alarm delay:

 (0÷255 min) time interval between the detection of an alarm condition 

and the corresponding alarm signalling. 

dAO Delay of temperature alarm at start-up:

 (0min÷23h 50min) time interval between the detection 

of the temperature alarm condition after the instrument power on and the alarm signalling.

 

EdA  Alarm  delay  at  the  end  of  defrost: 

(0

255  min)  Time  interval  between  the  detection  of  the 

temperature alarm condition at the end of defrost and the alarm signalling. 

dot   Delay  of  temperature  alarm  after  closing  the  door  : 

(0

255  min)  Time  delay  to  signal  the 

temperature alarm condition after closing the door. 

doA  Open door alarm delay:

(0÷255 min) delay between the detection of the open door condition and 

its alarm signalling: the flashing message “

dA

” is displayed. 

nPS  Pressure switch number:

 (0 

15) Number of activation of the pressure switch, during the “

did

” 

interval, before signalling the alarm event (I2F= PAL). 

If the nPS activation in the did time is reached, switch off and on the instrument to restart 

normal regulation. 

 

 

PROBE INPUTS 
Ot  Thermostat probe calibration: 

(-12.0

12.0°C/ -21

21°F) allows to adjust possible offset of the 

thermostat probe. 

O3    Display  probe  calibration: 

(-12.0

12.0°C/  -21

21°F)  allows  to  adjust  possible  offsets  of  the 

display probe. 

P3P  Display probe presence: n

= not present:; 

y=

 present:. 

HES Temperature increase during the Energy Saving cycle :

 (-30,0°C 

 30,0°C / -22÷86°F) sets 

the increasing value of the set point during the Energy Saving cycle.  

 

DIGITAL INPUTS 
odc  Compressor and fan status when open door:

  

no

 = normal; 

Fan

 = Fan OFF; 

CPr

 = Compressor OFF; 

 

F_C

 = Compressor and fan OFF.  

I2P  Configurable digital input polarity:

 

 

CL

 : the digital input is activated by closing the contact;

 

 

OP

 : the digital input is activated by opening the contact 

I2F  Digital input operating mode:

 configure the digital input function: 

 

EAL 

= generic alarm; 

 bAL 

= serious alarm mode; 

 

PAL 

=  Pressure  switch; 

  dFr 

=  Start 

defrost; 

 

AUS 

= Not used; 

Es 

= Energy Saving; 

onF 

= remote On/OFF; 

dor

 = door switch

 

did   Time interval/delay for digital input alarm:

(0

255 min.) If I2F=EAL or bAL (external alarms), 

“did” parameter defines the time delay between the detection and the successive signalling of the 
alarm. 

 

Содержание dixell XW30VS

Страница 1: ...mpressor operates in continuous mode for the time set through the CCt parameter The cycle can be terminated before the end of the set time using the same activation key o for about 3 seconds 3 3 DEFROST The defrost interval is control by means of parameter EdF EdF in the defrost is made every IdF time EdF Sd the interval IdF is calculate through Smart Defrost algorithm only when the compressor is ...

Страница 2: ...d rES Resolution for C in 1 C de 0 1 C allows decimal point display dE 0 1 C in 1 C Lod Local display select which probe is displayed by the instrument P1 Thermostat probe P3 Display probe P2 not set it 1r2 not set it DEFROST EdF Defrost mode in interval mode The defrost starts when the time Idf is expired Sd Smartfrost mode The time IdF interval between defrosts is increased only when the compres...

Страница 3: ...m the outputs and the power connections Do not exceed the maximum current allowed on each relay in case of heavier loads use a suitable external relay N B Maximum current allowed for all the loads is 20A 8 1 PROBE CONNECTIONS The probe shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration It is recommended to place the thermostat probe away from air streams to...

Страница 4: ...robe 0 255 min 15 Pr2 COF Compressor OFF time with faulty probe 0 255 min 30 Pr2 CH Type of regulation CL Ht CL Pr2 DISPLAY CF Temperature measurement unit C F C F Pr2 rES Resolution integer decimal point in de dE Pr1 Lod Local display P1 1r2 P1 Pr2 DEFROST EdF Defrost mode In Sd in Pr2 IdF Interval between defrost cycles 1 120h 8 Pr1 MdF Maximum length for 1 defrost 0 255 min 20 Pr1 dFd Displayin...

Отзывы: