Emerson dixell XW30VS Скачать руководство пользователя страница 4

 

1592009730 XW30-35VS GB r1.2 31.07.2015 

                            XW30VS  - XW35VS 

4/4 

11.

 

TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: 

facia 100x64 mm; depth 76mm 

Mounting:

 panel mounting in a 56x72 mm panel cut-out with two screws. 

 3x2mm. Distance between 

the holes 40mm 

Protection: 

IP20.

 

Frontal protection:

 IP65 with optional frontal gasket mod RGW-V (XW35VS). 

Connections: 

6,3mm faston heat-resistant wiring and/or 2,8mm for probes and d.i.  

Power supply: 

230Vac or. 110Vac 

 10% 

 

Power absorption: 

7VA max.

 

Display

: 3 digits, red LED, 14,2 mm high.  

Inputs

: 2 NTC or PTC probe 

Relay outputs:

 Total current on loads MAX. 20A

 

compressor:

 relay SPST 20(8) A, 250Vac or. SPST 8(3) A, 250Vac 

light: : 

relè SPST 16(6) A, 250Vac 

fans:

 relay SPST 8(3) A, 250Vac

 

Data storing

: on the non-volatile memory (EEPROM). 

Kind of action: 

1B. 

Pollution grade: 

normal 

Software class: 

A.

 

Operating temperature: 

0÷60 °C. 

Storage temperature: 

-25÷60 °C.  

Relative humidity:

 20

85% (no condensing) 

Measuring and regulation range:  

PTC probe: 

-50÷150°C (-58÷302°F) 

NTC probe: 

-40÷110°C (-58÷230°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable). 

Accuracy (ambient temp. 25°C)

:  ±0,5 °C ±1 digit 

  

12.

 

CONNECTIONS 

12.1

 

XW30VS 

Lig

ht

 

Power supply: use terminal 3-4;  according to the model 230Vac or 120Vac or 24Vac 

 

12.2

 

XW35VS 

Lig

ht

 

Power supply: use terminal 3-4; according to the model 230Vac or 120Vac or 24Vac 

 

 

 

 

 

 

13.

 

DEFAULT SETTING VALUES 

 

Label  Name 

  Range 

Default 

Level

 

 

REGULATION 

 

°C/°F 

 

Set 

Set point 

LS÷US 

3/37 

Pr1 

Hy 

Differential 

0,1÷25,5 °C / 1÷45°F 

2/4 

Pr1 

LS 

Minimum set point 

 -50,0°C÷SET / -

58°F÷SET 

-10/14 

Pr2 

US 

Maximum set point 

SET ÷ 110°C / SET ÷ 

230°F 

20/68 

Pr2 

OdS 

Outputs activation delay at start up 

0÷255 min. 

Pr2 

AC 

Anti-short cycle delay 

0÷30 min. 

Pr1 

CCt 

Compressor ON time during fast freezing 

0 ÷ 23h 50 min. 

0.0 

Pr2 

COn 

Compressor ON time with faulty probe 

0÷255 min. 

15 

Pr2 

COF 

Compressor OFF time with faulty probe 

0÷255 min. 

30 

Pr2 

CH 

Type of regulation 

CL, Ht 

CL 

Pr2 

 

DISPLAY 

 

 

 

CF 

Temperature measurement unit 

°C ÷ °F 

°C/F 

Pr2 

rES 

Resolution (integer/decimal point) 

in ÷ de 

dE/- 

Pr1 

Lod 

Local display  

P1 ÷ 1r2 

P1 

Pr2 

 

DEFROST 

 

 

 

EdF 

Defrost mode 

In, Sd 

in 

Pr2 

IdF 

Interval between defrost cycles 

1÷120h 

Pr1 

MdF 

(Maximum) length for 1° defrost 

0÷255 min. 

20 

Pr1 

dFd 

Displaying during defrost 

rt, it, SEt, dEF, dEG 

it 

Pr2 

dAd 

MAX display delay after defrost 

0÷255 min. 

30 

Pr2 

dPO 

First defrost after start up 

n ÷ y 

Pr2 

dAF 

Defrost delay after fast freezing 

0 ÷ 23h 50 min. 

0.0 

Pr2 

 

FANS- only XW35VS 

 

 

 

FnC 

Fans operating mode 

C-n, C-y, O-n, O-y  

O-n 

Pr2 

Fnd 

Fans delay after defrost 

0÷255 min. 

10 

Pr2 

 

ALARMS 

 

 

 

ALC 

Temperature alarms configuration 

rE÷Ab 

Ab 

Pr2 

ALU 

MAXIMUM temperature alarm 

-50,0÷110°C/ -58÷230°F  110/230 

Pr1 

ALL 

minimum temperature alarm 

-50,0÷110°C/ -58÷230°F  -40/-40 

Pr1 

AFH 

Temperature alarm differential 

0,1÷25,5 °C / 1÷45°F 

2/4 

Pr2 

ALd 

Temperature alarm delay 

0÷255 min. 

15 

Pr2 

dAO 

Delay of temperature alarm at start up 

0 ÷ 23h 50 min. 

1,3 

Pr2 

EdA 

Alarm delay at the end of defrost  

0÷255 min. 

30 

Pr2 

dot 

Delay  of  temperat.  alarm  after  closing  the 
door  

0÷255 min. 

15 

Pr2 

dOA 

Open door alarm delay  

0÷255 min. 

15 

Pr2 

nPS 

Pressure switch number 

0÷15 

Pr2 

 

ANALOGUE INPUTS 

 

 

 

Ot 

Thermostat probe calibration 

-12,0÷12,0°C / -21÷21°F 

0/0 

Pr2

 

O3 

Display probe calibration 

-12,0÷12,0°C / -21÷21°F 

0/0 

Pr2 

P3P 

Display probe presence 

n ÷ y 

Pr2 

HES 

Temperature  increasing  during  the  Energy 
Saving cycle 

-30÷30°F/-54÷54°F 

Pr2 

 

DIGITAL INPUTS 

 

 

 

Odc 

Open door control  

no, Fan, CPr, F_C 

no 

Pr2 

I2P 

Configurable digital input polarity 

CL÷OP 

cL 

Pr2 

i2F 

Digital input configuration 

dor, EAL, bAL, PAL, dFr,  

AUS, ES, OnF 

dor 

Pr2 

dId 

Digital input alarm delay 

0÷255 min. 

Pr2 

 

OTHER 

 

 

 

Adr 

Serial address 

0÷247 

Pr2 

Pbc 

Kind of probe 

PbC, ntc 

ntc/Ptc 

Pr2 

rEL 

Software release 

- - - 

2.0 

Pr2 

Ptb 

Map code 

- - - 

- - - 

Pr2 

Prd 

Probes display 

Pb1 

- - - 

Pr2 

Pr2  

Access parameter list 

- - - 

- - - 

Pr1 

 
 
 
 

 

Содержание dixell XW30VS

Страница 1: ...mpressor operates in continuous mode for the time set through the CCt parameter The cycle can be terminated before the end of the set time using the same activation key o for about 3 seconds 3 3 DEFROST The defrost interval is control by means of parameter EdF EdF in the defrost is made every IdF time EdF Sd the interval IdF is calculate through Smart Defrost algorithm only when the compressor is ...

Страница 2: ...d rES Resolution for C in 1 C de 0 1 C allows decimal point display dE 0 1 C in 1 C Lod Local display select which probe is displayed by the instrument P1 Thermostat probe P3 Display probe P2 not set it 1r2 not set it DEFROST EdF Defrost mode in interval mode The defrost starts when the time Idf is expired Sd Smartfrost mode The time IdF interval between defrosts is increased only when the compres...

Страница 3: ...m the outputs and the power connections Do not exceed the maximum current allowed on each relay in case of heavier loads use a suitable external relay N B Maximum current allowed for all the loads is 20A 8 1 PROBE CONNECTIONS The probe shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration It is recommended to place the thermostat probe away from air streams to...

Страница 4: ...robe 0 255 min 15 Pr2 COF Compressor OFF time with faulty probe 0 255 min 30 Pr2 CH Type of regulation CL Ht CL Pr2 DISPLAY CF Temperature measurement unit C F C F Pr2 rES Resolution integer decimal point in de dE Pr1 Lod Local display P1 1r2 P1 Pr2 DEFROST EdF Defrost mode In Sd in Pr2 IdF Interval between defrost cycles 1 120h 8 Pr1 MdF Maximum length for 1 defrost 0 255 min 20 Pr1 dFd Displayin...

Отзывы: