1592016130 XV300K EN MASTER r1.1 16.06.2015
XV300K
20/26
15.1
BASIC
SETTINGS
Allows to load one of the settings based on the below tables. Select one
setting to speed the programming up.
Caution:
previous settings will be overwritten; as for the Master pre-settings the values of SPD1 and SPD2 will be of
20% and 90% respectively.
CHILLER
2
Input
type
Scale
COOL
HEAT
P1
P2
MaxP
P1
P2
MaxP
MPRZM_34
0,5..4,5V
0..34,5 bar
13 bar
18 bar
19 bar
4 bar
6 bar
3 bar
MPRZM_45
0,5..4,5V
0..45 bar
20 bar
24 bar
25 bar
7 bar
11 bar
5 bar
MP420_30
4..20 mA
0..30 bar
13 bar
18 bar
19 bar
4 bar
6 bar
3 bar
MP420_50
4..20 mA
0..50 bar
20 bar
24 bar
25 bar
7 bar
11 bar
5 bar
DRY COOLER
Input type
COOL
HEAT
T1
T2
MaxT
T1
T2
MaxT
MTNTC_L
10kΩ @ 25°C (β3435)
22°C
28°C
29°C
22°C
24°C
21°C
MTNTC_H
10kΩ @ 25°C (β3435)
38°C
45°C
46°C
22°C
24°C
21°C
SLAVE
2
Input type
IN. MIN.
IN. MAX
V1
V2
S0_10
0..10V /Pwm
10%
100%
20%
100%
S4_20
4..20mA
10%
100%
20%
100%
S_MDB
Modbus RTU
S_PWM FV
Pwm FV
Allows selecting the motor adjusting curve.
Possible modes:
Q
= optimized for fans (Def.),
L
= linear
Allows forbidding the access to the “Operating parameters” menu.
ON (Def.): allows the access
OFF: forbids the access
Defines the type of signal used.
4-20 mA
(Def.): analogical signal 4-20mA;
0,5-4,5 V
: analogical signal 0,5-4,5 V=
Defines the type of signal used.
0-10 V
(Def.): analog signal 0..10V= , or
pwm
100Hz type with variable
average value
Range
: 5...15V.
PWM fv
: variable frequency pwm (do not use it).
modbus
: Controlled by Master controller on RTU Modbus transmission
0..10
IN. TYPE
[IB]
*
SLA
VE
CHILL
E
R
4..20 mA
INPUT
TYPE
[IB]
*
ON
[IB]
*
USER ACTIV
Q
[IB]
*
REG. MODE
PRESET.
[IB]