1592016130 XV300K EN MASTER r1.1 16.06.2015
XV300K
19/26
COOL cycle: For V1 Limit > V1 of the active cycle, if the pressure/temperature is lower than P1/T1, the Voltage OUT
(Vout%) will be fixed at the value of the V1 Limit (see for example the below chart 2).
HEAT cycle: For V1 Limit > V1 of the active cycle, if the pressure/temperature is higher than P2/T2, the voltage OUT
(Vout%) will be fixed at the value of the V1 Limit (see for example the below chart 4).
Voltage that replaces V2, in the Master cycle used, when the max
productions
I2 contact
is closed.
Min.
V1 Limit
Max.
MotorMaxLim
Def. 65%
[WITH CLOCK OPTION]
Allows enabling the V1 and V2 limits in the Master operating cycles, not only
by closing the I2 contact, but also through the timer calendar set in the
Clock menu (page
Error! Bookmark not defined.
). Def. OFF
15 FACTORY PARAMETERS MENU
To access the factory parameters menu press
, enter the number 0023
through the key
, press
to save
Caution
: When entering this menu, all the analogic outputs of the device will be closed and the adjusting operation will
be stopped until the menu is closed.
0000
PIN
[PW]
Off
ENAB W/TIME
[LV]
*
65
V2 LIMIT
[LV]
%