background image

 

1592020680 XRi60CH EN r2.0 2021.07.14

 

XRi60CH

 

5/9

 

ENERGY SAVING 

HES 

Energy saving mode temperature differential:

 (-30 to 30°C; -54 to 54°F) sets the 

increasing value of the set point during the Energy Saving cycle.

 

LdE 

Energy saving controls the lights (lights OFF when energy saving is active): 

(n; 

Y) lights off when energy saving mode is active

 

REAL TIME CLOCK 

Hur 

Hours: 

0 to 23 hours

 

Min 

Minutes:

 0 to 59 minutes

 

dAY 

Day of the week:

 Sun to Sat

 

dYM 

Day of the month:

 1 to 31 

Mon 

Month:

 1 to 12 

YAr 

Year:

 00 to 99 

Hd1 

First day of weekend: 

(Sun to SAt; nu) setting for the first day of the weekend.

 

Hd2 

Second day of weekend: 

(Sun to SAt; nu) setting for the second day of the 

weekend.

 

iLE 

Energy saving cycle start time on working days:

 (00h00min to 23h50min) 

during the Energy Saving cycle, the set point is increased by the value in HES 

so that the operation set point is 

SET+HES

.

 

dLE 

Energy saving cycle duration on working days:

 (00h00min to 24h00min) 

sets the duration of the Energy Saving cycle on working days.

 

iSE 

Energy saving cycle start time on weekends:

 00h00min to 23h50min

 

dSE 

Energy saving cycle duration on weekends:

 00h00min to 24h00min

 

dd1…dd6

 

Daily defrost enabled:

 (n; Y) to enable the 

Ld1 to Ld6

 defrost operations for 

any day of the week. 

 

dd1

 = Sunday defrost 

 

dd2

 = Monday defrost 

 

dd3

 = Tuesday defrost 

 

dd4

 = Wednesday defrost 

 

dd5

 = Thursday defrost 

 

dd6

 = Friday defrost 

 

dd7

 = Sunday defrost 

Ld1…Ld6

 

Defrost start time:

 (00h00min to 23h50min) these parameters set the 

beginning of the programmable defrost cycles during any 

ddx

 day. Example: 

when 

Ld2=12.4,

 the second defrost starts at 12:40 am during working days.

 

 

N.B.: To disable a defrost cycle set it to 

“nu”

 (not used).  

Ex: 

if

 Ld6=nu

;

 

the sixth defrost cycle will 

be disabled. 

OTHER 

Adr 

Serial address:

 (1 to 247) device address for Modbus communication 

bAU 

Baudrate: 

(9.6; 19.2) select the correct baudrate for serial communication  

onC 

ONOFF button configuration:

  

 

nU

 = not used 

 

oFF

 = to switch on and off the device  

 

ES

 = energy saving mode 

on2 

ONOFF button timed configuration (3 sec):  

 

nU

 = disabled  

 

oFF

 = to switch on and off the device  

 

ES

 = energy saving mode 

LGC 

Light button (left upper side) configuration:

  

 

nu

 = not used 

 

 

LiG

 = to activate and deactivate light output 

 

 

AUS

 = to activate and deactivate the auxiliary output 

 

 

Lnt

 = configuration map change

 

LG2 

Light button (left upper side) timed configuration (3 sec):

  

 

nu

 = not used 

 

 

LiG

 = to activate and deactivate light output 

 

 

AUS

 = to activate and deactivate the auxiliary output 

 

 

Lnt

 = configuration map change

 

dFC 

DEF button (left middle side) configuration: 

 

nu

 = not used

 

 

Pb2 

= show current Probe Pb2 value

 

 

AUS

 = to activate and deactivate the auxiliary output

 

dF2 

DEF button (left middle side) timed configuration (3 sec): 

 

nu

 = not used

 

 

dEF 

= defrost activation

 

 

AUS

 = to activate and deactivate the auxiliary output

 

dnC 

Down button configuration:  

 

nU

 = not used

 

 

Std

 = lower temperature value 

 

 

Lnt

 = configuration map change 

 

 

Pdn

 = force Pull Down mode

 

dn2 

Down button timed configuration (3 sec):  

 

nU

 = not used

 

 

Std

 = lower temperature value 

 

 

Lnt

 = configuration map change 

 

 

Pdn

 = force Pull Down mode

 

dP1 

Probe P1 value visualization 

dP2 

Probe P2 value visualization 

dP3 

Probe P3 value visualization 

dP4 

Probe P4 value visualization 

SPd 

Real regulation

 

Speed 

rSE 

Real set point

: it shows the set point used during the energy saving cycle or during 

the continuous cycle. 

rEL 

Firmware release

 for internal use. 

Ptb 

Parameter table code

: readable only. 

13.

 

DIGITAL INPUTS  

The first digital input (terminals 18-20) is enabled with 

P3P=n

The free voltage digital inputs are programmable by the 

i1F

 parameter. 

13.1

 

GENERIC ALARM (i1F = EAL) 

As soon as the digital input is activated the unit will wait for 

did

 

time delay before signalling the “

EAL

” 

alarm message. The outputs status does

n’t 

change. The alarm stops just after the digital input is de-

activated. 

13.2

 

SERIOUS ALARM MODE (i1F = bAL) 

When the digital input is activated, the unit will wait for 

did

 

delay before signalling the “

CA

” alarm 

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-

activated. 

13.3

 

EXTERNAL PRESSURE ALARM (i1F =PAL) 

It is used to detect any pressure external alarm. This signal locks the regulation after detecting 

nPS

 

events in the interval 

dxd

13.4

 

DOOR SWITCH INPUT (i1F = dor) 

It signals the door status and the corresponding relay output status through the 

odC

 parameter:  

no

 = normal (any change); 

FAn

 = Fan OFF; 

CPr

 = Compressor OFF; 

F_C

 = Compressor and fan OFF. 

Since the door is opened, after the delay time set through parameter 

doA

, the door alarm is enabled, 

the display shows the message 

dA

 and the regulation restarts is

 rtr=Y

. The alarm stops as soon as 

the external digital input is disabled again. With the door open, the high and low temperature alarms 

are disabled. 

13.5

 

START DEFROST (i1F = dEF) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will 

restart only if the digital input is disabled otherwise the instrument will wait until the 

MdF

 safety time is 

expired. 

13.6

 

SWITCH THE AUXILIARY RELAY (i1F = AUS) 

With 

oAx=AUS

 the digital input switched the status of the auxiliary relay. 

13.7

 

INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1F = Htr)  

This function allows inverting the regulation of the controller: from cooling to heating and viceversa. 

13.8

 

ENERGY SAVING (i1F = ES) 

The  Energy  Saving function  allows  to  change the  set  point  value  as the  result  of  the 

[SET+HES]

 

(parameter) sum. This function is enabled until the digital input is activated. 

13.9

 

ON OFF FUNCTION (i1F = onF)  

To switch the controller on and off. 

13.10

 

CHANGE PARAMETER MAP (i1F = Lnt) 

To move from LT to NT parameter map. 

13.11

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the 

i1P

 parameter. 

 

i1P=CL

, the input is activated by closing the contact.

 

 

i1P=OP

, the input is activated by opening the contact. 

14.

 

SERVICE SERIAL PORT  

A  specific  serial  tool  (XJ485CX)  can  be  connected  to  the  HOTKEY  port  to  change  parameter 

configuration. To do this, set par 

1Ao=n

: the frequency output must be disabled to use the service 

serial port. 

15.

 

INSTALLATION AND MOUNTING 

 

 

 

 

Instrument 

XRi60CH

 shall be mounted on vertical panel, in a 29x71 mm hole, and fixed using the 

special bracket supplied. The temperature range allowed for correct operation is 0 to 60°C. Avoid 

places  subject  to  strong  vibrations,  corrosive  gases,  excessive  dirt  or  humidity.  The  same 

recommendations apply to probes. Let air circulate by the cooling holes. 

16.

 

ELECTRICAL CONNECTIONS 

The instrument is provided with screw terminal block to connect cables with a cross section up to 

2.5mm2.  Before  connecting  cables  make  sure  the  power  supply  complies  with  the  instrument’s

 

requirements.  Separate the probe cables from the power supply cables, from the outputs and the 

power connections. Do not exceed the maximum current allowed on each relay, in case of heavier 

loads use a suitable external relay. 

Содержание Dixell XRi60CH

Страница 1: ...porator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 2 1 PRE DEFROST The par dAF enable a pre defrost phase During this interval the regulation setpoint will be moved to the value SET 1 C or SET 1 F The defrost phase starts as soon as the regulation temperature reach the pre defrost setpoint or when the...

Страница 2: ...the maximum compressor speed FMA until reaching the CCS setpoint The maximum interval of time for any PULL DOWN is defined from par CCt 8 2 OIL MIGRATION CONTROL VALID ONLY FOR VSC To avoid oil migration during variable speed compressor operation a lubrication control is implemented If the compressor works with a speed lower than the MnP threshold for tMi time then the compressor speed will be inc...

Страница 3: ...T HY1 Variable Speed Compressor Differential in normal mode 0 1 to 25 5 C 1 to 45 F odS Output activation delay at start up 0 to 255 min this function is enabled after the instrument power on and delays the output activations AC Anti short cycle delay 0 to 999 sec minimum interval between a compressor stop and the following restart AC1 Anti short cycle delay 2nd compressor 0 to 999 sec delay befor...

Страница 4: ...ating CL cooling SAA Set Point for auxiliary regulator 100 0 to 150 0 C 148 to 302 F it defines the room temperature set point to switch auxiliary relay SHY Auxiliary regulator differential 0 1 to 25 5 C 1 to 45 F differential for auxiliary output set point ACH CL AUX Cut in is SAA SHY AUX Cut out is SAA ACH Ht AUX Cut in is SAA SHY AUX Cut out is SAA ArP Probe selection for auxiliary regulator nP...

Страница 5: ...lease for internal use Ptb Parameter table code readable only 13 DIGITAL INPUTS The first digital input terminals 18 20 is enabled with P3P n The free voltage digital inputs are programmable by the i1F parameter 13 1 GENERIC ALARM i1F EAL As soon as the digital input is activated the unit will wait for did time delay before signalling the EAL alarm message The outputs status doesn t change The ala...

Страница 6: ...l operation Check connections before replacing the probe Temperature alarms HA and LA automatically stop as soon as the temperature returns to normal values Alarms EA and CA with ixF bAL PAL recover as soon as the digital input is disabled 18 3 OTHER MESSAGES Pon Keyboard unlocked PoF Keyboard locked noP In programming mode no parameter in Pr1 On the display or in dP2 dP3 dP4 the selected probe is...

Страница 7: ...tor fan controlled during defrost no no Pr2 Fon Evaporator fan ON time in normal mode with compressor OFF 0 0 Pr2 min FoF Evaporator fan OFF time in normal mode with compressor OFF 0 0 Pr2 min FAC Probe selection for condenser fan nP nP Pr2 St2 Set Point 2 Regulation for condenser fan 0 0 15 0 Pr2 C Hy2 Set Point 2 differential for condenser fan 1 0 10 0 Pr2 C FCC Condenser fan operating mode O_n ...

Страница 8: ...0 Pr2 hh mm Adr Serial address 1 1 Pr2 bAU Baudrate 9 6 9 6 Pr2 onC ONOFF button configuration left upper side nU nU Pr2 on2 ONOFF button timed 3sec configuration left upper side oFF oFF Pr2 LGC Light button configuration left upper side LiG LiG Pr2 LG2 Light button timed 3sec configuration left upper side nU nU Pr2 dFC DEF button configuration left upper side Pb2 Pb2 Pr2 dF2 DEF button timed 3sec...

Страница 9: ...50T150 C resolution 0 1 C or 1 C selectable Accuracy 0 7 C 1 digit and relative to the full scale Inputs 4 NTC PTC or PT1000 configurable 1 voltage free contacts I O port HOT KEY MAX voltage allowed is 5 VDC DO NOT CONNECT ANY EXTERNAL POWER SUPPLY Buzzer Optional Serial Outputs TTL standard available on 5 pin port HOT KEY connector Maximum cable length 2m Relay Outputs standard Ref Nominal UL IEC...

Отзывы: