1592020680 XRi60CH EN r2.0 2021.07.14
XRi60CH
5/9
ENERGY SAVING
HES
Energy saving mode temperature differential:
(-30 to 30°C; -54 to 54°F) sets the
increasing value of the set point during the Energy Saving cycle.
LdE
Energy saving controls the lights (lights OFF when energy saving is active):
(n;
Y) lights off when energy saving mode is active
REAL TIME CLOCK
Hur
Hours:
0 to 23 hours
Min
Minutes:
0 to 59 minutes
dAY
Day of the week:
Sun to Sat
dYM
Day of the month:
1 to 31
Mon
Month:
1 to 12
YAr
Year:
00 to 99
Hd1
First day of weekend:
(Sun to SAt; nu) setting for the first day of the weekend.
Hd2
Second day of weekend:
(Sun to SAt; nu) setting for the second day of the
weekend.
iLE
Energy saving cycle start time on working days:
(00h00min to 23h50min)
during the Energy Saving cycle, the set point is increased by the value in HES
so that the operation set point is
SET+HES
.
dLE
Energy saving cycle duration on working days:
(00h00min to 24h00min)
sets the duration of the Energy Saving cycle on working days.
iSE
Energy saving cycle start time on weekends:
00h00min to 23h50min
dSE
Energy saving cycle duration on weekends:
00h00min to 24h00min
dd1…dd6
Daily defrost enabled:
(n; Y) to enable the
Ld1 to Ld6
defrost operations for
any day of the week.
•
dd1
= Sunday defrost
•
dd2
= Monday defrost
•
dd3
= Tuesday defrost
•
dd4
= Wednesday defrost
•
dd5
= Thursday defrost
•
dd6
= Friday defrost
•
dd7
= Sunday defrost
Ld1…Ld6
Defrost start time:
(00h00min to 23h50min) these parameters set the
beginning of the programmable defrost cycles during any
ddx
day. Example:
when
Ld2=12.4,
the second defrost starts at 12:40 am during working days.
N.B.: To disable a defrost cycle set it to
“nu”
(not used).
Ex:
if
Ld6=nu
;
the sixth defrost cycle will
be disabled.
OTHER
Adr
Serial address:
(1 to 247) device address for Modbus communication
bAU
Baudrate:
(9.6; 19.2) select the correct baudrate for serial communication
onC
ONOFF button configuration:
•
nU
= not used
•
oFF
= to switch on and off the device
•
ES
= energy saving mode
on2
ONOFF button timed configuration (3 sec):
•
nU
= disabled
•
oFF
= to switch on and off the device
•
ES
= energy saving mode
LGC
Light button (left upper side) configuration:
•
nu
= not used
•
LiG
= to activate and deactivate light output
•
AUS
= to activate and deactivate the auxiliary output
•
Lnt
= configuration map change
LG2
Light button (left upper side) timed configuration (3 sec):
•
nu
= not used
•
LiG
= to activate and deactivate light output
•
AUS
= to activate and deactivate the auxiliary output
•
Lnt
= configuration map change
dFC
DEF button (left middle side) configuration:
•
nu
= not used
•
Pb2
= show current Probe Pb2 value
•
AUS
= to activate and deactivate the auxiliary output
dF2
DEF button (left middle side) timed configuration (3 sec):
•
nu
= not used
•
dEF
= defrost activation
•
AUS
= to activate and deactivate the auxiliary output
dnC
Down button configuration:
•
nU
= not used
•
Std
= lower temperature value
•
Lnt
= configuration map change
•
Pdn
= force Pull Down mode
dn2
Down button timed configuration (3 sec):
•
nU
= not used
•
Std
= lower temperature value
•
Lnt
= configuration map change
•
Pdn
= force Pull Down mode
dP1
Probe P1 value visualization
dP2
Probe P2 value visualization
dP3
Probe P3 value visualization
dP4
Probe P4 value visualization
SPd
Real regulation
Speed
rSE
Real set point
: it shows the set point used during the energy saving cycle or during
the continuous cycle.
rEL
Firmware release
for internal use.
Ptb
Parameter table code
: readable only.
13.
DIGITAL INPUTS
The first digital input (terminals 18-20) is enabled with
P3P=n
.
The free voltage digital inputs are programmable by the
i1F
parameter.
13.1
GENERIC ALARM (i1F = EAL)
As soon as the digital input is activated the unit will wait for
did
time delay before signalling the “
EAL
”
alarm message. The outputs status does
n’t
change. The alarm stops just after the digital input is de-
activated.
13.2
SERIOUS ALARM MODE (i1F = bAL)
When the digital input is activated, the unit will wait for
did
delay before signalling the “
CA
” alarm
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated.
13.3
EXTERNAL PRESSURE ALARM (i1F =PAL)
It is used to detect any pressure external alarm. This signal locks the regulation after detecting
nPS
events in the interval
dxd
.
13.4
DOOR SWITCH INPUT (i1F = dor)
It signals the door status and the corresponding relay output status through the
odC
parameter:
no
= normal (any change);
FAn
= Fan OFF;
CPr
= Compressor OFF;
F_C
= Compressor and fan OFF.
Since the door is opened, after the delay time set through parameter
doA
, the door alarm is enabled,
the display shows the message
dA
and the regulation restarts is
rtr=Y
. The alarm stops as soon as
the external digital input is disabled again. With the door open, the high and low temperature alarms
are disabled.
13.5
START DEFROST (i1F = dEF)
It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will
restart only if the digital input is disabled otherwise the instrument will wait until the
MdF
safety time is
expired.
13.6
SWITCH THE AUXILIARY RELAY (i1F = AUS)
With
oAx=AUS
the digital input switched the status of the auxiliary relay.
13.7
INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1F = Htr)
This function allows inverting the regulation of the controller: from cooling to heating and viceversa.
13.8
ENERGY SAVING (i1F = ES)
The Energy Saving function allows to change the set point value as the result of the
[SET+HES]
(parameter) sum. This function is enabled until the digital input is activated.
13.9
ON OFF FUNCTION (i1F = onF)
To switch the controller on and off.
13.10
CHANGE PARAMETER MAP (i1F = Lnt)
To move from LT to NT parameter map.
13.11
DIGITAL INPUTS POLARITY
The digital input polarity depends on the
i1P
parameter.
•
i1P=CL
, the input is activated by closing the contact.
•
i1P=OP
, the input is activated by opening the contact.
14.
SERVICE SERIAL PORT
A specific serial tool (XJ485CX) can be connected to the HOTKEY port to change parameter
configuration. To do this, set par
1Ao=n
: the frequency output must be disabled to use the service
serial port.
15.
INSTALLATION AND MOUNTING
Instrument
XRi60CH
shall be mounted on vertical panel, in a 29x71 mm hole, and fixed using the
special bracket supplied. The temperature range allowed for correct operation is 0 to 60°C. Avoid
places subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same
recommendations apply to probes. Let air circulate by the cooling holes.
16.
ELECTRICAL CONNECTIONS
The instrument is provided with screw terminal block to connect cables with a cross section up to
2.5mm2. Before connecting cables make sure the power supply complies with the instrument’s
requirements. Separate the probe cables from the power supply cables, from the outputs and the
power connections. Do not exceed the maximum current allowed on each relay, in case of heavier
loads use a suitable external relay.