1592020680 XRi60CH EN r2.0 2021.07.14

 

XRi60CH

 

7/9

 

rSr 

PI regulator: range for output value calculation (RPM * 

10) 

40 

120 

Pr2  RPM*10 

Str 

PI regulator: delay before range drift 

60 

20 

Pr2 

sec 

dPt 

PI regulator: divisor for PI response time reduction 

(acts on both par. tSt and iSt) 

Pr2 

 

SAt 

Sampling time to calculate the average compressor 

speed before any desfrost cycle 

Pr2 

min 

CMn 

Continuous control ON in normal mode 

yes 

no 

Pr2 

 

CME 

Continuous control ON in energy saving 

yes 

no 

Pr2 

 

MnP 

Compressor speed threshold to activate lubrication 

(valid only for variable speed compressors, 

0=disabled) 

nu 

nu 

Pr2 

tMi 

Time range with compressor speed below MnP to 

activate lubrication cycle 

00:00  00:00  Pr2 

hh:mm 

tMA 

Time range with compressor speed at 100% to 

activate lubrication cycle 

Pr2 

min 

CF 

Temperature measurement unit: Celsius; Fahrenheit 

°C 

°C 

Pr2 

 

rES 

Temperature resolution: decimal, integer   

dE 

dE 

Pr2 

 

Lod 

Probe default displayed 

P1 

P1 

Pr2 

 

dLy 

Temperature display delay (resolution 10 sec) 

00:00  00:00  Pr2 

min 

dtr 

Probe visualization percentage=F(P1;P2) (ex: dtr=1 

means VALUE=0.01*P1+0.99*P2) 

99 

99 

Pr2 

 

EdF 

Defrost mode 

in 

in 

Pr2 

 

tdF 

Defrost type: electric heating, hot gas 

in 

in 

Pr2 

 

dFP 

Probe selection for defrost control 

P2 

P2 

Pr1 

 

dtE 

End defrost temperature 

8.0 

12.0 

Pr2 

°C 

idF 

Interval between two successive defrost cycles 

12 

12 

Pr1 

hh 

MdF 

Maximum length of defrost cycle 

30 

30 

Pr1 

min 

dSd 

Start defrost delay 

Pr2 

sec 

StC 

Compressor off-cycle before starting any defrost 

Pr2 

sec 

dFd 

Displaying during defrost 

dEF 

dEF 

Pr2 

 

dAd 

Temperature display delay after any defrost cycle 

Pr2 

min 

Fdt 

Draining time 

Pr2 

min 

Hon 

Drain heater enabled after draining time (par. Fdt) 

00:00  00:00  Pr2 

hh:mm 

dPo 

Defrost cycle enebled at stat-up 

no 

no 

Pr2 

 

Pd2 

Defrost output deactivation delay 

Pr2 

sec 

dAF 

Pre-defrost time 

Pr2 

min 

FAP 

Probe selection for evaporator fan 

nP 

nP 

Pr2 

 

FSt 

Evaporator fan stop temperature 

0.0 

10.0 

Pr2 

°C 

HyF 

Evaporator fan regulator differential 

1.0 

2.0 

Pr2 

°C 

FnC 

Evaporator fan operating mode 

C_n 

C_n 

Pr2 

 

Fnd 

Evaporator fan delay after defrost cycle 

Pr2 

min 

FCt 

Differential temperature for cyclic activation of 

evaporator fans (0=disabled) 

Pr2 

°C 

Ft 

Evaporator fan controlled during defrost  

no 

no 

Pr2 

 

Fon 

Evaporator fan ON time in normal mode (with 

compressor OFF)  

Pr2 

min 

FoF 

Evaporator fan OFF time in normal mode (with 

compressor OFF) 

Pr2 

min 

FAC 

Probe selection for condenser fan 

nP 

nP 

Pr2 

 

St2 

Set Point 2 Regulation (for condenser fan) 

0.0 

15.0 

Pr2 

°C 

Hy2 

Set Point 2 differential (for condenser fan) 

1.0 

10.0 

Pr2 

°C 

FCC 

Condenser fan operating mode 

O_n 

C_n 

Pr2 

 

Fd4 

Condenser fan deactivation delay 

Pr2 

sec 

ALP 

Probe selection for temperature alarms 

P1 

P1 

Pr1 

 

ALC 

Temperature alarms configuration: relative, absolute 

Ab 

Ab 

Pr1 

 

ALU 

High temperature alarm 

150.0  150.0  Pr1 

°C 

ALL 

Low temperature alarm 

-100.0 

-

100.0  Pr1 

°C 

AFH 

Temperature alarm differential 

2.0 

2.0 

Pr1 

°C 

ALd 

Temperature alarm delay 

Pr1 

min 

dAo 

Temperature alarm delay at start-up 

00:00  00:00  Pr1 

hh:mm 

AP2 

Probe selection for 2nd temperature alarm 

nP 

nP 

Pr2 

 

AL2 

2nd low temperature alarm 

-20.0 

0.0 

Pr2 

°C 

AU2 

2nd high temperature alarm 

20.0 

0.0 

Pr2 

°C 

AH2 

2nd temperature alarm differential 

2.0 

0.1 

Pr2 

°C 

Ad2 

2nd temperature alarm delay 

Pr2 

min 

dA2 

2nd temperature alarm delay at start-up 

00:00  00:00  Pr2 

hh:mm 

bLL 

Compressor OFF due to 2nd low temperature alarm 

no 

no 

Pr2 

 

AC2 

Compressor OFF due to 2nd high temperature alarm 

no 

no 

Pr2 

 

SAF 

Differential for anti-freezing control 

0.0 

0.0 

Pr2 

°C 

tbA 

Alarm relay deactivation 

yes 

yes 

Pr2 

 

oA1 

Relay output oA1 configuration 

dEF 

dEF 

Pr2 

 

oA2 

Relay output oA2 configuration 

LiG 

LiG 

Pr2 

 

oA3 

Relay output oA3 configuration 

Fan 

Fan 

Pr2 

 

AOP 

Alarm relay polarity 

CL 

CL 

Pr2 

 

1Ao 

Analogue output 1 configuration 

FrE 

FrE 

Pr2 

 

ibt 

Base times for digital inputs 

SEC 

SEC 

Pr1 

 

i1P 

Digital input 1 polarity 

CL 

CL 

Pr1 

 

i1F 

Digital input 1 configuration 

nu 

EAL 

Pr1 

 

d1d 

Digital inputs 1 alarm delay (base time depends on 

par. ibt) 

Pr1 

sec 

nPS 

Number of external pressure switch alarms before 

stopping the regulation 

15 

Pr2 

 

OdC 

Compressor and fan status after door opening 

F-C 

no 

Pr2 

 

rrd 

Regulation restart after door alarm 

no 

no 

Pr2 

 

HES 

Temperature differential in energy saving 

0.0 

0.0 

Pr1 

°C 

LdE 

ErA controls the lights in energy saving (lights OFF 

when energy saving goes active) 

yes 

no 

Pr1 

 

Hur 

Hours 

 

 

Pr1 

 

Min 

Minutes 

 

 

Pr1 

 

dAY 

Day of the week 

 

 

Pr1 

 

dyM 

Day of the month 

 

 

Pr1 

 

Mon 

Month 

 

 

Pr1 

 

yAr 

Year 

 

 

Pr1 

 

Hd1 

First day of weekend 

Sat 

Sat 

Pr2 

 

Hd2 

2nd day of weekend 

Sun 

Sun 

Pr2 

 

iLE 

Energy saving cycle starting time on working days 

00:00  00:00  Pr2 

hh:mm 

Содержание Dixell XRi60CH

Страница 1: ...porator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 2 1 PRE DEFROST The par dAF enable a pre defrost phase During this interval the regulation setpoint will be moved to the value SET 1 C or SET 1 F The defrost phase starts as soon as the regulation temperature reach the pre defrost setpoint or when the...

Страница 2: ...the maximum compressor speed FMA until reaching the CCS setpoint The maximum interval of time for any PULL DOWN is defined from par CCt 8 2 OIL MIGRATION CONTROL VALID ONLY FOR VSC To avoid oil migration during variable speed compressor operation a lubrication control is implemented If the compressor works with a speed lower than the MnP threshold for tMi time then the compressor speed will be inc...

Страница 3: ...T HY1 Variable Speed Compressor Differential in normal mode 0 1 to 25 5 C 1 to 45 F odS Output activation delay at start up 0 to 255 min this function is enabled after the instrument power on and delays the output activations AC Anti short cycle delay 0 to 999 sec minimum interval between a compressor stop and the following restart AC1 Anti short cycle delay 2nd compressor 0 to 999 sec delay befor...

Страница 4: ...ating CL cooling SAA Set Point for auxiliary regulator 100 0 to 150 0 C 148 to 302 F it defines the room temperature set point to switch auxiliary relay SHY Auxiliary regulator differential 0 1 to 25 5 C 1 to 45 F differential for auxiliary output set point ACH CL AUX Cut in is SAA SHY AUX Cut out is SAA ACH Ht AUX Cut in is SAA SHY AUX Cut out is SAA ArP Probe selection for auxiliary regulator nP...

Страница 5: ...lease for internal use Ptb Parameter table code readable only 13 DIGITAL INPUTS The first digital input terminals 18 20 is enabled with P3P n The free voltage digital inputs are programmable by the i1F parameter 13 1 GENERIC ALARM i1F EAL As soon as the digital input is activated the unit will wait for did time delay before signalling the EAL alarm message The outputs status doesn t change The ala...

Страница 6: ...l operation Check connections before replacing the probe Temperature alarms HA and LA automatically stop as soon as the temperature returns to normal values Alarms EA and CA with ixF bAL PAL recover as soon as the digital input is disabled 18 3 OTHER MESSAGES Pon Keyboard unlocked PoF Keyboard locked noP In programming mode no parameter in Pr1 On the display or in dP2 dP3 dP4 the selected probe is...

Страница 7: ...tor fan controlled during defrost no no Pr2 Fon Evaporator fan ON time in normal mode with compressor OFF 0 0 Pr2 min FoF Evaporator fan OFF time in normal mode with compressor OFF 0 0 Pr2 min FAC Probe selection for condenser fan nP nP Pr2 St2 Set Point 2 Regulation for condenser fan 0 0 15 0 Pr2 C Hy2 Set Point 2 differential for condenser fan 1 0 10 0 Pr2 C FCC Condenser fan operating mode O_n ...

Страница 8: ...0 Pr2 hh mm Adr Serial address 1 1 Pr2 bAU Baudrate 9 6 9 6 Pr2 onC ONOFF button configuration left upper side nU nU Pr2 on2 ONOFF button timed 3sec configuration left upper side oFF oFF Pr2 LGC Light button configuration left upper side LiG LiG Pr2 LG2 Light button timed 3sec configuration left upper side nU nU Pr2 dFC DEF button configuration left upper side Pb2 Pb2 Pr2 dF2 DEF button timed 3sec...

Страница 9: ...50T150 C resolution 0 1 C or 1 C selectable Accuracy 0 7 C 1 digit and relative to the full scale Inputs 4 NTC PTC or PT1000 configurable 1 voltage free contacts I O port HOT KEY MAX voltage allowed is 5 VDC DO NOT CONNECT ANY EXTERNAL POWER SUPPLY Buzzer Optional Serial Outputs TTL standard available on 5 pin port HOT KEY connector Maximum cable length 2m Relay Outputs standard Ref Nominal UL IEC...

Отзывы: