1592020680 XRi60CH EN r2.0 2021.07.14
XRi60CH
7/9
rSr
PI regulator: range for output value calculation (RPM *
10)
40
120
Pr2 RPM*10
Str
PI regulator: delay before range drift
60
20
Pr2
sec
dPt
PI regulator: divisor for PI response time reduction
(acts on both par. tSt and iSt)
2
1
Pr2
SAt
Sampling time to calculate the average compressor
speed before any desfrost cycle
8
1
Pr2
min
CMn
Continuous control ON in normal mode
yes
no
Pr2
CME
Continuous control ON in energy saving
yes
no
Pr2
MnP
Compressor speed threshold to activate lubrication
(valid only for variable speed compressors,
0=disabled)
nu
nu
Pr2
%
tMi
Time range with compressor speed below MnP to
activate lubrication cycle
00:00 00:00 Pr2
hh:mm
tMA
Time range with compressor speed at 100% to
activate lubrication cycle
0
0
Pr2
min
CF
Temperature measurement unit: Celsius; Fahrenheit
°C
°C
Pr2
rES
Temperature resolution: decimal, integer
dE
dE
Pr2
Lod
Probe default displayed
P1
P1
Pr2
dLy
Temperature display delay (resolution 10 sec)
00:00 00:00 Pr2
min
dtr
Probe visualization percentage=F(P1;P2) (ex: dtr=1
means VALUE=0.01*P1+0.99*P2)
99
99
Pr2
EdF
Defrost mode
in
in
Pr2
tdF
Defrost type: electric heating, hot gas
in
in
Pr2
dFP
Probe selection for defrost control
P2
P2
Pr1
dtE
End defrost temperature
8.0
12.0
Pr2
°C
idF
Interval between two successive defrost cycles
12
12
Pr1
hh
MdF
Maximum length of defrost cycle
30
30
Pr1
min
dSd
Start defrost delay
0
0
Pr2
sec
StC
Compressor off-cycle before starting any defrost
0
0
Pr2
sec
dFd
Displaying during defrost
dEF
dEF
Pr2
dAd
Temperature display delay after any defrost cycle
0
0
Pr2
min
Fdt
Draining time
5
5
Pr2
min
Hon
Drain heater enabled after draining time (par. Fdt)
00:00 00:00 Pr2
hh:mm
dPo
Defrost cycle enebled at stat-up
no
no
Pr2
Pd2
Defrost output deactivation delay
0
0
Pr2
sec
dAF
Pre-defrost time
0
0
Pr2
min
FAP
Probe selection for evaporator fan
nP
nP
Pr2
FSt
Evaporator fan stop temperature
0.0
10.0
Pr2
°C
HyF
Evaporator fan regulator differential
1.0
2.0
Pr2
°C
FnC
Evaporator fan operating mode
C_n
C_n
Pr2
Fnd
Evaporator fan delay after defrost cycle
5
0
Pr2
min
FCt
Differential temperature for cyclic activation of
evaporator fans (0=disabled)
1
0
Pr2
°C
Ft
Evaporator fan controlled during defrost
no
no
Pr2
Fon
Evaporator fan ON time in normal mode (with
compressor OFF)
0
0
Pr2
min
FoF
Evaporator fan OFF time in normal mode (with
compressor OFF)
0
0
Pr2
min
FAC
Probe selection for condenser fan
nP
nP
Pr2
St2
Set Point 2 Regulation (for condenser fan)
0.0
15.0
Pr2
°C
Hy2
Set Point 2 differential (for condenser fan)
1.0
10.0
Pr2
°C
FCC
Condenser fan operating mode
O_n
C_n
Pr2
Fd4
Condenser fan deactivation delay
0
0
Pr2
sec
ALP
Probe selection for temperature alarms
P1
P1
Pr1
ALC
Temperature alarms configuration: relative, absolute
Ab
Ab
Pr1
ALU
High temperature alarm
150.0 150.0 Pr1
°C
ALL
Low temperature alarm
-100.0
-
100.0 Pr1
°C
AFH
Temperature alarm differential
2.0
2.0
Pr1
°C
ALd
Temperature alarm delay
0
0
Pr1
min
dAo
Temperature alarm delay at start-up
00:00 00:00 Pr1
hh:mm
AP2
Probe selection for 2nd temperature alarm
nP
nP
Pr2
AL2
2nd low temperature alarm
-20.0
0.0
Pr2
°C
AU2
2nd high temperature alarm
20.0
0.0
Pr2
°C
AH2
2nd temperature alarm differential
2.0
0.1
Pr2
°C
Ad2
2nd temperature alarm delay
0
0
Pr2
min
dA2
2nd temperature alarm delay at start-up
00:00 00:00 Pr2
hh:mm
bLL
Compressor OFF due to 2nd low temperature alarm
no
no
Pr2
AC2
Compressor OFF due to 2nd high temperature alarm
no
no
Pr2
SAF
Differential for anti-freezing control
0.0
0.0
Pr2
°C
tbA
Alarm relay deactivation
yes
yes
Pr2
oA1
Relay output oA1 configuration
dEF
dEF
Pr2
oA2
Relay output oA2 configuration
LiG
LiG
Pr2
oA3
Relay output oA3 configuration
Fan
Fan
Pr2
AOP
Alarm relay polarity
CL
CL
Pr2
1Ao
Analogue output 1 configuration
FrE
FrE
Pr2
ibt
Base times for digital inputs
SEC
SEC
Pr1
i1P
Digital input 1 polarity
CL
CL
Pr1
i1F
Digital input 1 configuration
nu
EAL
Pr1
d1d
Digital inputs 1 alarm delay (base time depends on
par. ibt)
0
0
Pr1
sec
nPS
Number of external pressure switch alarms before
stopping the regulation
15
0
Pr2
OdC
Compressor and fan status after door opening
F-C
no
Pr2
rrd
Regulation restart after door alarm
no
no
Pr2
HES
Temperature differential in energy saving
0.0
0.0
Pr1
°C
LdE
ErA controls the lights in energy saving (lights OFF
when energy saving goes active)
yes
no
Pr1
Hur
Hours
Pr1
Min
Minutes
Pr1
dAY
Day of the week
Pr1
dyM
Day of the month
Pr1
Mon
Month
Pr1
yAr
Year
Pr1
Hd1
First day of weekend
Sat
Sat
Pr2
Hd2
2nd day of weekend
Sun
Sun
Pr2
iLE
Energy saving cycle starting time on working days
00:00 00:00 Pr2
hh:mm