XRB60CHC EN r1.1 2018.11.01.docx 

                           XRB60CHC 

3/7 

 

8.1.5

 

Alarm relay 

With 

oAx=ALr 

the AUX relay operates as alarm relay. It is activated every time an alarm happens. Its 

status depends on the 

tbA 

parameter: if 

tbA=Y

, the relay is silenced by pressing any key.  

If 

tbA=n

, the alarm relay stay on until the alarm condition recovers. 

8.1.6

 

Activation during energy saving cycles 

With 

oAx=HES, 

the AUX relay is energised when the energy saving cycle is activated. 

9

 

FRONT PANEL COMMANDS 

 

 

 

Press to display target set point and the real set point. When in programming mode 

it selects a parameter or confirms an operation 

 

(

ECO

) To switch on and off the Energy Saving mode or the light output. Other 

functions related to par. 

LGC 

and

 LG2

 

 

(

UP

) In programming mode it browses the parameter codes or increases the 

displayed value. Other functions related to par. 

UPC 

and

 UP2

 

 

(

DOWN

) In programming mode it browses the parameter codes or decreases the 

displayed value. Other functions related to the par. 

dnC 

and

 dn2 

 

(

ONOFF

) Keep it pressed for 3 sec to switch on and off the device

 

 

KEYS COMBINATION 

 

+

 

 

To lock or unlock the keyboard

 

 

+

 

 

To enter in programming mode 

 

+

 

 

To return to room temperature display

 

 

ICON 

MODE 

MEANING 

 

On 

Compressor enabled 

Flashing 

Anti-short cycle delay enabled (

AC

 parameter) 

 

On 

Light output enabled 

 

On 

Ventilator output enabled 

Flashing 

Ventilator delay after defrost 

,

 

 

On 

Measurement unit  

Flashing 

Programming mode 

 

On 

Energy saving mode active 

 

On 

An alarm condition is present 

Flashing 

Start-up operations are pending 

 

On 

Auxiliary output is activated 

 

NOTE: 

start-up operations lasts about 30 sec after powering on the device. At the end of this phase, 

the alarm icon will switch off if no alarm is active. 

9.1

 

SET POINT MENU 

The 

SET 

key gives access to a quick menu where it is possible to see: 

-

 

the set point value 

-

 

the real set point value (

rSE

Push and release the 

SET

 key five times or wait for 60 sec to return to normal visualisation. 

9.2

 

CHANGE THE SETPOINT 

1.

 

Push the 

SET

 key for more than 2 sec to change the Set point value; 

2.

 

The value of the set point will be displayed and the “°C” LED starts blinking;

 

3.

 

To change the Set value push the 

UP

 or 

DOWN 

button. 

4.

 

To memorise the new set point value push the 

SET

 key again or wait for 60 sec. 

9.3

 

START A MANUAL DEFROST 

Push the 

DEFROST

 button for more than 2 sec to start a manual defrost. 

9.4

 

CHANGE A PARAMETER VALUE 

To change the parameter values operate as follows:  

1.

 

Enter  the  Programming  mode  by  pressing  the 

SET+DOWN

  buttons  for  3  sec 

(“

°C

 

LED  starts 

blinking). 

2.

 

Select the required parameter. Press the 

SET

 button to display its value 

3.

 

Use 

UP

 or 

DOWN 

buttons to change its value. 

4.

 

Press 

SET

 to store the new value and move to the following parameter. 

 

To exit:

 Press 

SET+UP 

buttons or waits for 15 sec without pressing any key. 

 

NOTE:

 the set value is stored even when the procedure is exited by waiting the time-out to expire. 

9.5

 

ENTERING THE HIDDEN MENU 

The hidden menu includes all the parameters of the instrument. 

ENTER THE HIDDEN MENU 

1.

 

Enter the Programming mode by pressing 

SET+DOWN

 buttons for 3 sec 

(“

°C

 

or “

°F

 LED starts 

blinking). 

2.

 

Released the keys and then push again 

SET+DOWN

 buttons for more than 7 sec. The 

L2

  label 

will be displayed immediately followed from the 

HY

 parameter.  

NOW YOU ARE IN THE HIDDEN MENU.

 

3.

 

Select the required parameter. 

4.

 

Press the 

SET

 key to display its value 

5.

 

Use 

UP

 or 

DOWN

 to change its value. 

6.

 

Press 

SET

 to store the new value and move to the following parameter. 

 

To exit

: Press 

SET+

UP

 or wait for 15 sec without pressing any key. 

 

NOTE1: 

if there are no parameters in L1, after 3 sec 

the “

nP

” 

label will  be displayed. Keep the keys 

pushed till the 

L2

 message will be displayed. 

  

NOTE2:

 the previous set value will be stored even if the programming mode is exited by waiting for the 

time-out to expire. 

MOVE PARAMETERS FROM THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA. 

Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user 

level) by pressing 

SET+DOWN

. If a parameter is visible also in the First Level, in the HIDDEN MENU 

the decimal point will be lit. 

9.6

 

LOCK THE KEYBOARD 

1.

 

Keep both 

UP 

and 

DOWN 

buttons pressed for more than 3 sec. 

2.

 

The “

oFF

” label

 will be displayed and the keyboard will be locked. If any button is pressed more 

than 3 sec, 

the “

oFF

” message will be displayed.

 

9.7

 

UNLOCK THE KEYBOARD 

Keep both 

UP 

and 

DOWN 

buttons pressed together for more than 3 sec till the 

“on”

 

message will be 

displayed. 

9.8

 

THE ON/OFF FUNCTION 

 

 

If 

onF = oFF

, the instrument will be switched off by pushing the 

ON/OFF

 button. The 

OFF

 

message  will  appear  on  the  display.  In  this  configuration  the  regulation  is 

disabled. To switch the instrument on, push again the 

ON/OFF

 button. 

 
WARNING: any load connected to the normally closed contacts of the relays is always supplied 

from the main voltage, even if the instrument is in standby mode.

 

10

 

PARAMETERS 

REGULATION 

Set 

Regulation Set Point:

 LS to US 

LS 

Minimum SET POINT:

 (-55.0°C to SET;  -67°F  to SET) sets the minimum value for the set 

point. 

US 

Maximum SET POINT:

 (SET to 150.0°C; SET to 302°F) set the maximum value for set point. 

HY 

Differential in normal mode (energy saving  mode not active):

  (0.1 to  25.0°C; 1  to  45°F) 

differential for set point. Compressor Cut-IN is  

[SET-POINT + HY]

. Compressor Cut-OUT is when the temperature reaches the set point. 

HYE 

Differential when energy saving mode is active:

 (0.1 to 25.0°C; 1 to 45°F) differential for set 

point. Compressor Cut-IN is 

[SET-POINT + HES +  HYE]

. Compressor Cut-OUT is when the 

temperature reaches the 

[SET-POINT + HES]

odS 

Outputs  delay  activation  after  power  on:

 (0  to  255  min)  this  function  is  enabled  after  the 

power-on of the instrument and inhibits  any output  activation for the period of time set in the 
parameter. 

AC 

Anti-short cycle delay:

 (0 to  50 min) minimum interval  between a compressor stop and the 

following restart. 

Rtr 

P1-P2 percentage for regulation: 

100=P1 only; 0=P2 only

 

CCt 

Maximum duration for pull down:

 (0.0 to 23h50min, res. 10min) after elapsing this interval of 

time the super cooling function is immediately stopped 

CCS 

Differential for pull down:

 (-12.0 to 12.0°C; -21 to 21°F) during any super cooling phase the 

regulation  SETPOINT  is  moved  to 

SET+CCS 

(in  normal  mode)  or  to 

SET+HES+CCS

  (in 

energy saving mode)

 

oHt 

Overheating  before  activating  the  pull  down  function  (when  in  normal  mode): 

(1.0  to 

12.0°C; 1 to 21°F) this is the upper threshold limit used to activate the super cooling function. 

oHE 

Overheating before activating the pull down function (when in energy saving mode): 

(1.0 

to  12.0°C;  1  to  21°F)  this  is  the  upper  threshold  limit  used  to  activate  the  super  cooling 
function. 

Con 

Compressor ON time with faulty probe:

 (0 to 255 min) time during which the compressor is 

active in case of faulty thermostat probe. With 

CY=0

 compressor is always OFF. 

CoF 

Compressor OFF time with faulty probe:

 (0 to 255 min) time during which the compressor is 

OFF in case of faulty thermostat probe. With 

Cn=0

 compressor is always active. 

PROBE SETUP 

ot 

Thermostat probe calibration:

  (-12.0 to 12.0°C;  -21 to 21°F)  allows to  adjust any  possible 

offset of the first probe. 

P2P 

Evaporator probe presence:

 

n

 = not present; 

Y

 = the defrost stops by temperature. 

Содержание Dixell XRB60CHC

Страница 1: ...e standard SET POINT SET is used to maintain the temperature at a certain value when the energy saving status ES is not active On the other side when the ES status is active a different SET POINT SET_ES higher than the standard one will be used The parameter HES will have to be set to change the regulation temperature according to the following formula SET_ES SET HES There are also two different d...

Страница 2: ... OR PROBE CONTROLLED MODE Two defrost modes are available timed or controlled by the evaporator s probe A couple of parameters is used to control the interval between defrost cycles idF and its maximum length MdF During the defrost cycle is possible to select some different display indications by using the dFd parameter These modes are available with any kind of defrost type tdF EL electric heater...

Страница 3: ...Press SET UP or wait for 15 sec without pressing any key NOTE1 if there are no parameters in L1 after 3 sec the nP label will be displayed Keep the keys pushed till the L2 message will be displayed NOTE2 the previous set value will be stored even if the programming mode is exited by waiting for the time out to expire MOVE PARAMETERS FROM THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA Each parame...

Страница 4: ...P4 nP no probe the auxiliary relay is switched only by the digital input P1 Probe 1 Thermostat probe P2 Probe 2 evaporator probe P3 do not use it P4 Probe 4 Sdd Auxiliary relay switched off during defrost n Y n the auxiliary relay operates during defrost Y the auxiliary relay is switched off during defrost btA Base Time for timed activation of auxiliary output SEC Min SEC base time is in second At...

Страница 5: ... the right of the appliance card present on the Permissions webpage OTHER Adr Serial address for Modbus communication 1 to 247 bAU Baudrate 9 6 19 2 38 4 57 6 select the correct baudrate for serial communication wired LGC Light button configuration nu not used ES change working mode from normal to energy saving mode and vice versa LiG light output control AUS auxiliary output control dEF defrost c...

Страница 6: ...ections Screw terminal block 2 5 mm2 wiring Power supply according to the model 230Vac 10 50 60Hz 110Vac 10 50 60Hz Power absorption 3 5VA max Display 3 digits red LED 14 2 mm high Inputs up to 4 NTC probes Digital input free voltage contact Relay outputs Compressor SPST 16 5 A or 20 8 A 250VAC Light SPDT 5 2 A 250VAC Fans SPST 8 3 A 250VAC Data storing 8 Kbytes EEPROM Kind of action 1B Pollution ...

Страница 7: ...is compliant with the following standards FCC 15 247 The XRB60CHC is compliant to Part 15 of the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation This device has been designed and complies with the safety requirements for p...

Отзывы: