background image

 

1592020070 XR70CX GB m&M r1.3 27.03.2015 

XR70CX 

1/5 

Digital controller with defrost and fan management

 

XR70CX  

1.

 

GENERAL WARNING ________________________________________________________ 1

 

2.

 

GENERAL DESCRIPTION  ____________________________________________________ 1

 

3.

 

CONTROLLING LOADS ______________________________________________________ 1

 

4.

 

FRONT PANEL COMMANDS __________________________________________________ 1

 

5.

 

MAX & MIN TEMPERATURE MEMORIZATION ____________________________________ 1

 

6.

 

MAIN FUNCTIONS  __________________________________________________________ 2

 

7.

 

PARAMETERS  _____________________________________________________________ 2

 

8.

 

DIGITAL INPUTS ____________________________________________________________ 3

 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS ________________________________ 3

 

10.

 

X-REP OUTPUT – OPTIONAL _________________________________________________ 3

 

11.

 

INSTALLATION AND MOUNTING  ______________________________________________ 4

 

12.

 

ELECTRICAL CONNECTIONS _________________________________________________ 4

 

13.

 

USE THE HOT KEY __________________________________________________________ 4

 

14.

 

ALARM SIGNALS  ___________________________________________________________ 4

 

15.

 

TECHNICAL DATA  __________________________________________________________ 4

 

16.

 

CONNECTIONS _____________________________________________________________ 4

 

17.

 

DEFAULT SETTING VALUES __________________________________________________ 4

 

 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and quick 
reference. 

 

The  instrument  shall  not  be  used  for  purposes  different  from  those  described  hereunder.  It 
cannot be used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell  Srl  reserves  the  right  to  change  the  composition  of  its  products,  even  without  notice, 
ensuring the same and unchanged functionality. 

1.2

 

SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding 
sudden  temperature  changes  with  high  atmospheric  humidity  to  prevent    formation  of 
condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In  case  of  failure  or  faulty  operation  send  the  instrument  back  to  the  distributor  or  to  “Dixell 
S.r.l.” (see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that  the wires for probes, loads and the power supply are separated and far enough 
from each other, without crossing or intertwining. 

 

In  case  of  applications  in  industrial  environments,  the  use  of  mains  filters  (our  mod.  FT1) in 
parallel with inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

Model 

XR70CX

,  format  32x74mm,  is  microprocessor  based  controller,  suitable  for  applications  on 

medium  or  low  temperature  ventilated  refrigerating  units.  It  has  four  relay  outputs  to  control 
compressor, fan, and defrost, which can be either electrical or reverse cycle (hot gas). The last one 
can be used as light, for alarm signalling or as auxiliary output. It is also provided with up to 4 NTC or 
PTC  probe  inputs,  the  first  one  for  temperature  control,  the  second  one,  to  be  located  onto  the 
evaporator, to control the defrost termination temperature and to managed the fan. The digital input 
can operate as third temperature probe.  The fourth one, to connect to the HOT KEY terminals, is 
used to signal the condenser temperature alarm or to display another temperature. 
The 

HOT-KEY

 output allows to connect the unit, by means of the external module XJ485-CX, to a 

network line 

ModBUS-RTU

 compatible such as the Dixell monitoring units of X-WEB family. It allows 

to program the controller by means the HOT-KEY programming keyboard.  
The  instrument  is  fully  configurable  through  special  parameters  that  can  be  easily  programmed 
through the keyboard. 

3.

 

CONTROLLING LOADS 

3.1

 

COMPRESSOR 

The  regulation  is  performed  according 
to  the  temperature  measured  by  the 
thermostat  probe  with  a  positive 
differential  from  the  set  point:  if  the 
temperature  increases  and reaches set 
point plus differential the compressor is 
started  and  then  turned  off  when  the 
temperature reaches the set point value 
again. 

Time

Temper.

Compr.

SET

ON

 

In  case  of  fault  in  the  thermostat  probe  the  start  and  stop  of  the  compressor  are  timed  through 
parameters 

Con

 and 

CoF

3.2

 

DEFROST  

Two  defrost  modes  are  available  through  the 

tdF

  parameter:  defrost  through  electrical  heater 

(

tdF=EL

) and hot gas defrost (

tdF=in

).  

Other parameters are used to control the interval between defrost cycles (

idF

), its maximum length 

(

MdF

) and two defrost modes: timed or controlled by the evaporator’s probe (

P2P

).  

At the end of defrost dripping time is started, its length is set in the 

Fdt

 parameter. With 

Fdt=0

 the 

dripping time is disabled. 

3.3

 

CONTROL OF EVAPORATOR FANS 

The fan control mode is selected by means of the 

FnC

 parameter: 

FnC=C_n

, fans will switch ON and OFF with the compressor and

 not run

 during defrost. 

FnC=o_n

, fans will run even if the compressor is off, and not run during defrost. 

 
After defrost, there is a timed fan delay allowing for drip time, set by means of the 

Fnd

 parameter. 

FnC=C_Y

,

 

fans will switch ON and OFF with the compressor and 

run

 during defrost. 

FnC=o_Y

, fans will run continuously also during defrost. 

 

An additional parameter 

FSt

 provides the setting of temperature, detected by the evaporator probe, 

above  which  the  fans  are  always  OFF.  This  is  used  to  make  sure  circulation  of  air  only  if  his 
temperature is lower than set in 

FSt

3.3.1  Forced activation of fans 

This function managed by the 

FCt

 parameter is designed to avoid short cycles of fans, that could 

happen  when  the  controller  is  switched  on  or  after  a  defrost,  when  the  room  air  warms  the 
evaporator. 

How it works: 

if the temperature difference between evaporator probe and room probe 

is higher than the 

FCt

 parameter value, fans will be switched on. With 

FCt=0

 the function is disabled. 

3.3.2  Cyclical activation of the fans with compressor off. 

When 

FnC=C-n

 or 

C-Y

 (fans working in parallel with the compressor), by means of the 

Fon

 and 

FoF

 

parameters the fans can carry out on and off cycles even if the compressor is switched off. When the 
compressor is stopped the fans go on working for the 

Fon

 time. With 

Fon=0

 the fans remain always 

off, also when the compressor is off.  

4.

 

FRONT PANEL COMMANDS 

 

 

 

 

 

To display target set point; in programming mode it selects a parameter or confirm 
an operation. 

 

(

DEF

) To start a manual defrost. 

 

(

UP

) To see the max stored temperature; in programming mode it browses the 

parameter codes or increases the displayed value. 

 

(

DOWN

) To see the min stored temperature; in programming mode it browses the 

parameter codes or decreases the displayed value. 

 

To switch the instrument on and off (when 

onF=oFF

).  

 

To switch on and off the light (when 

oA3=LiG

). 

 
KEY COMBINATIONS: 

  

 

 

To lock & unlock the keyboard

.

 

 

+

  

 

To enter in programming mode. 

  

+

  

 

To return to the room temperature display. 

4.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED  MODE  FUNCTION 

 

ON 

Compressor enabled 

Flashing  Anti-short cycle delay enabled 

 

ON 

Defrost enabled 

Flashing  Drip time in progress 

 

ON 

Fans enabled 

Flashing  Fans delay after defrost in progress. 

 

ON 

An alarm is occurring 

 

ON 

Continuous cycle is running 

 

ON 

Energy saving enabled 

 

ON 

Light on 

  ON 

Auxiliary relay on 

°C/°F 

ON 

Measurement unit 

Flashing  Programming phase 

5.

 

MAX & MIN TEMPERATURE MEMORIZATION 

5.1

 

HOW TO: SEE THE MIN TEMPERATURE 

1. 

 

Press and release the 

DOWN

 key. 

2. 

 

The “

Lo

” message will be displayed followed by the minimum temperature recorded. 

3. 

 

By pressing the 

DOWN

 key again or by waiting 5 sec the normal display will be restored. 

Содержание Dixell XR70CX

Страница 1: ... the Dixell monitoring units of X WEB family It allows to program the controller by means the HOT KEY programming keyboard The instrument is fully configurable through special parameters that can be easily programmed through the keyboard 3 CONTROLLING LOADS 3 1 COMPRESSOR The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the...

Страница 2: ... sets the minimum value for the set point US Maximum set point SET to 150 C SET to 302 F set the maximum value for set point ot Thermostat probe calibration 12 0 to 12 0 C 21 to 21 F allows to adjust possible offset of the thermostat probe P2P Evaporator probe presence n Y n not present the defrost stops by time Y present the defrost stops by temperature oE Evaporator probe calibration 12 0 to 12 ...

Страница 3: ...by opening the contact CL the digital input is activated by closing the contact i1F Second digital input configuration EAL bAL PAL dor dEF ES AUS Htr FAn HdF onF EAL external alarm EA message is displayed bAL serious alarm CA message is displayed PAL pressure switch alarm CA message is displayed dor door switch function dEF activation of a defrost cycle ES energy saving AUS auxiliary relay activat...

Страница 4: ...alarm Output unchanged CA Serious external alarm i2F bAL All outputs OFF CA Pressure switch alarm i2F PAL All outputs OFF rtc Real time clock alarm Alarm output ON Other outputs unchanged Defrosts according to par idF Set real time clock has to be set rtF Real time clock board failure Alarm output ON Other outputs unchanged Defrosts according to par idF Contact the service 14 1 ALARM RECOVERY Prob...

Страница 5: ...C 0 to 90 F AbS 100 C to ALU 148 F to ALU 50 0 Pr1 AFH Differential for temperat alarm recovery 0 1 to 25 5 C 1 to 45 F 1 0 Pr2 ALd Temperature alarm delay 0 to 255 min 15 Pr2 dAo Delay of temperature alarm at start up 0 0 to 24h00min res 10 min 1 3 Pr2 AP2 Probe for temperat alarm of condenser nP P1 P2 P3 P4 P4 Pr2 AL2 Condenser for low temperat alarm 100 to 150 C 148 to 302 F 40 Pr2 AU2 Condense...