HOW TO: SEE THE MAX TEMPERATURE 

1. 

 

Press and release the 

UP

 key. 

2. 

 

The “

Hi

” message will be displayed followed by the maximum temperature recorded. 

3. 

 

By pressing the 

UP

 key again or by waiting 5 sec the normal display will be restored. 

5.3

 

HOW TO: RESET THE MAX AND MIN TEMPERATURE RECORDED 

1.

 

Keep the 

SET

 key pressed more than 3 sec, while the max or min temperature is displayed. 

(“

rSt

” message will be displayed) 

2.

 

To confirm the operation the “

rSt

” message will start blinking and the normal temperature will 

be displayed. 

6.

 

MAIN FUNCTIONS 

6.1

 

HOW TO: SEE THE SET POINT 

 

1.

 

Push  and  immediately  release  the 

SET 

key:  the  display  will  show  the 

Set point value. 

2.

 

Push and immediately release the 

SET 

key or wait for 5 sec to display 

the probe value again. 

6.2

 

HOW TO CHANGE THE SET POINT 

1.

 

Push the 

SET 

key more than 2 sec to change the Set point value. 

2.

 

The value of the set point will be displayed and the “

°C

” or “

°F

” LED will start blinking. 

3.

 

To change the Set value push the 

UP

 

or 

DOWN

 arrows within 10 sec. 

4.

 

To save the new set point value, push the 

SET

 key again or wait for 10 sec. 

6.3

 

HOW TO START A MANUAL DEFROST 

 

Push the 

DEF 

key for more than 2 sec and a manual defrost will start. 

6.4

 

HOW TO: CHANGE A PARAMETER VALUE 

To change a parameter value, operate as follows:  
1.

 

Enter the Programming mode by pressing the 

SET+DOWN 

buttons for 3s (the 

°C 

or

 °F

 LED will 

start blinking). 

2.

 

Select the required parameter. Press the 

SET

 button to display its actual   value. 

3.

 

Use 

UP

 or 

DOWN 

buttons to change its value. 

4.

 

Press 

SET 

button to store the new value and move to the following parameter. 

 

To exit

: Press 

SET + UP 

buttons or waiting for 15s without pressing any key. 

 
NOTE

: the set value is stored even when the procedure is exited by waiting for the time-out to expire. 

6.5

 

THE HIDDEN MENU 

The hidden menu includes all the parameters of the instrument. 

6.5.1  HOW TO: ENTER THE HIDDEN MENU 

1.

 

Enter the Programming mode by pressing the 

SET+DOWN 

buttons for 3 sec (the 

°C 

or

 °F

 LED 

will start blinking). 

2.

 

Released the buttons and then push again the 

SET+DOWN 

buttons for more than 7s. The Pr2 

label will be displayed immediately followed from the 

HY

 parameter.  

Now it is possible to browse the hidden menu.

 

3.

 

Select the required parameter. 

4.

 

Press the 

SET

 button to display its value. 

5.

 

Use 

UP 

or 

DOWN 

to change its value. 

6.

 

Press 

SET

 to store the new value and move to the following parameter. 

 

To exit

: Press 

SET+DOWN 

or wait 15 sec without pressing a key. 

 
NOTE1: 

if no parameter is present in Pr1 menu, after 3 sec the “

noP

” message will be displayed. 

Keep the buttons pushed till the Pr2 message will be displayed.  
 

NOTE2:

  the  set  value  is  stored  even  when  the  procedure  is  exited  by  waiting  for  the  time-out  to 

expire 
 

6.5.2  HOW  TO:  MOVE  A  PARAMETER  FROM  THE  HIDDEN  MENU  TO  THE 
FIRST LEVEL AND VICEVERSA. 

Each parameter present in the hidden menu (Pr2) can be moved into the user level (Pr1) by pressing 

SET+DOWN 

buttons. If a parameter is part of the user level, when showed in the hidden menu the 

decimal point will be lit. 

6.6

 

HOW TO: LOCK THE KEYBOARD 

1. 

 

Keep both 

UP

 and 

DOWN

 buttons pressed for more than 3 sec. 

2. 

 

The “

PoF

” message will be displayed and the keyboard will be locked. At this point it will be 

possible only to see the set point or the MAX o Min temperature stored 

3. 

 

If a button is pressed more than 3 sec the “

PoF

” message will be displayed 

6.7

 

HOW TO: UNLOCK THE KEYBOARD 

Keep pressed together for more than 3 sec the 

UP

 

and 

DOWN

 keys till the 

“Pon” 

message will be 

displayed. 

6.8

 

THE CONTINUOUS CYCLE 

When defrost is not in progress, it can be activated by holding the 

UP

 key pressed for about 3 sec. 

The compressor operates to maintain the 

CCS

 set point for the time set through the 

CCt

 parameter. 

The cycle can be terminated before the end of the set time using the same activation key 

UP

 for 3 

sec. 

6.9

 

THE ON/OFF FUNCTION 

 

With “

onF = oFF

”, pushing the 

ON/OFF

 key, the instrument is switched off. The 

“OFF” 

message is displayed. In this configuration, the regulation is disabled.  

 

To switch the instrument on, push again the ON/OFF key. 

 

WARNING:  Loads  connected  to  the  normally  closed  contacts  of  the  relays  are  always 

supplied and under voltage, even if the instrument is in stand by mode.  

7.

 

PARAMETERS 

REGULATION 

HY 

Differential:

  (0.1  to  25.5°C;  1  to  45°F)  intervention  differential  for  set  point. 

Compressor Cut IN is Set Point + differential (

HY

). Compressor Cut OUT is when the 

temperature reaches the set point. 

LS   

Minimum set point:

 (-100°C to SET; -148°F to SET) sets the minimum value for the 

set point. 

US 

Maximum set point:

 (SET to 150°C; SET to 302°F) set the maximum value for set 

point. 

ot   

Thermostat  probe  calibration:

  (-12.0  to  12.0°C;  -21  to  21°F)  allows  to  adjust 

possible offset of the thermostat probe. 

P2P 

Evaporator probe presence:

 (n; Y) 

n

 = not present, the defrost stops by time;  

Y

 = present, the defrost stops by temperature. 

oE 

Evaporator probe calibration:

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible 

offset of the evaporator probe. 

P3P 

Third probe presence (P3):

 (n; Y) 

n

 = not  present, the  terminals 18-20 operate as 

digital input; 

Y

 = present, the terminals 18-20 operate as third probe. 

o3 

Third probe calibration (P3):

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible 

offset of the third probe. 

P4P 

Fourth probe presence: 

(n; Y) n = Not present; Y = present. 

o4 

Fourth  probe  calibration:

  (-12.0  to  12.0°C;  -21  to  21°F)  allows  to  adjust  possible 

offset of the fourth probe. 

odS 

Outputs  activation  delay  at  start  up:

 (0  to  255min)  this  function  is  enabled  at  the 

initial start up of the instrument and inhibits any output activation for the period of time 
set in the parameter.  

AC   

Anti-short cycle delay:

 (0 to 50min) minimum interval between the compressor stop 

and the following restart. 

rtr 

Percentage of the second and first probe for regulation:

 (0 to 100; 100=P1, 0=P2) 

it allows to set the regulation according to the percentage of the first and second probe, 
as for the following formula (

rtr

(P1-P2)/100 + P2). 

CCt 

Compressor  ON  time  during  continuous  cycle:

  (0.0  to  24h00min,  res.  10min) 

allows  to  set  the  length  of  the  continuous  cycle.  Compressor  stays  on  without 
interruption during 

CCt

 time. This is useful, for instance, when the room is filled with 

new products. 

CCS 

Set  point  for  continuous  cycle:

  (-55  to  150°C;  -67  to  302°F)  it  sets  the  set  point 

used during the continuous cycle. 

Con 

Compressor  ON  time  with  faulty  probe:

  (0  to  255min)  time  during  which  the 

compressor  is  active  in  case  of  faulty  thermostat  probe.  With 

Con=0

  compressor  is 

always OFF. 

CoF 

Compressor  OFF  time  with  faulty  probe:

  (0  to  255min)  time  during  which  the 

compressor  is  OFF  in  case  of  faulty  thermostat  probe.  With 

CoF=0

  compressor  is 

always active. 

DISPLAY 

CF 

Temperature measurement unit:

 (°C; °F) 

°C

 = Celsius; 

°F 

= Fahrenheit.  

WARNING:

 When the measurement unit is changed the SET point and the values of 

the  parameters 

HY

LS

US

ot

ALU

  and 

ALL

  have  to  be  checked  and  modified  (if 

necessary). 

rES 

Resolution (for °C):

 (in=1°C; dE=0.1°C) allows decimal point display. 

Lod 

Instrument display:

 (P1; P2, P3, P4, SET, dtr) it selects which probe is displayed by 

the instrument. 

P1

 = Thermostat probe; 

P2

 = Evaporator probe; 

P3

 = Third probe (only 

for  model  with  this  option  enabled); 

P4

  =  Fourth  probe, 

SET

  =  set  point; 

dtr

  = 

percentage of visualization. 

rEd 

X-REP  display  (optional):

  (P1;  P2,  P3,  P4,  SET,  dtr)  it  selects  which  probe  is 

displayed by X- REP. 

P1

 = Thermostat probe; 

P2

 = Evaporator probe; 

P3

 = Third probe 

(only for model with this option enabled); 

P4

 = Fourth probe, 

SET

 = set point;  

dtr

 = percentage of visualization. 

dL

Display delay:

 (0 to 20min00s; res. 10s) when the temperature increases, the display 

is updated of 1°C or 1°F after this time. 

dtr 

Percentage of the second and first probe for visualization when Lod=dtr:

 (0 to 99; 

100=P1, 0=P2) if 

Lod=dtr

 it allows to set the visualization according to the percentage 

of the first and second probe, as for the following formula (

dtr

(P1-P2)/100 + P2). 

DEFROST 

tdF 

Defrost type:

 (EL; in) 

EL

 = electrical heater; 

in

 = hot gas. 

dFP 

Probe selection for defrost termination:

 (nP; P1; P2; P3; P4) 

nP

 = no probe;  

P1

 =thermostat probe; 

P2

 = evaporator probe; 

P3

 =configurable probe; 

P4

 = Probe on 

Hot Key plug. 

dtE 

Defrost  termination  temperature:

  (-55  to  50°C;  -67  to  122°F)  (enabled  only  when 

EdF=Pb

) sets the temperature measured by the evaporator probe, which causes the 

end of defrost. 

idF 

Interval  between  defrost  cycles:

  (0  to  120hours)  determines  the  interval  of  time 

between two defrost cycles. 

Md

F   

(Maximum)  length  for  defrost:

  (0  to  255min)  when 

P2P=n

,  (not  evaporator  probe: 

timed  defrost)  it  sets  the  defrost  duration.  When 

P2P=Y

  (defrost  end  based  on 

temperature) it sets the maximum length for defrost. 

dSd 

Start defrost delay:

 (0 to 99min) this is useful when different defrost start times are 

necessary to avoid overloading the plant.  

dFd    Temperature displayed during defrost:

 (rt; it; SEt; dEF) 

rt

 = real temperature;  

it

 = temperature at defrost start; 

SEt

 = set point; 

dEF

 = “

dEF

” label. 

dAd 

MAX display delay after defrost:

 (0 to 255min) sets the maximum time between the 

end of defrost and the restarting of the real room temperature display. 

Fdt 

Drip  time:

  (0  to  120min)  time  interval  between  reaching  defrost  termination 

temperature  and  the  restoring  of  the  control’s  normal  operation.  This  time  allows  the 
evaporator to eliminate water drops that might have formed due to defrost. 

Содержание Dixell XR70CX

Страница 1: ... the Dixell monitoring units of X WEB family It allows to program the controller by means the HOT KEY programming keyboard The instrument is fully configurable through special parameters that can be easily programmed through the keyboard 3 CONTROLLING LOADS 3 1 COMPRESSOR The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the...

Страница 2: ... sets the minimum value for the set point US Maximum set point SET to 150 C SET to 302 F set the maximum value for set point ot Thermostat probe calibration 12 0 to 12 0 C 21 to 21 F allows to adjust possible offset of the thermostat probe P2P Evaporator probe presence n Y n not present the defrost stops by time Y present the defrost stops by temperature oE Evaporator probe calibration 12 0 to 12 ...

Страница 3: ...by opening the contact CL the digital input is activated by closing the contact i1F Second digital input configuration EAL bAL PAL dor dEF ES AUS Htr FAn HdF onF EAL external alarm EA message is displayed bAL serious alarm CA message is displayed PAL pressure switch alarm CA message is displayed dor door switch function dEF activation of a defrost cycle ES energy saving AUS auxiliary relay activat...

Страница 4: ...alarm Output unchanged CA Serious external alarm i2F bAL All outputs OFF CA Pressure switch alarm i2F PAL All outputs OFF rtc Real time clock alarm Alarm output ON Other outputs unchanged Defrosts according to par idF Set real time clock has to be set rtF Real time clock board failure Alarm output ON Other outputs unchanged Defrosts according to par idF Contact the service 14 1 ALARM RECOVERY Prob...

Страница 5: ...C 0 to 90 F AbS 100 C to ALU 148 F to ALU 50 0 Pr1 AFH Differential for temperat alarm recovery 0 1 to 25 5 C 1 to 45 F 1 0 Pr2 ALd Temperature alarm delay 0 to 255 min 15 Pr2 dAo Delay of temperature alarm at start up 0 0 to 24h00min res 10 min 1 3 Pr2 AP2 Probe for temperat alarm of condenser nP P1 P2 P3 P4 P4 Pr2 AL2 Condenser for low temperat alarm 100 to 150 C 148 to 302 F 40 Pr2 AU2 Condense...

Отзывы: