1592020070 XR70CX GB m&M r1.3 27.03.2015
XR70CX
5/5
Label
Name
Range
Value Level
Con
Compressor ON time with faulty probe
0 to 255 min
15
Pr2
CoF
Compressor OFF time with faulty probe
0 to 255 min
30
Pr2
CF
Temperature measurement unit
°C; °F
°C
Pr2
rES
Resolution
dE; in
dE
Pr1
Lod
Probe displayed
P1; P2; P3; P4; SEt; dtr
P1
Pr2
rEd
2
X-REP display
P1; P2; P3; P4; SEt; dtr
P1
Pr2
dLY
Display temperature delay
0.0 to 20min00sec, res. 10 sec
0.0
Pr2
dtr
P1-P2 percentage for display
1 to 99
50
Pr2
tdF
Defrost type
EL; in
EL
Pr1
dFP
Probe selection for defrost termination
nP; P1; P2; P3; P4
P2
Pr2
dtE
Defrost termination temperature
[-55 to 50.0°C]
[-67 to 122°F]
8
Pr1
idF
Interval between defrost cycles
0 to 120 hours
6
Pr1
MdF
(Maximum) length for defrost
0 to 255 min
30
Pr1
dSd
Start defrost delay
0 to 255 min
0
Pr2
dFd
Displaying during defrost
rt; it; SEt; dEF
it
Pr2
dAd
MAX display delay after defrost
0 to 255 min
30
Pr2
Fdt
Draining time
0 to 255 min
0
Pr2
dPo
First defrost after start-up
n; Y
n
Pr2
dAF
Defrost delay after fast freezing
0.0 to 24h00min, res. 10 min
0.0
Pr2
FnC
Fan operating mode
C-n; o-n; C-Y; o-Y
o-n
Pr1
Fnd
Fan delay after defrost
0 to 255 min
10
Pr1
FCt
Differential of temperature for forced
activation of fans
[0 to 50°C]
[0 to 90°F]
10
Pr2
FSt
Fan stop temperature
[-55 to 50.0°C]
[-67 to 122°F]
2
Pr1
Fon
Fan on time with compressor off
0 to 15 min
0
Pr2
FoF
Fan off time with compressor off
0 to 15 min
0
Pr2
FAP
Probe selection for fan management
nP; P1; P2; P3; P4
P2
Pr2
ALC
Temperat. alarms configuration
rE; Ab
Ab
Pr2
ALU
MAXIMUM temperature alarm
Rel: [0.0 to 50.0°C] [0 to 90°F]
AbS: [ALL to 150°C] [ALL to 302°F]
110.0 Pr1
ALL
Minimum temperature alarm
Rel: [0.0 to 50.0°C] [0 to 90°F]
AbS: [-100°C to ALU] [-148°F to
ALU]
-50.0
Pr1
AFH
Differential for temperat. alarm recovery
[0.1 to 25.5°C]
[1 to 45°F]
1.0
Pr2
ALd
Temperature alarm delay
0 to 255 min
15
Pr2
dAo
Delay of temperature alarm at start up
0.0 to 24h00min, res. 10 min
1.3
Pr2
AP2
Probe for temperat. alarm of condenser
nP; P1; P2; P3; P4
P4
Pr2
AL2
Condenser for low temperat. alarm
[-100 to 150°C]
[-148 to 302°F]
-40
Pr2
AU2
Condenser for high temperat. alarm
[-100 to 150°C]
[-148 to 302°F]
110
Pr2
AH2
Differ. for condenser temp. alar.
recovery
[0.1 to 25.5°C]
[1 to 45°F]
5
Pr2
Ad2
Condenser temperature alarm delay
0 to 254 min, 255(nu)
15
Pr2
dA2
Delay of cond. temper. alarm at start up
0.0 to 24h00min, res. 10 min
1.3
Pr2
bLL
Compr. off for condenser low
temperature alarm
n; Y
n
Pr2
AC2
Compr. off for condenser high
temperature alarm
n; Y
n
Pr2
tbA
Alarm relay disabling
n; Y
Y
Pr2
oA3
Fourth relay configuration
ALr = alarm; dEF = do not select it;
LiG =Light; AUS =AUX; onF=always
on; FAn= do not select it; db = neutral
zone; CP2 = second compressor;
dF2 = do not select it
ALr
Pr2
AoP
Alarm relay polarity (oA3=ALr)
oP; CL
CL
Pr2
i1P
Digital input polarity (18-19)
oP; CL
CL
Pr1
i1F
Digital input configuration (18-19)
EAL; bAL; PAL; dor; dEF; ES; AUS;
Htr; FAn; HdF; onF
dor
Pr1
did
Digital input alarm delay (18-20)
0 to 255 min
15
Pr1
nPS
Number of activation of pressure switch
0 to 15
15
Pr2
odC
Compress and fan status when open
door
no; FAn; CPr; F-C
F-C
Pr2
rrd
Regulation restart with door open alarm
n; Y
Y
Pr2
HES
Differential for Energy Saving
[-30 to 30°C]
[-54 to 54°F]
0
Pr2
Adr
Serial address
0 to 247
1
Pr2
PbC
Kind of probe
PtC; ntC
ntC
Pr2
onF
on/off key enabling
nu; oFF; ES
nu
Pr2
dP1
Room probe display
probe value
-
Pr1
dP2
Evaporator probe display
probe value
-
Pr1
dP3
Third probe display
probe value
-
Pr1
dP4
Fourth probe display
probe value
-
Pr1
rSE
Real set
actual set
-
Pr2
rEL
Software release
read only
-
Pr2
Ptb
Map code
read only
-
Pr2