1592020070 XR70CX GB m&M r1.3 27.03.2015
XR70CX
3/5
dPo
First defrost after start-up:
(n; Y)
n
= after the
idF
time,
Y
= immediately.
dAF
Defrost delay after continuous cycle:
(0.0 to 24h00min, res. 10min) time interval
between the end of the fast freezing cycle and the following defrost related to it.
FANS
FnC
Fans operating mode:
(C-n; o-n; C-Y; o-Y)
C-n
= runs with the compressor, OFF
during defrost;
o-n
= continuous mode, OFF during defrost;
C-Y
= runs with the
compressor, ON during defrost;
o-Y
= continuous mode, ON during defrost.
Fnd
Fans delay after defrost:
(0 to 255min) interval between end of defrost and evaporator
fans start.
FCt
Temperature differential to avoid fan short cycles:
(0 to 59°C; 0 to 90°F) (N.B.: if
FCt=0
function disabled) if the difference of temperature between the evaporator and
the room probes is higher than
FCt
value, the fans will be switched on.
FSt
Fans stop temperature:
(-55 to 50°C; -67 to 122°F) setting of temperature, detected
by evaporator probe, above which fans are always OFF.
Fon
Fan ON time:
(0 to 15min) with
Fnc=C_n
or
C_Y
, (fan activated in parallel with
compressor) it sets the evaporator fan ON cycling time when the compressor is off.
With
Fon=0
and
FoF≠0
the fan are always off, with
Fon=0
and
FoF=0
the fan are
always off.
FoF
Fan OFF time:
(0 to 15min) With
FnC=C_n
or
C_Y
, (fan activated in parallel with
compressor) it sets the evaporator fan off cycling time when the compressor is off.
With
Fon=0
and
FoF≠0
the fan are always off, with
Fon=0
and
FoF=0
the fan are
always off.
FAP
Probe selection for fan management:
(nP; P1; P2; P3; P4)
nP
= no probe;
P1
=thermostat probe;
P2
= evaporator probe;
P3
=configurable probe;
P4
= Probe on
Hot Key plug.
ALARMS
ALC Temperature alarms configuration:
(Ab; rE)
Ab
= absolute temperature, alarm
temperature is given by the
ALL
or
ALU
values.
rE
= temperature alarms are referred
to the set point. Temperature alarm is enabled when the temperature exceeds the
[
SET+ALU
] or [
SET-ALL
] values.
ALU
MAXIMUM temperature alarm:
If
ALC=Ab
: [ALL to 150.0°C or ALL to 302°F]
If
ALC=rE
: [0.0 to 50.0°C or 0 to 90°F]
when this temperature is reached the alarm is enabled, after the
ALd
delay time.
ALL
Minimum temperature alarm:
If
ALC=Ab
: [-100°C to ALU; -148 to ALU]
If
ALC=rE
: [0.0 to 50.0°C or 0 to 90°F]
when this temperature is reached the alarm is enabled, after the
ALd
delay time.
AFH
Differential for temperature alarm recovery:
(0.1 to 25.5°C; 1 to 45°F) intervention
differential for recovery of temperature alarm.
ALd Temperature alarm delay:
(0 to 255 min) time interval between the detection of an
alarm condition and alarm signalling.
dAo
Exclusion of temperature alarm at start-up:
(0.0 to 24h00min, res. 10min) time
interval between the detection of the temperature alarm condition after instrument
power on and alarm signalling.
CONDENSER TEMPERATURE ALARM
AP2
Probe selection for temperature alarm of condenser:
(nP; P1; P2; P3; P4)
nP
= no probe;
P1
= thermostat probe;
P2
= evaporator probe;
P3
= configurable
probe;
P4
= Probe on Hot Key plug.
AL2
Low temperature alarm of condenser:
(-100 to 150°C; -148 to 302°F) when this
temperature is reached the
LA2
alarm is signalled, possibly after the Ad2 delay.
Au2
High temperature alarm of condenser:
(-100 to 150°C; -148 to 302°F) when this
temperature is reached the
HA2
alarm is signalled, possibly after the
Ad2
delay.
AH2
Differential for temperature condenser alarm recovery:
0.1 to 25.5°C; 1 to 45°F
Ad2
Condenser temperature alarm delay:
(0 to 255 min) time interval between the
detection of the condenser alarm condition and alarm signalling.
dA2
Condenser temperature alarm exclusion at start up:
0.0 to 24h00min, res. 10min.
bLL
Compressor off with low temperature alarm of condenser:
(n; Y)
n
= compressor
keeps on working;
Y
= compressor is switched off till the alarm is present, in any case
regulation restarts after
AC
time at minimum.
AC2
Compressor off with high temperature alarm of condenser:
(n; Y)
n
= compressor
keeps on working;
Y
= compressor is switched off till the alarm is present, in any case
regulation restarts after
AC
time at minimum.
FOURTH RELAY
tbA
Alarm relay silencing (with oA3 =ALr):
(n; Y)
n
= silencing disabled: alarm relay
stays on till alarm condition lasts.
Y
= silencing enabled: alarm relay is switched OFF by
pressing a key during an alarm.
oA3
Second relay configuration (1-4):
(dEF; FAn; ALr; LiG; AUS; onF; db; dEF2; HES)
dEF
= defrost;
FAn
= do not select it;
ALr
= alarm;
LiG
= light;
AUS
= Auxiliary relay;
onF
= always on with instrument on;
db
= neutral zone;
dEF2
= do not select it;
HES
=
night blind.
AoP
Alarm relay polarity:
(CL; oP) it set if the alarm relay is open or closed when an alarm
occurs.
CL
= terminals 1-4 closed during an alarm;
oP
= terminals 1-4 open during an
alarm.
DIGITAL INPUTS
i1P
Second digital input polarity:
(oP; CL)
oP
= the digital input is activated by opening
the contact;
CL
= the digital input is activated by closing the contact.
i1F
Second digital input configuration:
(EAL; bAL; PAL; dor; dEF; ES; AUS; Htr; FAn;
HdF; onF)
EAL
= external alarm: “
EA
” message is displayed;
bAL
= serious alarm “
CA
”
message is displayed;
PAL
= pressure switch alarm, “
CA
” message is displayed;
dor
=
door switch function;
dEF
= activation of a defrost cycle;
ES
= energy saving;
AUS
=
auxiliary relay activation with
oA3=AUS
;
Htr
= type of inverting action (cooling or
heating);
FAn
= fan;
HdF
= Holiday defrost (enable only with RTC);
onF
= to switch the
controller off.
did
Digital input 1 alarm delay:
(0 to 255 min) delay between the detection of the
external alarm condition and its signalling.
When
i1F= PAL
, it is the interval of time to calculate the number of pressure switch
activation.
nPS
Number of pressure switch activation:
(0 to 15) Number of activation, during the
did
or
d2d
interval, before signalling an alarm event (
i1F, i2F=PAL
).
If the
nPS
activation during
did
or
d2d
time is reached, switch off and on the instrument
to restart normal regulation.
odC
Compressor status when open door:
(no; FAn; CPr;F_C;)
no
= normal;
FAn
= normal;
CPr
= compressor OFF,
F_C
= compressor OFF.
rrd
Outputs restart after door open alarm:
(n; Y)
n
= outputs follow the
odC
parameter.
Y
= outputs restart with a door open alarm.
HES
Delta temperature during an Energy Saving cycle:
(-30.0 to 30.0°C; -54 to 54°F) it
sets the increasing value of the set point
[SET+HES]
during the Energy Saving cycle.
OTHER
Adr
Serial address:
(1 to 247) identifies the instrument address when connected to a
ModBUS compatible monitoring system.
PbC
Type of probe:
(PtC; ntC) it allows to set the kind of probe used by the instrument:
PtC
= PTC probe,
ntC
= NTC probe.
onF
On/Off key enabling:
(nU; oFF; ES)
nU
= disabled;
oFF
= enabled;
ES
= not set it.
dP1
Thermostat probe display.
dP2
Evaporator probe display.
dP3
Third probe display- optional.
dP4
Fourth probe display.
rSE
Real set point: it shows the set point used during the energy saving cycle or during the
continuous cycle.
rEL
Software release for internal use.
Ptb
Parameter table code: readable only.
8.
DIGITAL INPUTS
The free voltage digital input is programmable by the
i1F
parameter.
8.1
GENERIC ALARM (I1F = EAL)
As soon as the digital input is activated the unit will wait for
did
time delay before signalling the
EAL
alarm message. The outputs statuses don’t change. The alarm stops just after the digital input is de-
activated.
8.2
SERIOUS ALARM MODE (I1F = BAL)
When the digital input is activated, the unit will wait for
did
delay before signalling the
CA
alarm
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated.
8.3
PRESSURE SWITCH (I1F = PAL)
If during the interval time set by
did
parameter, the pressure switch has reached the number of
activation of the
nPS
parameter; the
CA
pressure alarm message will be displayed. The compressor
and the regulation are stopped. When the digital input is ON the compressor is always OFF.
If the
nPS activation in the did time is reached, switch off and on the instrument to restart normal
regulation.
8.4
DOOR SWITCH INPUT (I1F = DOR)
It signals the door status and the corresponding relay output status through the
odC
parameter:
no
= normal (any change);
FAn
= Fan OFF;
CPr
= Compressor OFF;
F_C
= Compressor and fan
OFF. Since the door is opened, after the delay time set through parameter
doA
, the door alarm is
enabled, the display shows the message
dA
and
the regulation restarts is rtr=YES.
The alarm
stops as soon as the external digital input is disabled again. With the door open, the high and low
temperature alarms are disabled.
8.5
START DEFROST (I1F = DEF)
It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation
will restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety
time is expired.
8.6
SWITCH THE AUXILIARY RELAY (I1F = AUS)
With oA3 = AUS the digital input switched the status of the auxiliary relay
8.7
INVERSION OF THE KIND OF ACTION: HEATING-COOLING (I1F=HTR)
This function allows to invert the regulation of the controller: from cooling to heating and viceversa.
8.8
ENERGY SAVING (I1F = ES)
The Energy Saving function allows to change the set point value as the result of the SET+ HES
(parameter) sum. This function is enabled until the digital input is activated.
8.9
ON OFF FUNCTION (I1F = ONF)
To switch the controller on and off.
8.10
DIGITAL INPUT POLARITY
The digital input polarity depends on the
i1P
parameter.
i1P = CL
: the input is activated by closing the contact.
i1P = oP
: the input is activated by opening the contact
9.
TTL SERIAL LINE – FOR MONITORING SYSTEMS
The TTL serial line, available through the HOT KEY connector, allows to connect the instrument to a
monitoring system
ModBUS-RTU
compatible such as the
XWEB500
.
10.
X-REP OUTPUT – OPTIONAL
As optional, an X-REP can be connected to the instrument, trough the dedicated
connector.