XR70CX 

3/5 

dPo 

First defrost after start-up:

 (n; Y)  

 

n

 = after the 

idF

 time,  

 

Y

 = immediately. 

dAF 

Defrost  delay  after  continuous  cycle:

  (0.0  to  24h00min,  res.  10min)  time  interval 

between the end of the fast freezing cycle and the following defrost related to it. 

FANS 

FnC 

Fans  operating  mode:

  (C-n;  o-n;  C-Y;  o-Y) 

C-n

  =  runs  with  the  compressor,  OFF 

during  defrost; 

o-n

  =  continuous  mode,  OFF  during  defrost; 

C-Y

  =  runs  with  the 

compressor, ON during defrost; 

o-Y

 = continuous mode, ON during defrost. 

Fnd 

Fans delay after defrost:

 (0 to 255min) interval between end of defrost and evaporator 

fans start. 

FCt 

Temperature differential to avoid fan short cycles:

 (0 to 59°C; 0 to 90°F) (N.B.: if 

FCt=0

 function disabled) if the difference of temperature between the evaporator and 

the room probes is higher than 

FCt

 value, the fans will be switched on. 

FSt 

Fans stop temperature:

 (-55 to 50°C; -67 to 122°F) setting of temperature, detected 

by evaporator probe, above which fans are always OFF. 

Fon 

Fan  ON  time:

  (0  to  15min)  with 

Fnc=C_n

  or 

C_Y

,  (fan  activated  in  parallel  with 

compressor)  it  sets  the  evaporator  fan  ON  cycling  time  when  the  compressor  is  off. 
With 

Fon=0

  and 

FoF≠0

  the  fan  are  always  off,  with 

Fon=0

  and 

FoF=0

  the  fan  are 

always off. 

FoF 

Fan  OFF  time:

  (0  to  15min)  With 

FnC=C_n

  or 

C_Y

,  (fan  activated  in  parallel  with 

compressor) it sets the evaporator fan off cycling time when the compressor is off.  
With 

Fon=0

  and 

FoF≠0

  the  fan  are  always  off,  with 

Fon=0

  and 

FoF=0

  the  fan  are 

always off. 

FAP 

Probe selection for fan management:

 (nP; P1; P2; P3; P4) 

nP

 = no probe;  

P1

 =thermostat probe; 

P2

 = evaporator probe; 

P3

 =configurable probe; 

P4

 = Probe on 

Hot Key plug. 

ALARMS 

ALC    Temperature  alarms  configuration:

  (Ab;  rE) 

Ab

  =  absolute  temperature,  alarm 

temperature is given by the 

ALL

 or 

ALU

 values.  

rE

 = temperature alarms are referred 

to  the  set  point.  Temperature  alarm  is  enabled  when  the  temperature  exceeds  the 
[

SET+ALU

] or [

SET-ALL

] values. 

ALU 

MAXIMUM temperature alarm:

  

 

If 

ALC=Ab

: [ALL to 150.0°C or ALL to 302°F] 

 

If 

ALC=rE

: [0.0 to 50.0°C or 0 to 90°F] 

when this temperature is reached the alarm is enabled, after the 

ALd

 delay time. 

ALL 

Minimum temperature alarm:

  

 

If 

ALC=Ab

: [-100°C to ALU; -148 to ALU] 

 

If 

ALC=rE

: [0.0 to 50.0°C or 0 to 90°F] 

when this temperature is reached the alarm is enabled, after the 

ALd

 delay time. 

AFH 

Differential for temperature alarm recovery:

 (0.1 to 25.5°C; 1 to 45°F) intervention 

differential for recovery of temperature alarm. 

ALd    Temperature  alarm  delay:

  (0  to  255  min)  time  interval  between  the  detection  of  an 

alarm condition and alarm signalling. 

dAo 

Exclusion  of  temperature  alarm  at  start-up:

  (0.0  to  24h00min,  res.  10min)  time 

interval  between  the  detection  of  the  temperature  alarm  condition  after  instrument 
power on and alarm signalling. 

CONDENSER TEMPERATURE ALARM 

AP2 

Probe selection for temperature alarm of condenser:

 (nP; P1; P2; P3; P4)  

nP

  =  no  probe; 

P1

  =  thermostat  probe; 

P2

  =  evaporator  probe; 

P3

  =  configurable 

probe; 

P4

 = Probe on Hot Key plug. 

AL2 

Low  temperature  alarm  of  condenser:

  (-100  to  150°C;  -148  to  302°F)  when  this 

temperature is reached the 

LA2

 alarm is signalled, possibly after the Ad2 delay. 

Au2 

High  temperature  alarm  of  condenser:

  (-100  to  150°C;  -148  to  302°F)  when  this 

temperature is reached the 

HA2

 alarm is signalled, possibly after the 

Ad2

 delay. 

AH2 

Differential for temperature condenser alarm recovery:

 0.1 to 25.5°C; 1 to 45°F 

Ad2 

Condenser  temperature  alarm  delay:

  (0  to  255  min)  time  interval  between  the 

detection of the condenser alarm condition and alarm signalling. 

dA2 

Condenser temperature alarm exclusion at start up:

 0.0 to 24h00min, res. 10min. 

bLL 

Compressor off with low temperature alarm of condenser:

 (n; Y) 

n

 = compressor 

keeps on working; 

Y

 = compressor is switched off till the alarm is present, in any case 

regulation restarts after 

AC

 time at minimum. 

AC2 

Compressor off with high temperature alarm of condenser:

 (n; Y) 

n

 = compressor 

keeps on working; 

Y

 = compressor is switched off till the alarm is present, in any case 

regulation restarts after 

AC

 time at minimum. 

FOURTH RELAY 

tbA 

Alarm  relay  silencing  (with  oA3  =ALr):

  (n;  Y) 

n

  =  silencing  disabled:  alarm  relay 

stays on till alarm condition lasts. 

Y

 = silencing enabled: alarm relay is switched OFF by 

pressing a key during an alarm. 

oA3 

Second relay configuration (1-4): 

(dEF; FAn;  ALr; LiG; AUS; onF; db; dEF2; HES) 

dEF

 = defrost; 

FAn

 = do not select it; 

ALr

 = alarm; 

LiG

 = light; 

AUS

 = Auxiliary relay; 

onF

 = always on with instrument on; 

db

 = neutral zone; 

dEF2

 = do not select it; 

HES

 = 

night blind. 

AoP 

Alarm relay polarity:

 (CL; oP) it set if the alarm relay is open or closed when an alarm 

occurs. 

CL 

= terminals 1-4 closed during an alarm; 

oP

 = terminals 1-4 open during an 

alarm. 

DIGITAL INPUTS 

i1P 

Second digital input polarity:

 (oP; CL) 

oP

 = the digital input is activated by opening 

the contact; 

CL 

= the digital input is activated by closing the contact. 

i1F   

Second digital input configuration:

 (EAL; bAL; PAL; dor; dEF; ES; AUS; Htr; FAn; 

HdF; onF) 

EAL 

= external alarm: “

EA

” message is displayed; 

bAL

 = serious alarm “

CA

” 

message is displayed; 

PAL

 = pressure switch alarm, “

CA

” message is displayed; 

dor

 = 

door switch function; 

dEF

 = activation of a defrost cycle; 

ES

 = energy saving; 

AUS

 = 

auxiliary  relay  activation  with 

oA3=AUS

Htr

  =  type  of  inverting  action  (cooling  or 

heating); 

FAn

 = fan; 

HdF

 = Holiday defrost (enable only with RTC); 

onF

 = to switch the 

controller off. 

did 

Digital  input  1  alarm  delay: 

  (0  to  255  min)  delay  between  the  detection  of  the 

external alarm condition and its signalling. 
When 

i1F=  PAL

,  it is the interval of  time to calculate the number of  pressure switch 

activation. 

nPS 

Number of pressure switch activation:

 (0 to 15) Number of activation, during the 

did

 

or 

d2d

 interval, before signalling an alarm event (

i1F, i2F=PAL

).  

If the 

nPS

 activation during 

did 

or 

d2d

 time is reached, switch off and on the instrument 

to restart normal regulation. 

odC 

Compressor status when open door:

 (no; FAn; CPr;F_C;)  

no

 = normal;  

FAn

 = normal; 

CPr

 = compressor OFF, 

F_C

 = compressor OFF. 

rrd 

Outputs restart after door open alarm:

 (n; Y) 

n

 = outputs follow the 

odC

 parameter.  

Y

 = outputs restart with a door open alarm.  

HES 

Delta temperature during an Energy Saving cycle: 

(-30.0 to 30.0°C; -54 to 54°F) it 

sets the increasing value of the set point 

[SET+HES]

 during the Energy Saving cycle.

 

OTHER 

Adr 

Serial  address:

  (1  to  247)  identifies  the  instrument  address  when  connected  to  a 

ModBUS compatible monitoring system. 

PbC 

Type of probe:

 (PtC; ntC) it allows to set the kind of probe used by the instrument:  

PtC 

= PTC probe, 

ntC

 = NTC probe. 

onF 

On/Off key enabling:

 (nU; oFF; ES) 

nU

 = disabled; 

oFF

 = enabled; 

ES

 = not set it. 

dP1 

Thermostat probe display. 

dP2 

Evaporator probe display. 

dP3 

Third probe display- optional. 

dP4 

Fourth probe display. 

rSE 

Real set point: it shows the set point used during the energy saving cycle or during the 
continuous cycle. 

rEL 

Software release for internal use. 

Ptb 

Parameter table code: readable only. 

8.

 

DIGITAL INPUTS  

The free voltage digital input is programmable by the 

i1F

 parameter. 

8.1

 

GENERIC ALARM (I1F = EAL) 

As soon as the digital input is activated the unit will wait for 

did

 time delay before signalling the 

EAL

 

alarm message. The outputs statuses don’t change. The alarm stops just after the digital input is de-
activated. 

8.2

 

SERIOUS ALARM MODE (I1F = BAL) 

When  the  digital  input  is  activated,  the  unit  will  wait  for 

did

  delay  before  signalling  the 

CA

  alarm 

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated. 

8.3

 

PRESSURE SWITCH (I1F = PAL) 

If  during  the  interval  time  set  by 

did

  parameter,  the  pressure  switch  has  reached  the  number  of 

activation of the 

nPS

 parameter; the 

CA

 pressure alarm message will be displayed. The compressor 

and the regulation are stopped. When the digital input is ON the compressor is always OFF. 

If the 

nPS activation in the did time is reached, switch off and on the instrument to restart normal 

regulation. 

8.4

 

DOOR SWITCH INPUT (I1F = DOR) 

It signals the door status and the corresponding relay output status through the 

odC

 parameter:  

no 

= normal (any change); 

FAn

 = Fan OFF; 

CPr

 = Compressor OFF; 

F_C

 = Compressor and fan 

OFF. Since the door is opened, after the delay time set through parameter 

doA

, the door alarm is 

enabled,  the  display  shows  the  message 

dA

  and 

the  regulation  restarts  is  rtr=YES.

  The  alarm 

stops as soon as the external digital input is disabled again. With the door open, the high and low 
temperature alarms are disabled. 

8.5

 

START DEFROST (I1F = DEF) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation 
will restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety 
time is expired. 

8.6

 

SWITCH THE AUXILIARY RELAY (I1F = AUS) 

With oA3 = AUS the digital input switched the status of the auxiliary relay 

8.7

 

INVERSION OF THE KIND OF ACTION: HEATING-COOLING (I1F=HTR)  

This function allows to invert the regulation of the controller: from cooling to heating and viceversa. 

8.8

 

ENERGY SAVING (I1F = ES) 

The  Energy  Saving  function  allows  to  change  the  set  point  value  as  the  result  of  the  SET+  HES 
(parameter) sum. This function is enabled until the digital input is activated. 

8.9

 

ON OFF FUNCTION (I1F = ONF)  

To switch the controller on and off. 

8.10

 

DIGITAL INPUT POLARITY  

The digital input polarity depends on the 

i1P

 parameter. 

i1P = CL

: the input is activated by closing the contact.

 

i1P = oP

: the input is activated by opening the contact 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS 

The TTL serial line, available through the HOT KEY connector, allows to connect the instrument to a 
monitoring system 

ModBUS-RTU

 compatible such as the 

XWEB500

10.

 

X-REP OUTPUT – OPTIONAL 

As optional, an X-REP can be connected to the instrument, trough the dedicated 
connector. 

 

Содержание Dixell XR70CX

Страница 1: ... the Dixell monitoring units of X WEB family It allows to program the controller by means the HOT KEY programming keyboard The instrument is fully configurable through special parameters that can be easily programmed through the keyboard 3 CONTROLLING LOADS 3 1 COMPRESSOR The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the...

Страница 2: ... sets the minimum value for the set point US Maximum set point SET to 150 C SET to 302 F set the maximum value for set point ot Thermostat probe calibration 12 0 to 12 0 C 21 to 21 F allows to adjust possible offset of the thermostat probe P2P Evaporator probe presence n Y n not present the defrost stops by time Y present the defrost stops by temperature oE Evaporator probe calibration 12 0 to 12 ...

Страница 3: ...by opening the contact CL the digital input is activated by closing the contact i1F Second digital input configuration EAL bAL PAL dor dEF ES AUS Htr FAn HdF onF EAL external alarm EA message is displayed bAL serious alarm CA message is displayed PAL pressure switch alarm CA message is displayed dor door switch function dEF activation of a defrost cycle ES energy saving AUS auxiliary relay activat...

Страница 4: ...alarm Output unchanged CA Serious external alarm i2F bAL All outputs OFF CA Pressure switch alarm i2F PAL All outputs OFF rtc Real time clock alarm Alarm output ON Other outputs unchanged Defrosts according to par idF Set real time clock has to be set rtF Real time clock board failure Alarm output ON Other outputs unchanged Defrosts according to par idF Contact the service 14 1 ALARM RECOVERY Prob...

Страница 5: ...C 0 to 90 F AbS 100 C to ALU 148 F to ALU 50 0 Pr1 AFH Differential for temperat alarm recovery 0 1 to 25 5 C 1 to 45 F 1 0 Pr2 ALd Temperature alarm delay 0 to 255 min 15 Pr2 dAo Delay of temperature alarm at start up 0 0 to 24h00min res 10 min 1 3 Pr2 AP2 Probe for temperat alarm of condenser nP P1 P2 P3 P4 P4 Pr2 AL2 Condenser for low temperat alarm 100 to 150 C 148 to 302 F 40 Pr2 AU2 Condense...

Отзывы: