1592020070 XR70CX GB m&M r1.3 27.03.2015 

XR70CX 

4/5 

 

To connect the X-REP to the 
instrument the following connectors 
must be used CAB-51F(1m), CAB-
52F(2m), CAB-55F(5m), 

11.

 

INSTALLATION AND MOUNTING 

 

Instrument 

XR70CX

  shall  be  mounted  on  vertical  panel,  in  a 

29x71 mm hole, and fixed using the special bracket supplied.  
The temperature range allowed for correct operation is 0 to 60°C. 
Avoid  places  subject  to  strong  vibrations,  corrosive  gases, 
excessive  dirt  or  humidity. The same recommendations apply to 
probes. Let air circulate by the cooling holes. 
 

 

12.

 

ELECTRICAL CONNECTIONS 

The instrument is provided with screw terminal block to connect cables with a cross section up to 
2.5mm

2

.  Before  connecting  cables  make  sure  the  power  supply  complies  with  the  instrument’s 

requirements.  Separate  the probe cables from the power supply cables, from the outputs and the 
power connections. Do not exceed the maximum current allowed on each relay, in case of heavier 
loads use a suitable external relay. 

12.1

 

PROBE CONNECTION 

The  probes  shall  be  mounted  with  the  bulb  upwards  to  prevent  damages  due  to  casual  liquid 
infiltration.  It  is  recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly 
measure the average room temperature. Place the defrost termination probe among the evaporator 
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 
defrost, to prevent premature defrost termination. 

13.

 

USE THE HOT KEY  

13.1

 

HOW TO: PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the “

HOT-KEY

” and push 

UP 

button; the “

uPL

 

message 

appears followed a by a flashing “

End

” label. 

3.

 

Push 

SET 

button and the “

End

” will stop flashing. 

4.

 

Turn OFF the instrument, remove the “

HOT-KEY

” and

 

then turn it ON again. 

 

NOTE

:  the  “

Err

”  message  appears  in  case  of  a  failed  programming  operation.  In  this  case  push 

again button if you want to restart the upload again or remove the “

HOT-KEY

” to abort the operation. 

13.2

 

HOW TO: PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert a 

pre-programmed 

HOT-KEY

 into the 5-PIN receptacle 

and then turn the Controller 

ON. 

3.

 

The  parameter  list  of  the  “

HOT-KEY

”  will  be  automatically  downloaded  into  the  Controller 

memory. The “

doL

” message will blink followed a by a flashing “

End

” label. 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the “

HOT-KEY

”. 

 

NOTE: 

the message “

Err

” is displayed for failed programming. In this case turn the unit off and then 

on if you want to restart the download again or remove the “

HOT-KEY

” to abort the operation. 

14.

 

ALARM SIGNALS 

Message 

Cause 

Outputs 

“P1” 

Room probe  failure 

Compressor output acc. to par. 

Con

 and 

CoF

 

“P2” 

Evaporator probe  failure 

Defrost end is timed 

“P3” 

Third probe  failure 

Outputs unchanged 

“P4” 

Fourth probe  failure 

Outputs unchanged 

“HA” 

Maximum temperature alarm 

Outputs unchanged. 

“LA” 

Minimum temperature alarm 

Outputs unchanged. 

"HA2" 

Condenser high temperature 

It depends on the 

AC2

 parameter 

"LA2" 

Condenser low temperature 

It depends on the 

bLL

 parameter 

“dA” 

Door open 

Compressor and fans restarts  

“EA” 

External alarm 

Output unchanged. 

“CA” 

Serious external alarm (

i2F=bAL

)  All outputs OFF. 

“CA” 

Pressure switch alarm (

i2F=PAL

)  All outputs OFF 

“rtc” 

Real time clock alarm 

Alarm output ON; Other outputs unchanged; 
Defrosts according to par. 

idF

 Set real time clock 

has to be set 

rtF 

Real time clock board failure 

Alarm output ON; Other outputs unchanged; 
Defrosts according to par. 

idF

 Contact the service 

14.1

 

ALARM RECOVERY  

Probe alarms 

P1

”, “

P2”,

 “

P3

” and “

P4

” start some seconds after the fault in the related probe; they 

automatically  stop  some  seconds  after  the  probe  restarts  normal  operation.  Check  connections 
before replacing the probe. 
Temperature  alarms  “

HA

”,  “

LA

”  “

HA2

”  and  “

LA2

”  automatically  stop  as  soon  as  the  temperature 

returns to normal values. 
Alarms 

“EA”

 and 

“CA” 

(with 

i2F=bAL

)

 

recover as soon as the digital input is disabled. 

Alarm “

CA”

 (with 

i2F=PAL

) recovers only by 

switching off and on

 the instrument. 

14.2

 

OTHER MESSAGES 

Pon 

Keyboard unlocked. 

PoF 

Keyboard locked 

noP 

In programming mode

: none parameter is present in Pr1 

On the display

 or in dP2, dP3, dP4: the selected probe is nor enabled 

15.

 

TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: 

frontal 32x74 mm; depth 60mm; 

Mounting: 

panel mounting in a 71x29mm panel cut-out 

Protection: 

IP20; 

Frontal protection: 

IP65 

Connections: 

Screw terminal block 

 2.5 mm

2

 wiring 

Power supply: 

according to the model  

12VAC/DC, ±10% 
110AC 

10%, 50/60Hz

 

230VAC 

10%, 50/60Hz 

Power absorption: 

3VA max

 

Display

: 3 digits, red LED, 14.2 mm high  

Inputs

: Up to 4 NTC or PTC probes

 

Digital inputs: 

 free voltage contact 

Relay outputs: compressor 

SPST 8(3) A, 250VAC or SPST 16A 250VAC

 

 

Defrost: 

SPDT 8(3) A, 250VAC 

 

Fan: 

SPST 5A, 250VAC 

 

Aux: 

SPDT 8(3) A, 250VAC  

Buzzer: 

optional 

Data storing

: on the non-volatile memory (EEPROM) 

Internal clock back-up:

 24 hours 

Kind of action: 

1B  

Pollution degree: 

Software class: 

A  

Rated impulsive voltage

: 2500V  

Overvoltage Category

: II

 

Operating temperature: 

0 to 55°C 

Storage temperature: 

-25 to 60°C  

Relative humidity:

 20 to 85% (no condensing) 

Measuring and regulation range:  

NTC probe: 

-40 to 110°C (-40 to 230°F)  

PTC probe: 

-100 to 150°C (-148 to 302°F) 

Resolution: 

0.1°C or 1°C or 1°F (selectable)  

Accuracy (ambient temp. 25°C)

:  ±0.7°C ±1 digit 

16.

 

CONNECTIONS 

The X-REP

 

output

 

excludes

 the TTL output.. It’s present in the following codes:  

XR70CX- xx

2

xx, XR70CX –xx

3

xx; 

16.1

 

XR70CX – 8A OR 16A COMP. RELAY - 230VAC OR 110VAC 

 

NOTE: 

The compressor relay is 

8(3)A or 16(6)A according to the 

model. 

24Vac supply

: connect to the 

terminals 5 and 6. 

 

16.2

 

XR70CX – 4 X 16A - 12VAC/DC 

 

 

17.

 

DEFAULT SETTING VALUES 

Label 

Name 

Range 

Value  Level 

SEt 

Set point 

LS; US 

-5.0 

- - - 

HY 

Differential 

[0.1 to 25.5°C] 

[1 to 45°F] 

2.0 

Pr1 

LS 

Minimum set point 

[-100°C to SET] 

[-148°F to SET] 

-50.0 

Pr2 

US 

Maximum set point 

[SET to 150°C] 

[SET to 302°F] 

110 

Pr2 

ot 

Thermostat probe calibration 

[-12.0 to 12.0°C] 

[-21 to 21°F] 

0.0 

Pr1 

P2P 

Evaporator probe presence 

n; Y 

Pr1 

oE 

Evaporator probe calibration 

[-12.0 to 12.0°C] 

[-21 to 21°F] 

0.0 

Pr2 

P3P 

Third probe presence 

n; Y 

Pr2 

o3 

Third probe calibration 

[-12.0 to 12.0°C] 

[-21 to 21°F] 

Pr2 

P4P 

Fourth probe presence 

n; Y 

Pr2 

o4 

Fourth probe calibration 

[-12.0 to 12.0°C] 

[-21 to 21°F] 

Pr2 

odS 

Outputs delay at start up 

0 to 255 min 

Pr2 

AC 

Anti-short cycle delay 

0 to 50 min 

Pr1 

rtr 

P1-P2 percentage for regulation 

0 to 100 (100=P1 , 0=P2) 

100 

Pr2 

CCt 

Continuous cycle duration 

0.0 to 24h00min, res. 10 min 

0.0 

Pr2 

CCS 

Set point for continuous cycle 

[-100 to 150.0°C] 

[-148 to 302°F] 

-5 

Pr2 

Содержание Dixell XR70CX

Страница 1: ... the Dixell monitoring units of X WEB family It allows to program the controller by means the HOT KEY programming keyboard The instrument is fully configurable through special parameters that can be easily programmed through the keyboard 3 CONTROLLING LOADS 3 1 COMPRESSOR The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the...

Страница 2: ... sets the minimum value for the set point US Maximum set point SET to 150 C SET to 302 F set the maximum value for set point ot Thermostat probe calibration 12 0 to 12 0 C 21 to 21 F allows to adjust possible offset of the thermostat probe P2P Evaporator probe presence n Y n not present the defrost stops by time Y present the defrost stops by temperature oE Evaporator probe calibration 12 0 to 12 ...

Страница 3: ...by opening the contact CL the digital input is activated by closing the contact i1F Second digital input configuration EAL bAL PAL dor dEF ES AUS Htr FAn HdF onF EAL external alarm EA message is displayed bAL serious alarm CA message is displayed PAL pressure switch alarm CA message is displayed dor door switch function dEF activation of a defrost cycle ES energy saving AUS auxiliary relay activat...

Страница 4: ...alarm Output unchanged CA Serious external alarm i2F bAL All outputs OFF CA Pressure switch alarm i2F PAL All outputs OFF rtc Real time clock alarm Alarm output ON Other outputs unchanged Defrosts according to par idF Set real time clock has to be set rtF Real time clock board failure Alarm output ON Other outputs unchanged Defrosts according to par idF Contact the service 14 1 ALARM RECOVERY Prob...

Страница 5: ...C 0 to 90 F AbS 100 C to ALU 148 F to ALU 50 0 Pr1 AFH Differential for temperat alarm recovery 0 1 to 25 5 C 1 to 45 F 1 0 Pr2 ALd Temperature alarm delay 0 to 255 min 15 Pr2 dAo Delay of temperature alarm at start up 0 0 to 24h00min res 10 min 1 3 Pr2 AP2 Probe for temperat alarm of condenser nP P1 P2 P3 P4 P4 Pr2 AL2 Condenser for low temperat alarm 100 to 150 C 148 to 302 F 40 Pr2 AU2 Condense...