dP3
- - -
Probe 3 display
Read only
L°t
- - -
Minimum temperature display
Read only
H°t
- - -
Maximum temperature display
Read only
ALTERNATIVE PARAMETER MAP
SET
4
Set point
LS to US
Hy*
3
HY is the ON/OFF heat regulation differential
[0.1 to 25.5°C]
LS*
0
Minimum Set-Point that can be set by keyboard
[-55.0 to SET]
US*
20
Maximum Set-Point that can be set by keyboard
[SET to 150.0°C]
tdF*
OFF
Defrosting mode
EL; in; OFF
dtE*
8
Probe dPA defrost 1 end temperature
[-55.0 to 50.0°C]
dtS*
8
Probe dPb defrost 2 end temperature
[-55.0 to 50.0°C]
idF*
8
Defrost 1 interval if EdF=in (intervals) If idF=0 defrost is forced manually only, from serial, from outside contact, from
coordinated defrost LAN.
0 to 120 hours
IdS*
0
Defrost 2 interval if EdF=in (intervals) If idS=0 defrost is forced manually only, from serial, from outside contact, from
coordinated defrost LAN.
0 to 120 hours
MdF*
30
Maximum duration forcing defrost 1 end if it is not cut-off before the dTE temperature.
0 to 255 min
MdS*
0
Maximum duration forcing defrost 2 end if it is not cut-off before the dTS temperature.
0 to 255 min
dFd*
rt
Display during defrost
rt; it; Set, dEF
FnC*
O-y
Fans functioning mode. C= active only with cold output ON, O= always active, n= stopped for defrost, Y= active for defrost.
C-n; O-n; C-Y; O-Y
Fnd*
0
Fan switch-on delay after defrost
0 to 255 min
FSt*
10
Fan block temperature on fan probe
[-55.0 to 50.0°C]
Ot*
0
Probe P1 calibration
[-12.0 to 12.0°C]
P1C*
Ntc
Probe P1 Configuration nP= not present
nP; PtC; ntC
P2C*
nP
Probe P2 Configuration nP= not present
nP; PtC; ntC
P3C*
nP
Probe P3 Configuration nP= not present
nP; PtC; ntC