1592001530 XC15-35CX EN r1.2 11.04.2017 XC15-35CX
9/40
Temperature probes (NTC10k)
Pb1 (P1C = NTC): 13-14
Pb2 (P2C =NTC): 13-15
Temperature probes (NTC10k, PT1000, NTC86k)
Pb3 (P3C = NTC, PT1000, NTC86k): 19-21
Pb4 (P4C = NTC, PT1000, NTC86k): 19-20
Ratiometric transducers (0.5÷4.5Vdc)
Pb1 (P1C = 0-5)
13 (+); 14(in); 16 (gnd)
Pb2 (P2C =0-5)
13 (+); 15(in); 16 (gnd)
4.4 DIGITAL INPUTS
D.I.1:
available if probe
P3
in not available (
P3P=no
)
D.I.2:
always available
D.I.3:
available if probe
P4
in not available (
P4P=no
)
NOTE: all digital inputs are free of voltage input types
4.5 ANALOGUE OUTPUT: OAN
Output PWM:
17(-); 18(+)
Output 0-10Vdc:
17(+); 18(-)
4.6 POWER OUTPUT: OA3 (TRIAC)
There are 2 different models, characterized by a different TRIAC power supply stage. As
general rule, the TRIAC is always internally connected to the device power supply line.