1592001530 XC15-35CX EN r1.2 11.04.2017 XC15-35CX
34/40
17.3
“BUMP” FUNCTION
This feature is available only using ON-OFF compressors and if par.
bMp=Y
. When regulation
starts, the compressor will be activated and deactivated for a
nub
number of cycles and with a
duration respectively set in par.
bon
and
boF
. During the "BUMP" phase pressure/temperature
alarms are ignored.
17.4 COMPRESSOR CAPACITY LIMITATION IN CASE OF HIGH
CONDENSER PRESSURE/TEMPERATURE
If pressure/temperature measured from probe
FPb>HAF
, then the compressor capacity will be
able to be limited in the following way:
-
By using par.
HFL
(if Digital or inverter-controlled compressor) for
dHF
interval of
time. After that, the compressor will be stopped if the alarm condition persists and if
HFC=YES
-
Immediately stopped after
dHF
interval of time if ON-OFF compressor.
17.5 PRESSURE PROBE ERROR MANAGEMENT AT START-UP
At powering on, a pressure error probe will be signaled after the
P1d
delay expires. If pressure
error probe persists, the ON-OFF compressor will be activated following par.
Con
and
CoF
.
If regulation is stopped because of:
-
Safety delays
-
External alarms (from digital input)
-
Pressure alarms
then any measured pressure value out of the probe range will not raise any additional alarm but
the display will show the last valid measured value.