1592001530 XC15-35CX EN r1.2 11.04.2017 XC15-35CX
12/40
5. Mounting & installation
The instruments are suitable only for internal use. Instruments shall be mounted on panel, in a
29x71 mm hole, and fixed using the special brackets supplied.
The ambient operating temperature range is between -10T60°C.
Avoid locations subject to heavy vibration, corrosive gases or excessive dirt. The same applies
to the probes. Ensure ventilation around the instrument.
78,5
36
,9
59,5
28
,5
6
70
29
71
6. FIRST INSTALLATION
PRELIMINARY CONFIGURATION CHECK:
Check pressure transducer range:
P1i
,
P1E
,
P2i
e
P2E
Check unit of measurement for both compressor and ventilator regulators
6.1 PRESSURE TRANSDUCERS
Use the following parameters to set pressure probe range for both P1 (suction probe) and P2
(discharge probe):
P1i, P2i:
set the measurment value corresponding to 0.5V
P1E, P2E:
set the measurment value corresponding to 4.5V
These parameters need to be set with the boundaries of the operating range of the pressure
probe.
Procedure:
1.
Enter programming menu by keeping
SET+DOWN
pressed for 3 sec