1592001530 XC15-35CX EN r1.2 11.04.2017 XC15-35CX
25/40
bMi
Interval of time with compressor OFF before activating the BUMP function:
0.0
to 23h50min, res. 10 min
15.14 ANTI-RESONANCE
ArF
Anti-resonance function enabled:
n; Y
Si1
Lower boundary of the first skipped band:
-
If frequency output: 0 to
SE1
Hz
-
If voltage output: 0.0 to
SE1
V
SE1
Upper boundary of the first skipped band:
-
If frequency output:
SE1
to 500Hz
-
If voltage output:
SE1
to 10V
Si2
Lower boundary of the second skipped band:
-
If frequency output: 0 to
SE2
Hz
-
If voltage output: 0.0 to
SE2
V
SE2
Upper boundary of the second skipped band:
-
If frequency output:
SE2
to 500Hz
-
If voltage output:
SE2
to 10V
Si3
Lower boundary of the third skipped band:
-
If frequency output: 0 to
SE3
Hz
-
If voltage output: 0.0 to
SE3
V
SE3
Upper boundary of the third skipped band:
-
If frequency output:
SE3
to 500Hz
-
If voltage output:
SE3
to 10V
15.15 OUTPUT CONFIGURATION
tbA
Alarm relay deactivation:
n; Y
oA1
Relay output (16 A):
-
nu
=output not used
-
onF
=output activated when controller in ON
-
ALr
=alarm output
-
Fn1
=ventilator output
-
dGt
=Digital Scroll output
-
d4d
=Digital Stream (4 cylinder) output
-
inV
=Inverter output
-
CP1
=ONOFF compressor output
oA2
Relay output (5 A) (only for XC35CX models):
-
nu
=output not used
-
onF
=output activated when controller in ON
-
ALr
= alarm output
-
Fn2
= ventilator output
-
CP2
= ONOFF compressor output
oA3
TRIAC output (MAX 2.2 A):
-
nu
=output not used
-
onF
=output activated when controller in ON
-
ALr
=alarm output
-
PCF
=phase-cut controlled output
-
dGt
=Digital Scroll discharge valve control
-
d4d
= Digital Stream discharge valve control