Open collector output settings
(continued)
Table 1-5:
Settings
Description
Pulse output Pulse
width
Unless otherwise stated, pulses are 50% duty cycle for required frequency.
A pulse rate retransmit output generates 100 to 130
μ
s pulses at the falling
edge of every input pulse.
Pulse output maxi-
mum frequency
5 kHz, pulse width at 50% duty cycle.
If the programming of the outputs would exceed 5 kHz, the meter dis-
playsPULSE OVERRNG
Quadrature output
Output set to quadrature lags the other pulse output by 90° (1/4 duty cycle)
at output frequency. Minimum 1 Hz
Timer output
Programmable on and off time, repeating cycle. Minimum period 0.1 sec-
ond, maximum 100,000 seconds. Minimum pulse time 0.01 second, maxi-
mum 10,000 seconds.
1.7
Serial communication settings
The settings below are serial communication specifications for the Internal Display. Except
when noted, all specifications apply to operation at +25°C (+77°F).
Serial communication settings
Table 1-6:
Settings
Description
Protocol
2-Wire RS-485 Modbus
®
RTU
Meter address/slave
ID
1 - 247
Baud rate
1,200; 4,800; 9,600; 19,200; 38,400; 57,600; or 115,200 bps
Transmit time delay
Programmable between 0 and 199 ms
Parity/Stop it
Even, odd, none with 1 stop bit, or none with 2 stop bits
Byte-to-byte timeout Max of 1.5 character times or 750
μ
s
Note: Refer to Modbus Register Tables at www.predig.com for details.
1.8
Default settings for startup of Internal Display
Internal Display factory settings are shown in the table below.
Default settings for startup
Table 1-7:
Parameter
Display
Default setting
Input type
INPUT
Active
K - Factor units
FUN IT
Pulses/gallon
Introduction
10
LTM Internal Display
Содержание Daniel 1200 Series
Страница 8: ......
Страница 12: ...Contents iv LTM Internal Display ...
Страница 14: ...Plan 2 LTM Internal Display ...
Страница 33: ...Open collector output connections Figure 3 13 Product connections User manual 21 ...
Страница 34: ...Product connections 22 LTM Internal Display ...
Страница 35: ...Part II Install Install User manual 23 ...
Страница 36: ...Install 24 LTM Internal Display ...
Страница 38: ...Installation requirements and limitations 26 LTM Internal Display ...
Страница 40: ...Operate 28 LTM Internal Display ...
Страница 64: ...Setting the toggle time TIME Figure 5 20 Setup and programming 52 LTM Internal Display ...
Страница 98: ...Product advanced features 86 LTM Internal Display ...
Страница 106: ...Startup procedure 94 LTM Internal Display ...
Страница 107: ...Part IV Maintain Maintain User manual 95 ...
Страница 108: ...Maintain 96 LTM Internal Display ...
Страница 113: ...Maintenance User manual 101 ...