to display spectral and analysis parameter data and to configure spectral data
acquisition settings. You can import spectral data to AMS Machinery Manager for further
analysis.
Note
You must have the Advanced Diagnostics application license to view this feature. For more
information on the Advanced Diagnostics application, see
Spectra
Figure 2-33:
The Fmax settings define the default frequency range of the thumbnail spectra for Velocity
and PeakVue. If you enable the Average Velocity option in AMS Machinery Manager, you
can configure the high-resolution Velocity Analytical spectrum to return 400 or 800 lines
of resolution, with averaging. If the Average Velocity option is not enabled in AMS
Machinery Manager, the spectrum is calculated at 1600 lines of resolution, with no
averaging.
When vibration data is acquired, a PeakVue waveform is sampled for 3.2 seconds. If you
set the PeakVue True Fmax to 1000 Hz, the first 1.6 seconds of the PeakVue waveform is
used for the analytical spectrum. If you set the Fmax to 500 Hz, the entire 3.2 second
PeakVue waveform is used to calculate the analytical spectrum. Regardless of what you
choose in Fmax, the overall PeakVue trend parameter is calculated over the entire 3.2
second waveform.
Configuration
52
MHM-97408, Rev 15
Содержание CSI 9420
Страница 4: ......
Страница 10: ...Revision numbers in AMS Device Manager Figure 1 2 Introduction 4 MHM 97408 Rev 15 ...
Страница 60: ...PeakVue spectrum Figure 2 35 Configuration 54 MHM 97408 Rev 15 ...
Страница 92: ...Setup 86 MHM 97408 Rev 15 ...
Страница 98: ...Velocity waveform Figure 5 1 PeakVue waveform Figure 5 2 Velocity PeakVue and temperature 92 MHM 97408 Rev 15 ...
Страница 134: ...Product certifications 128 MHM 97408 Rev 15 ...
Страница 144: ...LCD screen messages 138 MHM 97408 Rev 15 ...